Wiki source code of Siemens

Last modified by Joe on 2024/04/30 15:38

Show last authors
1 == **S7-200 Smart Serial** ==
2
3 **V-BOX setting**
4
5 (% style="width:1323.87px" %)
6 |**Items**|**Settings**|**Note**
7 |Protocol|(% style="width:783px" %)Siemens S7-200 CPU22x/Smart PPI|
8 |Connection|(% style="width:783px" %)RS485|
9 |Baud rate|(% style="width:783px" %)9600|
10 |Data bit|(% style="width:783px" %)8|
11 |Parity|(% style="width:783px" %)EVEN|
12 |Stop bit|(% style="width:783px" %)1|
13 |PLC station No.|(% style="width:783px" %)2|
14
15 (% style="text-align:center" %)
16 [[image:西门子200串口.png]]
17
18 **Address List **
19
20 |**Type**|**Device register**|**Format**|**Range**|**Note**
21 |(% rowspan="9" %)Bit|I|I ddddd.o|0.0~~99999.7|
22 |Q|Q ddddd.o|0.0~~99999.7|
23 |V|VWbit ddddd.o|0.0~~99999.7|
24 |V|V ddddd.o|0.0~~99999.7|
25 |M|M ddddd.o|0.0~~99999.7|
26 |SM|ddddd.o|0.0~~99999.7|
27 |S|ddddd.o|0.0~~99999.7|Read only
28 |T|ddddd|0~~99999|Timer state, read only
29 |C|ddddd|0~~99999|Counter state, read only
30 |(% rowspan="12" %)Word|I|IW ddddd|0~~99999|
31 |Q|QW ddddd|0~~99999|
32 |AI|AIW ddddd|0~~99999|
33 |AQ|VB ddddd|0~~99999|
34 |V|VW ddddd|0~~99998|(((
35 VW0=VB (0~~1)
36
37 VW2=VB (2~~3)
38
39 Address value is a multiple of 2
40 )))
41 |V|VD ddddd|0~~99998|(((
42 VD0=VB (0~~3)
43
44 VD2=VB (4~~7)
45
46 Address value is a multiple of 4
47 )))
48 |M|MB ddddd|0~~99999|
49 |M|MW ddddd|0~~99999|(((
50 MW0=MB(0~~1)
51
52 MW2=MB(2~~3)
53
54 Address value is a multiple of 2
55 )))
56 |M|MD ddddd|0~~99999|(((
57 MD0=MB(0~~3)
58
59 MD4=MB(4~~7)
60
61 Address value is a multiple of 4
62 )))
63 |T|TW ddddd|0~~99999|Value of timer
64 |C|CW ddddd|0~~99999|Value of counter
65 |W|SW ddddd|0~~99999|
66
67 **PLC setting**
68
69 (% style="text-align:center" %)
70 [[image:西门子软件版本.png]]
71
72 (% style="text-align:center" %)
73 [[image:485通讯配置.png]]
74
75 **Connect and Download**
76
77 (% style="text-align:center" %)
78 [[image:以太网 PC和PLC连接.png]]
79
80 (% style="text-align:center" %)
81 [[image:以太网下载.png]]
82
83 **Cable Wiring**
84
85 (% style="text-align:center" %)
86 [[image:485接线.png]]
87
88 == **S7-200 Smart Ethernet ** ==
89
90 **V-BOX setting**
91
92 |**Items**|**Settings**
93 |Protocol|Siemens S7-200 Smart(Ethernet)
94 |Connection|Ethernet
95 |Port No.|102
96 |PLC station No.|2
97
98 (% style="text-align:center" %)
99 [[image:西门子200smart 以太网.png]]
100
101 **PLC setting**
102
103 (% style="text-align:center" %)
104 [[image:西门子软件版本.png]]
105
106 (% style="text-align:center" %)
107 [[image:以太网通讯配置.png]]
108
109 **Connect and Download**
110
111 (% style="text-align:center" %)
112 [[image:以太网 PC和PLC连接.png]]
113
114 (% style="text-align:center" %)
115 [[image:以太网下载.png]]
116
117 **Cable Wiring**
118
119 V-Box : RJ45 Ethernet interface
120
121 PLC : RJ45 Ethernet interface
122
123 (% style="text-align:center" %)
124 [[image:以太网连接.png]]
125
126 == **S7-300 Ethernet ** ==
127
128 Supported Series: Siemens S7-300 series PLC
129
130 **V-BOX setting**
131
