1 += {{id name="HSiemens"/}}**Siemens ** =
2 +
3 +== {{id name="HS7-200SmartA0Ethernet"/}}**S7-200 Smart Ethernet ** ==
4 +
5 +[[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20S7-200%20Smart.zip]]
6 +
7 +== {{id name="HS7-300Ethernet"/}}**S7-300 Ethernet ** ==
8 +
9 +Supported Series: Siemens S7-300 series PLC
10 +
11 +**1)V-BOX setting**
12 +
13 +|**Items**|**Settings**|**Note**
14 +|Protocol|Simens S7-300 Ethernet|
15 +|Connection|Ethernet|
16 +|Port No.|102|
17 +|PLC station No.|2|Need to be same as the PLC setting
18 +
19 +**2)Address List**
20 +
21 +|**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
22 +|(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
23 +|Q|Q|Q ddddd.o|0.0~~99999.7|
24 +|M|M|M ddddd.o|0.0~~99999.7|
25 +|DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
26 +nn: block number;
27 +
28 +dddd: address;
29 +)))
30 +|(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
31 +|Q|QW|QW ddddd|0~~99999|
32 +|(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
33 +|MW|MW ddddd|0~~99999|(((
34 +MW0=MB(0~~1)
35 +
36 +MW2=MB(2~~3)
37 +
38 +Address value is a multiple of 2
39 +)))
40 +|MD|MD ddddd|0~~99999|(((
41 +MD0=MB(0~~3)
42 +
43 +MD4=MB(4~~7)
44 +
45 +Address value is a multiple of 4
46 +)))
47 +|(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
48 +nn: block number;
49 +
50 +dddd: address
51 +)))
52 +|DBxDBW|DBxDBW nndddd|0~~99999999
53 +|DBxDBD|DBxDBD nndddd|0~~99999999
54 +
55 +**3)Configure the communication protocol**
56 +
57 +{{id name="Iimage-20220824161345-1.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_8e00ed9483ddb629.png||alt="image-20220824161345-1.png" height="1011" width="1920"]]
58 +
59 +**4)Cable Wiring**
60 +
61 +{{id name="Iimage-20220824161450-2.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ac8ece9a26719fda.png||alt="image-20220824161450-2.png" height="170" width="401"]]
62 +
63 +== {{id name="HS7-1200A0Ethernet"/}}**S7-1200 Ethernet ** ==
64 +
65 +[[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]]
66 +
67 +== {{id name="HS7-XXXEthernetl"/}}**S7-XXX Ethernet l** ==
68 +
69 +Supported Series: Siemens S7-400, S7-1200 and S7-1500
70 +
71 +**1)V-BOX setting**
72 +
73 +|=**Items**|=**Settings**|=**Note**
74 +|Protocol|Siemens S7-XXX|
75 +|Connection|Ethernet|
76 +|Port No.|102|
77 +|Device No.|Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|
78 +|HMI No.|Rack (Default as 0)|
79 +
80 +Slot from TIA Portal is equal to Device No. of V-net
81 +
82 +Rack from TIA Portal is equal to HMI No. of V-net
83 +
84 +{{id name="Iimage-20220824162459-3.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d78bc267e5fc6394.png||alt="image-20220824162459-3.png" height="503" width="798"]]
85 +
86 +{{id name="Iimage-20220824163305-2.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_c9ae84ef5d418580.png||alt="image-20220824163305-2.png" height="1009" width="1920"]]
87 +
88 +**2)Address List**
89 +
90 +|**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
91 +|(% rowspan="4" %)Bit|I|I|M d.o|(((
92 +d:0~-~-9999
93 +
94 +o:0-7
95 +)))|
96 +|Q|Q|Q d.o|(((
97 +d:0~-~-9999
98 +
99 +o:0-7
100 +)))|
101 +|M|M|M d.o|(((
102 +d:0~-~-9999
103 +
104 +o:0-7
105 +)))|
106 +|DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
107 +nn:0-9999,
108 +
109 +dddd:0-9999,
110 +
111 +o:0-7
112 +)))|(((
113 +nn:DB No.
114 +
115 +dddd:address value
116 +
117 +o: digit address
118 +)))
119 +|(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
120 +|M|MW|MW d|d:0-99999|(((
121 +MW0=MB(0~~1)
122 +
123 +MW2=MB(2~~3)
124 +
125 +Address value is a multiple of 2
126 +)))
127 +|M|MD|MD d|d:0-99999|(((
128 +MD0=MB(0~~3)
129 +
130 +MD4=MB(4~~7)
131 +
132 +Address value is a multiple of 4
133 +)))
134 +|I|IW|IW d|d:0-99999|
135 +|Q|QW|QW d|d:0-99999|
136 +|DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
137 +nn:0-9999
138 +
139 +dddd:0-9999
140 +)))|(((
141 +nn:DB No.
