Mitsubishi
FX3U,3G,3GA Serial
Supported Series: Mitsubishi FX3U, FX3G, FX3GA series
V-BOX Settings
Item | Settings | Note |
Protocol | Mitsubishi FX3U/3G/3GA | |
Connection | RS422/RS485/RS232 | |
Baud rate | 9600~115200 | |
Data bit | 7/8 | |
Parity | EVEN/Odd/None | |
Stop bit | 1/2 | |
PLC station No. | 1~255 |
Address List
Type | Device registers | Format | Range | Note |
Bit | X | Xo | 0~303237 | |
Y | Y o | 0~303237 | ||
M | M d | 0~99999 | ||
T | T d | 0~99999 | ||
C | C d | 0~99999 | ||
S | S d | 0~99999 | ||
SM | SM d | 8000~9999 | ||
Word | X | Xo | 0~303237 | |
Y | Y o | 0~303237 | ||
M | M d | 0~99999 | ||
T | T d | 0~99999 | ||
C | C d | 0~199 | ||
D | D d | 0~7999 | ||
S | S d | 0~99999 | ||
SD | SD d | 8000~9999 |
PLC Setting
Open GX Works2, create a new PLC project or open the project that has been created.
Create new project: [Project]→[New]→[Series] FXCPU→[Type] FX3G/FX3GC→[OK].
PLC Default Parameters:
[Connection type]RS422;[Baud rate]9600, [Data bit]7, [Stop bit]1,[Parity]EVEN; [Station number]0
Note:The serial port parameters should be set depending on field requirements
PC and PLC connection:
[All connection]→[Connection 1]→[Transfer Setup Connection1]→[Serial USB]→RS-232C: PC and PLC are connected by USB to RS232 adapter,choose corresponding [COM Port]COM 5 →[Transmission speed]9.6Kbps→[setup] →[Parity]EVEN→[Data bits]7→[Stop bits]1→[OK]
Connection test:when connection is OK,the GX Works2 prompts “Successfully connected with the FX3G/FX3GCCPU.”
Cable Wiring
RS422
FX NOPROTOCOL
Mitsubishi FX3G-RS232-BD
V-Box Settings
Item | Settings | Note |
---|---|---|
Protocol | Mitsubishi FX NOPROTOCOL | |
Connection | RS232 | |
Baud rate | 9600 | |
Data bit | 7 | |
Parity | EVEN | |
Stop bit | 1 | |
PLC station No. | 0 |
Address List
Type | Device registers | Format | Range | Note |
---|---|---|---|---|
Bit | X | X o | 0~303237 | |
Y | Y o | 0~303237 | ||
M | M d | 0~99999 | ||
T | T d | 0~99999 | ||
C | C d | 0~99999 | ||
S | S d | 0~99999 | ||
SM | SM d | 8000~9999 | ||
Lamp | Lamp d | 0~0 | ||
Word | X | X o | 0~303237 | |
Y | Y o | 0~303237 | ||
M | M d | 0~99999 | ||
T | T d | 0~99999 | ||
C | C d | 0~199 | ||
D | D d | 0~7999 | ||
S | S d | 0~99999 | ||
SD | SD d | 8000~9999 |
Cable Wiring
FX3U Ethernet
Supported Modules: FX3U-ENET-ADP, FX3U-ENET-L
V-BOX Settings
Items | Settings | Note |
Protocol | Mitsubishi FX3U | |
Connection | Ethernet | |
Port No. | 5009 | Must be the same as the PLC setting |
PLC station No. | 0 |
Address List
Type | Device registers | Format | Range | Note |
Bit | X | X OOO | 0~377 | |
Y | Y OOO | 0~377 | ||
M | M DDDD | 0~7679 | ||
SM | SM DDDD | 8000~8511 | ||
S | S DDDD | 0~4095 | ||
TS | TS DDD | 0~511 | ||
CS | CS DDD | 0~255 | ||
Word | CN | CN DDD | 0~199 | |
TN | TN DDD | 0~511 | ||
D | D DDDD | 0~7999 | ||
SD | SD DDDD | 8000~8511 | ||
R | R DDDDD | 0~32767 |
Ethernet Module Settings
FX3U-ENET-L module configuration
Set up the FX3U-ENET-L Ethernet module settings as follows.
Select the module location, which in this document is Module 0.
Select "Operational setting" to enter the following screen.
The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
Select "Open setting" to enter the setting interface, the settings are as follows.
The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
Click on "transter setup" - "PC side I/F setting", see the following figure.
After setting, the first download must use the programming cable, as shown in the figure; after that, can
use the IP set in the "Ethernet board" to communicate directly with the network cable.