132 |**Items**|**Settings**|**Note**
133 |Protocol|Simens S7-300 Ethernet|
134 |Connection|Ethernet|
135 |Port No.|102|
136 |PLC station No.|2|Need to be same as the PLC setting
137
138 **Address List**
139
140 |**Type**|**Device register**|**Format**|**Range**|**Note**
141 |(% rowspan="4" %)Bit|I|I ddddd.o|0.0~~99999.7|
142 |Q|Q ddddd.o|0.0~~99999.7|
143 |M|M ddddd.o|0.0~~99999.7|
144 |DB0.DB~~DB99.DB|DBxDB nndddd.o|0.0~~99999999.7|(((
145 nn: block number;
146
147 dddd: address;
148 )))
149 |(% rowspan="8" %)Word|I|IW ddddd|0~~99999|
150 |Q|QW ddddd|0~~99999|
151 |(% rowspan="3" %)M|MB ddddd|0~~99999|
152 |MW ddddd|0~~99999|(((
153 MW0=MB(0~~1)
154
155 MW2=MB(2~~3)
156
157 Address value is a multiple of 2
158 )))
159 |MD ddddd|0~~99999|(((
160 MD0=MB(0~~3)
161
162 MD4=MB(4~~7)
163
164 Address value is a multiple of 4
165 )))
166 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
167 nn: block number;
168
169 dddd: address
170 )))
171 |DBxDBW nndddd|0~~99999999
172 |DBxDBD nndddd|0~~99999999
173
174 **Configure the communication protocol**
175
176 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_8e00ed9483ddb629.png||alt="image-20220824161345-1.png" height="1011" width="1920"]]
177
178 **Cable Wiring**
179
180 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ac8ece9a26719fda.png||alt="image-20220824161450-2.png" height="170" width="401"]]
181
182 == **S7-1200 Ethernet ** ==
183
184 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]]
185
186 **V-BOX Setting**
187
188 |**Items**|**Settings**|**Note**
189 |Protocol|Siemens S7-1200|
190 |Connection|Ethernet|
191 |Port No.|102|
192 |PLC station No.|2|
193
194 (% style="text-align:center" %)
195 [[image:西门子1200协议参数.png]]
196
197 **Address List**
198
199 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
200 |(% rowspan="4" %)Bit|I|I|M d.o|(((
201 d:0~-~-9999
202
203 o:0-7
204 )))|
205 |Q|Q|Q d.o|(((
206 d:0~-~-9999
207
208 o:0-7
209 )))|
210 |M|M|M d.o|(((
211 d:0~-~-9999
212
213 o:0-7
214 )))|
215 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
216 nn:0-9999,
217
218 dddd:0-9999,
219
220 o:0-7
221 )))|(((
222 nn:DB No.
223
224 dddd:address value
225
226 o: digit address
227 )))
228 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
229 |M|MW|MW d|d:0-99999|(((
230 MW0=MB(0~~1)
231
232 MW2=MB(2~~3)
233
234 Address value is a multiple of 2
235 )))
236 |M|MD|MD d|d:0-99999|(((
237 MD0=MB(0~~3)
238
239 MD4=MB(4~~7)
240
241 Address value is a multiple of 4
242 )))
243 |I|IW|IW d|d:0-99999|
244 |Q|QW|QW d|d:0-99999|
245 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
246 nn:0-9999
247
248 dddd:0-9999
249 )))|(((
250 nn:DB No.
251
252 dddd:address value
253 )))
254 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
255 nn:0-9999
256
257 dddd:0-9999
258 )))|(((
259 nn:DB No.
260
261 dddd:address value
262
263 Address value is a multiple of 2
264 )))
265 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
266 nn:0-9999
267
268 dddd:0-9999
269 )))|(((
270 nn:DB No.
