Show last authors
1 = **RTU Slave ** =
2
3 Supported series: EC10 series
4
5 **1)V-BOX setting**
6
7 |**Items**|**Settings**|**Note**
8 |Protocol|Emerson 984 RTU Slave MODBUS|
9 |Connection|RS485|
10 |Baud rate|19200|
11 |Data bit|8|
12 |Parity|EVEN|
13 |Stop bit|1|
14 |Device station No.|1|Need to be same as the PLC setting
15
16 **2)PLC Setting**
17
18 Remember to use the Control Star to enable the Modbus RTU communication for port 1 in system block before dowload into PLC.
19
20 (% style="text-align:center" %)
21 [[image:ControlStarSystemBlock.png]]
22
23 (% style="text-align:center" %)
24 [[image:ControlStarCommunicate.png]]
25
26 (% style="text-align:center" %)
27 [[image:ControlStarModbus.png]]
28
29 **3)Address List**
30
31 |**Type**|**Device registers**|**Format**|**Range**|**Note**
32 |(% colspan="1" rowspan="12" %)Bit|Y|YOOO|0~~377|
33 |X|XOOO|0~~377|
34 |M0|M0DDDD|0~~2047|
35 |M1|M1DDDDD|2048~~10239|
36 |SM0|SM0DDD|0~~255|
37 |SM1|SM1DDD|256~~511|
38 |S0|S0DDDD|0~~1023|
39 |S1|S1DDDD|1024~~4095|
40 |T0|T0DDD|0~~255|
41 |T1|T1DDD|256~~511|
42 |C0|C0DDD|0~~255|
43 |C1|C1DDD|256~~306|
44 |(% colspan="1" rowspan="7" %)Word|D|DDDDD|0~~7999|
45 |Z|ZDD|0~~15|
46 |TW0|TW0DDD|0~~255|
47 |TW1|TW1DDD|256~~511|
48 |SD0|SD0DDD|0~~255|
49 |SD1|SD1DDD|256~~511|
50 |CW|CWDDD|0~~306|
51 |(% colspan="1" rowspan="2" %)Double Word|CW0|CW0DDD|200~~255|
52 |CW1|CW1DDDDD|256~~99999|
53
54 **4) Cable Wiring**