Read and write data from the Ethernet module
Set "Transter setup" to COM communication, and read or write operation as shown below
PLC Settings (GX Works 2)
Create a blank FX5U project
Find Current Connection in the navigation
Select Connection Channel List
Select Ethernet board communication
Select Ethernet Module
Set the IP address of the PLC
Read or write PLC data, in this document is read
FX5U Serial
Mitsubishi FX5U series PLC
V-BOX Settings
Item | Settings | Note |
Protocol | Mitsubishi FX5U | |
Connection | RS422/RS485 | |
Baud rate | 9600 | |
Data bit | 7 | |
Parity | Odd | |
Stop bit | 1 | |
PLC station No. | 1~255 | Need to be the same as PLC settings |
Address List
Type | Device registers | Format | Range | Note |
Bit | X | X o | 0~303237 | |
Y | Y o | 0~303237 | ||
M | M d | 0~99999 | ||
B | B h | 0~7FFF | ||
F | F d | 0~32767 | ||
SB | SB h | 0~7FFF | ||
TS | TS d | 0~1023 | ||
TC | TC d | 0~1023 | ||
STS | STS d | 0~1023 | ||
STC | STS d | 0~1023 | ||
CS | CS d | 0~1023 | ||
CC | CC d | 0~1023 | ||
SM | SM d | 0~9999 | ||
L | L d | 0~32767 | ||
S | S d | 0~4095 | ||
Word | W | W h | 0~3FF | |
TN | TN d | 0~1023 | ||
STN | STN d | 0~1023 | ||
CN | CN d | 0~1023 | ||
R | R d | 0~32767 | ||
SW | SW h | 0~7FFF | ||
Z | Z d | 0~23 | ||
D | D d | 0~7999 | ||
SD | SD d | 0~11999 |
PLC Settings (GX Works 3)
Create a blank FX5U project
Find the 485 serial port module in the system navigation bar and double click to enter the settings.
Select protocol in the setting item, and set parameters.
Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
Click the [Apply] button to finish the setting.
Click download and select the items as below, then click [execute] to download the configuration to PLC.
As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
Done.
Cable Wiring
RS422
FX5U Ethernet
Mitsubishi FX5U series PLC
V-BOX Settings
Items | Settings | Note |
Protocol | Mitsubishi FX5U | |
Connection | Ethernet | |
Port No. | 5002 | Must be the same as the PLC setting |
PLC station No. | 0 |
Address List
Type | Device registers | V-Box register | Format | Range | Note |
Bit | X | X | X o | 0~303237 | |
Y | Y | Y o | 0~303237 | ||
M | M | M d | 0~99999 | ||
B | B | B h | 0~7FFF | ||
F | F | F d | 0~32767 | ||
SB | SB | SB h | 0~7FFF | ||
TS | TS | TS d | 0~1023 | ||
TC | TC | TC d | 0~1023 | ||
STS | STS | STS d | 0~1023 | ||
STC | STC | STS d | 0~1023 | ||
CS | CS | CS d | 0~1023 | ||
CC | CC | CC d | 0~1023 | ||
SM | SM | SM d | 0~9999 | ||
L | L | L d | 0~32767 | ||
S | S | S d | 0~4095 | ||
Word | W | W | W h | 0~3FF | |
TN | TN | TN d | 0~1023 | ||
STN | STN | STN d | 0~1023 | ||
CN | CN | CN d | 0~1023 | ||
R | R | R d | 0~32767 | ||
SW | SW | SW h | 0~7FFF | ||
Z | Z | Z d | 0~23 | ||
D | D | D d | 0~7999 | ||
SD | SD | SD d | 0~11999 |
PLC Settings (GX Works 3)
Find the [Ethernet port] in the navigation area.
Select [Own Node Settings] in the [Setting Item List];
Set [IP Address], [Subnet Mask], [Default Gateway];
Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows;
Select [SLMP Connection Module] and add into host station as below picture shows;
Set Port number as 5002 (this is necessary settings);
Click [Close with Reflecting the Setting] to save and close window;
Click [Apply] to completed Etherenet settings;
Switch to the [On line data operation] interface as below, check the item and click [Execute] to download.
Cable Wiring
L02 Serial
Mitsubishi L02 series CPU built-in serial port.
