Delta
DVP Ethernet
Supoort Series: DELTA DVP20/32/40/60ES200RE/200TE or any DVP models with built-in Ethernet port, DELTA DVPEN01-SL module
1)V-BOX Settings
Items | Settings | Note |
---|---|---|
Protocol | DELTA DVP MODBUS TCP | |
Connection | Ethernet | |
Port No. | 502 | |
Device No. | 1 | |
VBox Device No. | 0 |
2)Address List
Type | Device registers | VBox registers | Format | Range | Note |
---|---|---|---|---|---|
Bit | X | X | X OOO | 0~377 | |
Bit | Y | Y | Y OOO | 0~377 | |
Bit | M0 | M0 | M0DDDD | 0~1535 | |
Bit | M1 | M1 | M1DDDD | 1536~4096 | |
Bit | T | T | TDDD | 0~255 | |
Bit | C | C | CDDD | 0~255 | |
Bit | S | S | SDDDD | 0~1023 | |
Word | D0 | D0 | D0DDDD | 0~4095 | |
Word | D1 | D1 | D1DDDD | 4096~11999 | |
Word | T | T | TDDD | 0~255 | |
Word | C | C | CDDD | 0~199 | |
Double Word | HC | HC | HCDDD | 200~255 |
3) PLC Setting:
1. Create new project in Delta WPL Soft, and click Setting to open the communication settings:
2. Set up the communication type and PLC IP:
3. Click OK and save the settings. Then click Communication on toolbar, then click Transfer Setup to open new window:
4. Select Communication Mode as PC => PLC to download or select PC <=PLC to upload:
5. Click Auto-Search Ethernet Module to find the PLC on the same LAN network:
4) V-BOX Setting:
Set the same IP address according to the setting from WPL Soft:
DVP serial
Supoort Series: DELTA DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX
1)V-BOX Settings
Items | Settings | Note |
---|---|---|
Protocol | DELTA DVP PROTOCOL | |
Connection | RS232 | |
Baud Rate | 9600 | |
Stop Bit | 1 | |
Data Bit | 7 | |
Parity | EVEN | |
Device No. | 1 |
2)Address List
Type | Device registers | VBox registers | Format | Range | Note |
---|---|---|---|---|---|
Bit | X | X | X OOOOOO | 0~303237 | |
Bit | Y | Y | Y OOOOOO | 0~303237 | |
Bit | M | M | MDDDDD | 0~99999 | |
Bit | T | T | TDDDDD | 0~99999 | |
Bit | C | C | CDDDDD | 0~99999 | |
Bit | S | S | SDDDDD | 0~99999 | |
Word | D | D | D DDDDD | 0~99999 | |
Word | T | T | TDDDDD | 0~99999 | |
Word | C | C | CDDD | 0~199 | |
Double Word | C | C | CDDDDD | 200~99999 |
3)Wiring Diagram
AS Ethernet
1)V-BOX Settings
Items | Settings | Note |
---|---|---|
Protocol | DELTA AS300 MODBUS TCP | |
Connection | Ethernet | |
Port No. | 502 | |
Device No. | 1 | |
HMI No. | 0 |
2)Address List
Type | Device registers | HMI registers | Format | Range | Note |
Bit | X | X | X d | 0~63 | |
Bit | Y | Y | Y d | 0~63 | |
Bit | D | D | D d | 0~29999 | |
Bit | M | M | M d | 0~8191 | |
Bit | SM | SM | SM d | 0~4095 | |
Bit | S | S | S h | 0~2047 | |
Bit | T | T | T d | 0~511 | |
Bit | C | C | C d | 0~511 | |
Bit | HC | HC | HC d | 0~255 | |
Word | X | X | X h | 0~63 | |
Word | Y | Y | Y d | 0~63 | |
Word | SR | SR | SR d | 0~2047 | |
Word | D | D | D d | 0~29999 | |
Word | T | T | T d | 0~511 | |
Word | C | C | C h | 0~511 | |
Word | E | E | E d | 0~9 |
3)Configure the communication protocol
4)Cable Wiring
Figure
Pin Definition Diagram