Changes for page Siemens

Last modified by Joe on 2024/08/30 14:46

From version 26.1
edited by Theodore Xu
on 2023/08/28 10:06
Change comment: There is no comment for this version
To version 40.1
edited by Theodore Xu
on 2023/09/15 11:58
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -1,24 +3,37 @@
1 -= **Siemens ** =
2 -
3 3  == **S7-200 Smart Serial** ==
4 4  
5 -**1)Address List **
3 +**V-BOX setting**
6 6  
7 -|**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
8 -|(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
9 -|Q|Q|Q ddddd.o|0.0~~99999.7|
10 -|V|VWbit|VWbit ddddd.o|0.0~~99999.7|
11 -|V|V|V ddddd.o|0.0~~99999.7|
12 -|M|M|M ddddd.o|0.0~~99999.7|
13 -|SM|SM|ddddd.o|0.0~~99999.7|
14 -|S|S|ddddd.o|0.0~~99999.7|Read only
15 -|T|T|ddddd|0~~99999|Timer state, read only
16 -|C|C|ddddd|0~~99999|Counter state, read only
17 -|(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999|
18 -|Q|QW|QW ddddd|0~~99999|
19 -|AI|AIW|AIW ddddd|0~~99999|
20 -|AQ|VB|VB ddddd|0~~99999|
21 -|V|VW|VW ddddd|0~~99998|(((
5 +(% style="width:1323.87px" %)
6 +|**Items**|**Settings**|**Note**
7 +|Protocol|(% style="width:783px" %)Siemens S7-200 CPU22x/Smart PPI|
8 +|Connection|(% style="width:783px" %)RS485|
9 +|Baud rate|(% style="width:783px" %)9600|
10 +|Data bit|(% style="width:783px" %)8|
11 +|Parity|(% style="width:783px" %)EVEN|
12 +|Stop bit|(% style="width:783px" %)1|
13 +|PLC station No.|(% style="width:783px" %)2|
14 +
15 +(% style="text-align:center" %)
16 +[[image:西门子200串口.png]]
17 +
18 +**Address List **
19 +
20 +|**Type**|**Device register**|**Format**|**Range**|**Note**
21 +|(% rowspan="9" %)Bit|I|I ddddd.o|0.0~~99999.7|
22 +|Q|Q ddddd.o|0.0~~99999.7|
23 +|V|VWbit ddddd.o|0.0~~99999.7|
24 +|V|V ddddd.o|0.0~~99999.7|
25 +|M|M ddddd.o|0.0~~99999.7|
26 +|SM|ddddd.o|0.0~~99999.7|
27 +|S|ddddd.o|0.0~~99999.7|Read only
28 +|T|ddddd|0~~99999|Timer state, read only
29 +|C|ddddd|0~~99999|Counter state, read only
30 +|(% rowspan="12" %)Word|I|IW ddddd|0~~99999|
31 +|Q|QW ddddd|0~~99999|
32 +|AI|AIW ddddd|0~~99999|
33 +|AQ|VB ddddd|0~~99999|
34 +|V|VW ddddd|0~~99998|(((
22 22  VW0=VB (0~~1)
23 23  
24 24  VW2=VB (2~~3)
... ... @@ -25,7 +25,7 @@
25 25  
26 26  Address value is a multiple of 2
27 27  )))
28 -|V|VD|VD ddddd|0~~99998|(((
41 +|V|VD ddddd|0~~99998|(((
29 29  VD0=VB (0~~3)
30 30  
31 31  VD2=VB (4~~7)
... ... @@ -32,8 +32,8 @@
32 32  
33 33  Address value is a multiple of 4
34 34  )))
35 -|M|MB|MB ddddd|0~~99999|
36 -|M|MW|MW ddddd|0~~99999|(((
48 +|M|MB ddddd|0~~99999|
49 +|M|MW ddddd|0~~99999|(((
37 37  MW0=MB(0~~1)
38 38  
39 39  MW2=MB(2~~3)
... ... @@ -40,7 +40,7 @@
40 40  
41 41  Address value is a multiple of 2
42 42  )))
43 -|M|MD|MD ddddd|0~~99999|(((
56 +|M|MD ddddd|0~~99999|(((
44 44  MD0=MB(0~~3)
45 45  
46 46  MD4=MB(4~~7)
... ... @@ -47,26 +47,19 @@
47 47  
48 48  Address value is a multiple of 4
49 49  )))
50 -|T|TW|TW ddddd|0~~99999|Value of timer
51 -|C|CW|CW ddddd|0~~99999|Value of counter
52 -|W|SW|SW ddddd|0~~99999|
63 +|T|TW ddddd|0~~99999|Value of timer
64 +|C|CW ddddd|0~~99999|Value of counter
65 +|W|SW ddddd|0~~99999|
53 53  
54 -**2)V-BOX Protocol:Siemens S7-200 CPU22x/Smart PPI**
67 +**PLC setting**
55 55  
56 56  (% style="text-align:center" %)
57 -[[image:西门子200串口.png]]
58 -
59 -**3)PLC software**
60 -