271
272 dddd:address value
273
274 Address value is a multiple of 4
275 )))
276
277 {{info}}
278 ✎Note:
279
280 * The S7-1200 supports simultaneous connection of three devices.
281 * V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (S7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
282 * S7-1200 String type, the default first two bytes are used to store the maximum character and valid characters, so the text data will be shifted back one word address. When interacting with the data, what way this address plc is displayed with is unknown. And because of an extra word of data causes us to display the wrong. The solution is if we use String, then the actual data address we want to operate on is actually shifted back two bytes, so as long as the address on the project is shifted back 2 bits to correspond with the actual data address.
283 {{/info}}
284
285 **PLC Settings**
286
287 Add BD
288
289 * Please uncheck [Symbolic access only] option;
290
291 (% style="text-align:center" %)
292 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_872ec32d12b55aa.png]]
293
294 Address settings, using BD2 as example.
295
296 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
297 * 2 represent DB block number
298 * xxxx represent address
299
300 **Such as:**
301
302 * DBxDBB20000 = DB2.DBB0
303 * DBxDBW20004 = DB2.DBW4
304
305 (% style="text-align:center" %)
306 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_8ee8d3ac3637bfc4.png]]
307
308 **How to setting String in PLC and V-net**
309 PLC configuration
310
311 choosing Data type~-~-String→add"[]" after String and input data length
312
313 (% style="text-align:center" %)
314 [[image:yUYuRVmMcL.png]]
315
316 V-box configuration
317
318 (% style="text-align:center" %)
319 [[image:BSRBeEWL0O.png]]
320
321 choosing Word and DBxDBW →input  Register Main No. →Data format is String →input data length you want to use → choosing Byte order~-~-Little-endian
322
323 (% class="box infomessage" %)
324 (((
325 Note: Register Main No. = offset in PLC + 2
326 For example, the image above has an offset of 4, so the register Main No. is 10006
327 If an offset is 8, the register Main No. is 10010
328 )))
329
330 **How to connect with S7-1200 Firmware V4.0**
331
332 PLC configuration
333
334 * Double click [device configuration] in Siemens via software
335 * Double click [protection] to enter protection configuration screen
336
337 (% style="text-align:center" %)
338 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_664a826cd356c830.png]]
339
340 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
341
342 (% style="text-align:center" %)
343 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_78026942a88f0fdb.png]]
344
345 DB settings
346
347 * Right click [DB], select [properties]
348 * Uncheck [optimized block access]
349
350 **Cable Wiring**
351
352 (% style="text-align:center" %)
353 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ac8ece9a26719fda.png]]
354
355 == **S7-XXX Ethernet** ==
356
357 Supported Series: Siemens S7-400, S7-1200 and S7-1500
358
359 **V-BOX setting**
360
361 |=**Items**|=**Settings**|=**Note**
362 |Protocol|Siemens S7-XXX|
363 |Connection|Ethernet|
364 |Port No.|102|
365 |Device No.|Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|
366 |HMI No.|Rack (Default as 0)|
367
368 Slot from TIA Portal is equal to Device No. of V-net
369
370 Rack from TIA Portal is equal to HMI No. of V-net
371
372 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d78bc267e5fc6394.png||alt="image-20220824162459-3.png" height="503" width="798"]]
373
374 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_c9ae84ef5d418580.png||alt="image-20220824163305-2.png" height="1009" width="1920"]]
375
376 **Address List**
377
378 |**Type**|**Device register**|**Format**|**Range**|**Note**
379 |(% rowspan="4" %)Bit|I|M d.o|(((
380 d:0~-~-9999
381
382 o:0-7
383 )))|
384 |Q|Q d.o|(((
385 d:0~-~-9999
386
387 o:0-7
388 )))|
389 |M|M d.o|(((
390 d:0~-~-9999
391
392 o:0-7
393 )))|
394 |DB0.DB-DB99.DB|DBxDBnndddd.o|(((
395 nn:0-9999,
396
397 dddd:0-9999,
398
399 o:0-7
400 )))|(((
401 nn:DB No.