V-BOX Settings
Item | Settings | Note |
Protocol | Mitsubishi L02 | |
Connection | RS422 | |
Baud rate | 115200 | |
Data bit | 8 | |
Parity | Odd | |
Stop bit | 1 | |
PLC station No. | 1~255 | Need to be the same as PLC settings |
Address List
Type | Device registers | HMI registers | Format | Range | Note |
Bit | X | X | X h | 0~FFFF | |
Y | Y | Y h | 0~FFFF | ||
M | M | M d | 0~9999 | ||
L | L | L d | 0~9999 | ||
F | F | F d | 0~9999 | ||
B | B | B h | 0~FFFF | ||
V | V | V d | 0~2047 | ||
TC | TC | TC d | 0~9999 | ||
SS | SS | SS d | 0~9999 | ||
SC | SC | SC d | 0~9999 | ||
CS | CS | CS d | 0~9999 | ||
CC | CC | CC d | 0~9999 | ||
SB | SB | SB h | 0~FFFF | ||
SM | SM | SM d | 0~2047 | ||
STS | STS | STS d | 0~1023 | ||
S | S | S d | 0~9999 | ||
DX | DX | DX h | 0~FFFF | ||
DY | DY | DY h | 0~FFFF | ||
TS | TS | TS d | 0~9999 | ||
Dbit | Dbit | Dbit d.d | 0~99999.0~15 | ||
Word | W | W | W h | 0~FFFF | |
TN | TN | TN d | 0~99999 | ||
SN | SN | SN d | 0~99999 | ||
CN | CN | CN d | 0~99999 | ||
R | R | R d | 0~99999 | ||
SW | SW | SW h | 0~FFFF | ||
Z | Z | Z d | 0~99999 | ||
ZR | ZR | ZR h | 0~FFFF | ||
D | D | D d | 0~99999 |
Cable Wiring
RS422
L02 Ethernet
Mitsubishi L series CPU built-in Ethernet port.
V-BOX Settings
Items | Settings | Note |
Protocol | MIT L02 CPU MELSEC | |
Connection | Ethernet | |
Port No. | 1025 | Must be the same as the PLC setting |
PLC station No. | 0 | Must be the same as the PLC setting |
PLC Settings (GX Works2 )
Create a project
Set PLC IP, subnet mask and gateway;
Select [Binary Code] as communication data code;
Set PLC port number, for example 1025
Save settings;
Download project into PLC device;
Restart PLC device;
Cable Wiring
Q12H Serial
This Demo shows V-BOX communicate with Q12H PLC by Q02H serial Protocol
QJ71E71 Ethernet
Mitsubishi QJ71E71 Ethernet communication module;
V-BOX Settings
Items | Settings | Note |
Protocol | MIT QJ71E71 MELSEC | |
Connection | Ethernet | |
Port No. | 1025 | Must be the same as the PLC setting |
PLC station No. | 0 | Must be the same as the PLC setting |
Address List
Type | Device registers | HMI registers | Format | Range | Note |
Bit | X | X | X h | 0~1FFF | |
Y | Y | Y h | 0~1FFF | ||
M | M | M d | 0~99999 | ||
L | L | L d | 0~8191 | ||
F | F | F d | 0~2047 | ||
B | B | B h | 0~1FFF | ||
V | V | V d | 0~2047 | ||
TS | TS | TS d | 0~2047 | ||
TC | TC | TC d | 0~2047 | ||
SS | SS | SS d | 0~2047 | ||
SC | SC | SC d | 0~2047 | ||
CS | CS | CS d | 0~1023 | ||
CC | CC | CC d | 0~1023 | ||
SB | SB | SB h | 0~7FF | ||
S | S | S d | 0~8191 | ||
DX | DX | DX h | 0~1FFF | ||
DY | DY | DY h | 0~1FFF | ||
SM | SM | SM d | 8000~9999 | ||
Word | SD | SD | SD d | 0~2047 | |
D | D | D d | 0~12287 | ||
W | W | W h | 0~1FFF | ||
TN | TN | TN d | 0~2047 | ||
SN | SN | SN d | 0~2047 | ||
CN | CN | CN d | 0~1023 | ||
R | R | R d | 0~32767 | ||
SW | SW | SW h | 0~7FF | ||
Z | Z | Z d | 0~15 | ||
ZR | ZR | ZR h | 0~FE7FF |
PLC Settings(GX Works2)
- Click [Ethernet/CC IE/MELSECNET];
- Please select [Ethernet] as network type;
- Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
- Select [Online] as Mode;
- Click [Operation setting] to set IP;
- Select [Binary Code] as [Communication Data Code];
- Click [Open setting]
- Set protocol: TCP;
- Set [unpassive] in [Open system];
- Set [receive] in [Fixed buffer];
- Set [procedure Exist] in [Fixed buffer communication];
- Disable [Pairing open];
- Set [No confirm] in [Existence confirmation];
- Host station port number: 5009;
- Save settings;
- Download project into PLC and restart it
Cable Wiring