61 -(% style="text-align:center" %)
62 62  [[image:西门子软件版本.png]]
63 63  
64 -**4)PLC Software Configuration**
65 -
66 66  (% style="text-align:center" %)
67 67  [[image:485通讯配置.png]]
68 68  
69 -**5)Connect and Download**
75 +**Connect and Download**
70 70  
71 71  (% style="text-align:center" %)
72 72  [[image:以太网 PC和PLC连接.png]]
... ... @@ -74,7 +74,7 @@
74 74  (% style="text-align:center" %)
75 75  [[image:以太网下载.png]]
76 76  
77 -**6)wiring**
83 +**Cable Wiring**
78 78  
79 79  (% style="text-align:center" %)
80 80  [[image:485接线.png]]
... ... @@ -81,32 +81,34 @@
81 81  
82 82  == **S7-200 Smart Ethernet ** ==
83 83  
84 -(% class="wikigeneratedid" id="H1FF09V-BOX" %)
85 -**1)V-BOX Protocol:Siemens S7-200 Smart(Ethernet)**
90 +**V-BOX setting**
86 86  
92 +|**Items**|**Settings**
93 +|Protocol|Siemens S7-200 Smart(Ethernet)
94 +|Connection|Ethernet
95 +|Port No.|102
96 +|PLC station No.|2
97 +
87 87  (% style="text-align:center" %)
88 88  [[image:西门子200smart 以太网.png]]
89 89  
90 -**2)PLC software**
101 +**PLC setting**
91 91  
92 92  (% style="text-align:center" %)
93 93  [[image:西门子软件版本.png]]
94 94  
95 -**3)PLC Software Configuration**
96 -
97 97  (% style="text-align:center" %)
98 98  [[image:以太网通讯配置.png]]
99 99  
100 -**4)Connect and Download**
109 +**Connect and Download**
101 101  
102 102  (% style="text-align:center" %)
103 103  [[image:以太网 PC和PLC连接.png]]
104 104  
105 -
106 106  (% style="text-align:center" %)
107 107  [[image:以太网下载.png]]
108 108  
109 -**5)wiring**
117 +**Cable Wiring**
110 110  
111 111  V-Box : RJ45 Ethernet interface
112 112  
... ... @@ -129,19 +129,19 @@
129 129  
130 130  **2)Address List**
131 131  
132 -|**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
133 -|(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
134 -|Q|Q|Q ddddd.o|0.0~~99999.7|
135 -|M|M|M ddddd.o|0.0~~99999.7|
136 -|DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
140 +|**Type**|**Device register**|**Format**|**Range**|**Note**
141 +|(% rowspan="4" %)Bit|I|I ddddd.o|0.0~~99999.7|
142 +|Q|Q ddddd.o|0.0~~99999.7|
143 +|M|M ddddd.o|0.0~~99999.7|
144 +|DB0.DB~~DB99.DB|DBxDB nndddd.o|0.0~~99999999.7|(((
137 137  nn: block number;
138 138  
139 139  dddd: address;
140 140  )))
141 -|(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
142 -|Q|QW|QW ddddd|0~~99999|
143 -|(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
144 -|MW|MW ddddd|0~~99999|(((
149 +|(% rowspan="8" %)Word|I|IW ddddd|0~~99999|
150 +|Q|QW ddddd|0~~99999|
151 +|(% rowspan="3" %)M|MB ddddd|0~~99999|
152 +|MW ddddd|0~~99999|(((
145 145  MW0=MB(0~~1)
146 146  
147 147  MW2=MB(2~~3)
... ... @@ -148,7 +148,7 @@
148 148  
149 149  Address value is a multiple of 2
150 150  )))
151 -|MD|MD ddddd|0~~99999|(((
159 +|MD ddddd|0~~99999|(((
152 152  MD0=MB(0~~3)
153 153  
154 154  MD4=MB(4~~7)
... ... @@ -155,13 +155,13 @@
155 155  
156 156  Address value is a multiple of 4
157 157  )))
158 -|(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
166 +|(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
159 159  nn: block number;
160 160  
161 161  dddd: address
162 162  )))
163 -|DBxDBW|DBxDBW nndddd|0~~99999999
164 -|DBxDBD|DBxDBD nndddd|0~~99999999
171 +|DBxDBW nndddd|0~~99999999
172 +|DBxDBD nndddd|0~~99999999
165 165  
166 166  **3)Configure the communication protocol**
167 167