142 +
143 +dddd:address value
144 +)))
145 +|DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
146 +nn:0-9999
147 +
148 +dddd:0-9999
149 +)))|(((
150 +nn:DB No.
151 +
152 +dddd:address value
153 +
154 +Address value is a multiple of 2
155 +)))
156 +|DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
157 +nn:0-9999
158 +
159 +dddd:0-9999
160 +)))|(((
161 +nn:DB No.
162 +
163 +dddd:address value
164 +
165 +Address value is a multiple of 4
166 +)))
167 +
168 +**3)Configure the communication protocol**
169 +
170 +{{id name="Iimage-20220824163448-3.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_9e740a8bf83ea3bf.png||alt="image-20220824163448-3.png" height="557" width="974"]]
171 +
172 +**✎Note:**
173 +
174 +* The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three V-BOX.
175 +* V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
176 +
177 +**4)Cable Wiring**
178 +
179 +{{id name="Iimage-20220824162342-2.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ac8ece9a26719fda.png||alt="image-20220824162342-2.png" height="170" width="401"]]
180 +
181 +== {{id name="HLOGOEthernet"/}}**LOGO Ethernet ** ==
182 +
183 +Supported Series: Siemens Logo 0BA0, 0BA1 series
184 +
185 +**V-BOX Settings**
186 +
187 +|**Items**|**Settings**|**Note**
188 +|Protocol|Siemens LOGO|
189 +|Connection|Ethernet|
190 +|Port No.|102|
191 +|PLC station No.|2|
192 +
193 +**Address List**
194 +
195 +|**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
196 +|1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
197 +|2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
198 +|3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
199 +|4|VW|Word|0-1468|DB1.DBX0.0|0x000000
200 +|5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
201 +|6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
202 +|7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
203 +|8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
204 +|9|AI|Word|1-16|DB1.DBX1032.0|0x002040
205 +|10|I|Bit|1-64|DB1.DBX1024.0|0x002000
206 +|11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
207 +|12|M|Bit|1-112|DB1.DBX1104.0|0x002280
208 +|13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
209 +|14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
210 +|15|V|Bit|0-14697|DB1.DBX0.0|0x000000
211 +
212 +**PLC Settings in LOGO Software:**
213 +
214 +Click [Tools]~-~-[Ethernet Connections],shown as below.
215 +
216 +{{id name="IPIStudio.125C.PLCprotocols.WebHome4012.PLCProtocol_html_8b9d2322edf89519.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d13df637bfedcc52.png||alt="12.PLC Protocol_html_8b9d2322edf89519.png" height="641" width="423"]]
217 +
218 +Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
219 +
220 +{{id name="IPIStudio.125C.PLCprotocols.WebHome40image-20221228142937-4.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_316247e0130c4c55.png||alt="image-20221228142937-4.png" height="484" width="366"]]
221 +
222 +**TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
223 +
224 +{{id name="IPIStudio.125C.PLCprotocols.WebHome40image-20221228143047-5.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_facc6ee1af05162f.png||alt="image-20221228143047-5.png" height="626" width="1088"]]
225 +
226 + **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
227 +
228 +{{id name="IPIStudio.125C.PLCprotocols.WebHome40image-20221228143246-6.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d43d2b7b2599ee64.png||alt="image-20221228143246-6.png" height="698" width="688"]]
229 +
230 +**V-BOX Communication Settings**
231 +
232 +Set PLC IP in [IP Address] settings;
233 +
234 +{{id name="ILldwDGntf4.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ab570912d299c09.png||alt="LldwDGntf4.png" height="530" width="899"]]
235 +
236 +Enable V-BOX Ethernet in [Network];
237 +
238 +{{id name="IWgvjfWbQif.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_637860db3ca1ca1b.png||alt="WgvjfWbQif.png" height="654" width="1195"]]
239 +
240 +TSAP setting
241 +
242 +* The initialization script needs to set the source TSAP address and the target TSAP address, otherwise the communication will not be successful.
243 +
244 +**function** **init**.main()
245 + addr_setword("@W_0#HSW1200",8192) //~-~- Set the source TSAP address//
246 + addr_setword("@W_0#HSW1201",4096) //~-~- Set the destination TSAP address//
247 + **end**
248 +
249 +Note: The name of the test script is init, 8192 and 4096 are the data used for the test, there is no HSW address in the register option, but you can directly set the value of the corresponding address through the code.
250 +
251 +**✎Note:**
252 +
253 +* **Communication port configuration: **
254 +** Continuous length needs to be set to 0.
255 +** Integration interval needs to be set to 1. (no change may result in data errors)
256 +** Set Port and Device Station NO.
257 +** Other set as defaulted.
258 +* **Notes on the use of registers:**
259 +** Register VD: Use only registers that are multiples of 4, such as 0, 4, 8, etc.
260 +** Register VW: Use only registers thay are multiples of 2, such as 0, 2, 4 etc. (Using an odd-length register may result in data errors, such as 2 3 4 )