Changes for page Siemens

Last modified by Joe on 2024/08/30 14:46

From version 32.1
edited by Theodore Xu
on 2023/09/11 17:57
Change comment: There is no comment for this version
To version 38.1
edited by Theodore Xu
on 2023/09/15 11:57
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -1,18 +3,16 @@
1 -= **Siemens ** =
2 -
3 3  == **S7-200 Smart Serial** ==
4 4  
5 -
6 6  **V-BOX setting**
7 7  
8 -|**Item**|**Settings**|**Note**
9 -|Protocol|Siemens S7-200 CPU22x/Smart PPI|
10 -|Connection|RS485|
11 -|Baud rate|9600|
12 -|Data bit|8|
13 -|Parity|EVEN|
14 -|Stop bit|1|
15 -|PLC station No.|2
5 +(% style="width:1323.87px" %)
6 +|**Items**|**Settings**|**Note**
7 +|Protocol|(% style="width:783px" %)Siemens S7-200 CPU22x/Smart PPI|
8 +|Connection|(% style="width:783px" %)RS485|
9 +|Baud rate|(% style="width:783px" %)9600|
10 +|Data bit|(% style="width:783px" %)8|
11 +|Parity|(% style="width:783px" %)EVEN|
12 +|Stop bit|(% style="width:783px" %)1|
13 +|PLC station No.|(% style="width:783px" %)2|
16 16  
17 17  (% style="text-align:center" %)
18 18  [[image:西门子200串口.png]]
... ... @@ -19,7 +19,7 @@
19 19  
20 20  **Address List **
21 21  
22 -|**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
20 +|**Type**|**Device register**|**V-Box register**|**Format**|**Range**|**Note**
23 23  |(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
24 24  |Q|Q|Q ddddd.o|0.0~~99999.7|
25 25  |V|VWbit|VWbit ddddd.o|0.0~~99999.7|
... ... @@ -91,11 +91,11 @@
91 91  
92 92  **V-BOX setting**
93 93  
94 -|**Items**|**Settings**|**Note**
95 -|Protocol|Siemens S7-200 Smart(Ethernet)|
96 -|Connection|Ethernet|
97 -|Port No.|102|
98 -|PLC station No.|2|
92 +|**Items**|**Settings**
93 +|Protocol|Siemens S7-200 Smart(Ethernet)
94 +|Connection|Ethernet
95 +|Port No.|102
96 +|PLC station No.|2
99 99  
100 100  (% style="text-align:center" %)
101 101  [[image:西门子200smart 以太网.png]]