Changes for page Siemens

Last modified by Joe on 2024/08/30 14:46

From version 36.1
edited by Theodore Xu
on 2023/09/12 10:56
Change comment: There is no comment for this version
To version 39.1
edited by Theodore Xu
on 2023/09/15 11:58
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -1,18 +3,16 @@
1 -= **Siemens ** =
2 -
3 3  == **S7-200 Smart Serial** ==
4 4  
5 5  **V-BOX setting**
6 6  
7 7  (% style="width:1323.87px" %)
8 -|**Items**|**Settings**
9 -|Protocol|(% style="width:783px" %)Siemens S7-200 CPU22x/Smart PPI
10 -|Connection|(% style="width:783px" %)RS485
11 -|Baud rate|(% style="width:783px" %)9600
12 -|Data bit|(% style="width:783px" %)8
13 -|Parity|(% style="width:783px" %)EVEN
14 -|Stop bit|(% style="width:783px" %)1
15 -|PLC station No.|(% style="width:783px" %)2
6 +|**Items**|**Settings**|**Note**
7 +|Protocol|(% style="width:783px" %)Siemens S7-200 CPU22x/Smart PPI|
8 +|Connection|(% style="width:783px" %)RS485|
9 +|Baud rate|(% style="width:783px" %)9600|
10 +|Data bit|(% style="width:783px" %)8|
11 +|Parity|(% style="width:783px" %)EVEN|
12 +|Stop bit|(% style="width:783px" %)1|
13 +|PLC station No.|(% style="width:783px" %)2|
16 16  
17 17  (% style="text-align:center" %)
18 18  [[image:西门子200串口.png]]
... ... @@ -19,21 +19,21 @@
19 19  
20 20  **Address List **
21 21  
22 -|**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
23 -|(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
24 -|Q|Q|Q ddddd.o|0.0~~99999.7|
25 -|V|VWbit|VWbit ddddd.o|0.0~~99999.7|
26 -|V|V|V ddddd.o|0.0~~99999.7|
27 -|M|M|M ddddd.o|0.0~~99999.7|
28 -|SM|SM|ddddd.o|0.0~~99999.7|
29 -|S|S|ddddd.o|0.0~~99999.7|Read only
30 -|T|T|ddddd|0~~99999|Timer state, read only
31 -|C|C|ddddd|0~~99999|Counter state, read only
32 -|(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999|
33 -|Q|QW|QW ddddd|0~~99999|
34 -|AI|AIW|AIW ddddd|0~~99999|
35 -|AQ|VB|VB ddddd|0~~99999|
36 -|V|VW|VW ddddd|0~~99998|(((
20 +|**Type**|**Device register**|**Format**|**Range**|**Note**
21 +|(% rowspan="9" %)Bit|I|I ddddd.o|0.0~~99999.7|
22 +|Q|Q ddddd.o|0.0~~99999.7|
23 +|V|VWbit ddddd.o|0.0~~99999.7|
24 +|V|V ddddd.o|0.0~~99999.7|
25 +|M|M ddddd.o|0.0~~99999.7|
26 +|SM|ddddd.o|0.0~~99999.7|
27 +|S|ddddd.o|0.0~~99999.7|Read only
28 +|T|ddddd|0~~99999|Timer state, read only
29 +|C|ddddd|0~~99999|Counter state, read only
30 +|(% rowspan="12" %)Word|I|IW ddddd|0~~99999|
31 +|Q|QW ddddd|0~~99999|
32 +|AI|AIW ddddd|0~~99999|
33 +|AQ|VB ddddd|0~~99999|
34 +|V|VW ddddd|0~~99998|(((
37 37  VW0=VB (0~~1)
38 38  
39 39  VW2=VB (2~~3)
... ... @@ -40,7 +40,7 @@
40 40  
41 41  Address value is a multiple of 2
42 42  )))
43 -|V|VD|VD ddddd|0~~99998|(((
41 +|V|VD ddddd|0~~99998|(((
44 44  VD0=VB (0~~3)
45 45  
46 46  VD2=VB (4~~7)
... ... @@ -47,8 +47,8 @@
47 47  
48 48  Address value is a multiple of 4
49 49  )))
50 -|M|MB|MB ddddd|0~~99999|
51 -|M|MW|MW ddddd|0~~99999|(((
48 +|M|MB ddddd|0~~99999|
49 +|M|MW ddddd|0~~99999|(((
52 52  MW0=MB(0~~1)
53 53  
54 54  MW2=MB(2~~3)
... ... @@ -55,7 +55,7 @@
55 55  
56 56  Address value is a multiple of 2
57 57  )))
58 -|M|MD|MD ddddd|0~~99999|(((
56 +|M|MD ddddd|0~~99999|(((
59 59  MD0=MB(0~~3)
60 60  
61 61  MD4=MB(4~~7)
... ... @@ -62,9 +62,9 @@
62 62  
63 63  Address value is a multiple of 4
64 64  )))
65 -|T|TW|TW ddddd|0~~99999|Value of timer
66 -|C|CW|CW ddddd|0~~99999|Value of counter
67 -|W|SW|SW ddddd|0~~99999|
63 +|T|TW ddddd|0~~99999|Value of timer
64 +|C|CW ddddd|0~~99999|Value of counter
65 +|W|SW ddddd|0~~99999|
68 68  
69 69  **PLC setting**
70 70