402
403 dddd:address value
404
405 o: digit address
406 )))
407 |(% rowspan="8" %)Word|M|MB d|d:0-99999|
408 |M|MW d|d:0-99999|(((
409 MW0=MB(0~~1)
410
411 MW2=MB(2~~3)
412
413 Address value is a multiple of 2
414 )))
415 |M|MD d|d:0-99999|(((
416 MD0=MB(0~~3)
417
418 MD4=MB(4~~7)
419
420 Address value is a multiple of 4
421 )))
422 |I|IW d|d:0-99999|
423 |Q|QW d|d:0-99999|
424 |DB0.DB-DB99.DB|DBxDBBnndddd|(((
425 nn:0-9999
426
427 dddd:0-9999
428 )))|(((
429 nn:DB No.
430
431 dddd:address value
432 )))
433 |DB0.DB-DB99.DB|DBxDBWnndddd|(((
434 nn:0-9999
435
436 dddd:0-9999
437 )))|(((
438 nn:DB No.
439
440 dddd:address value
441
442 Address value is a multiple of 2
443 )))
444 |DB0.DB-DB99.DB|DBxDBDnndddd|(((
445 nn:0-9999
446
447 dddd:0-9999
448 )))|(((
449 nn:DB No.
450
451 dddd:address value
452
453 Address value is a multiple of 4
454 )))
455
456 **Configure the communication protocol**
457
458 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_9e740a8bf83ea3bf.png||alt="image-20220824163448-3.png" height="557" width="974"]]
459
460 **✎Note:**
461
462 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three V-BOX.
463 * V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
464
465 **Cable Wiring**
466
467 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ac8ece9a26719fda.png||alt="image-20220824162342-2.png" height="170" width="401"]]
468
469 == {{id name="HLOGOEthernet"/}}**LOGO Ethernet ** ==
470
471 Supported Series: Siemens Logo 0BA0, 0BA1 series
472
473 **V-BOX Settings**
474
475 |**Items**|**Settings**|**Note**
476 |Protocol|Siemens LOGO|
477 |Connection|Ethernet|
478 |Port No.|102|
479 |PLC station No.|2|
480
481 **Address List**
482
483 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
484 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
485 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
486 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
487 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
488 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
489 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
490 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
491 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
492 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
493 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
494 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
495 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
496 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
497 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
498 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
499
500 **PLC Settings in LOGO Software:**
501
502 Click [Tools]~-~-[Ethernet Connections],shown as below.
503
504 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d13df637bfedcc52.png||alt="12.PLC Protocol_html_8b9d2322edf89519.png" height="641" width="423"]]
505
506 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
507
508 (% style="text-align:center" %)
509 [[image:hXadxkZTuR.png]]
510
511 **TSAP set**: The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
512
513 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_facc6ee1af05162f.png||alt="image-20221228143047-5.png" height="626" width="1088"]]
514
515 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
516
517 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d43d2b7b2599ee64.png||alt="image-20221228143246-6.png" height="698" width="688"]]
518
519 **V-BOX Communication Settings**
520
521 Set PLC IP in [IP Address] settings;
522
523 (% style="text-align:center" %)
524 [[image:V-NET_Client logo.png]]
525
526 TSAP setting
527
528 * The initialization script needs to set the source TSAP address and the target TSAP address, otherwise the communication will not be successful.
529
530 You can copy the following script into V-net directly.
531
532 (% class="box successmessage" %)
533 (((
534 **function** **init**.main()
535 addr_setword("@W_0#HSW1200",8192) //~-~- Set the source TSAP address//
536 addr_setword("@W_0#HSW1201",4096) //~-~- Set the destination TSAP address//
537 **end**
538 )))
539
540 (% class="box infomessage" %)
541 (((
542 Note:
543 The name of the test script must be “init”, 8192 and 4096 are the data used for the test, there is no HSW address in the register option, but you can directly set the value of the corresponding address through the code.
544 )))
545
546 **✎Note:**
547
548 * **Communication port configuration: **
549 ** Continuous length needs to be set to 0.
550 ** Integration interval needs to be set to 1. (no change may result in data errors)
551 ** Set Port and Device Station NO.
552 ** Other set as defaulted.