Changes for page Siemens

Last modified by Joe on 2024/08/30 14:46

From version 44.1
edited by Theodore Xu
on 2023/10/12 16:32
Change comment: There is no comment for this version
To version 45.1
edited by Theodore Xu
on 2023/10/12 16:37
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -179,10 +179,102 @@
179 179  
180 180  [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ac8ece9a26719fda.png||alt="image-20220824161450-2.png" height="170" width="401"]]
181 181  
182 -== {{id name="HS7-1200A0Ethernet"/}}**S7-1200 Ethernet ** ==
182 +== **S7-1200 Ethernet ** ==
183 183  
184 184  [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]]
185 185  
186 +**V-BOX Setting**
187 +
188 +|**Items**|**Settings**|**Note**
189 +|Protocol|Siemens S7-1200|
190 +|Connection|Ethernet|
191 +|Port No.|102|
192 +|PLC station No.|2|
193 +
194 +**Address List**
195 +
196 +|**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
197 +|(% rowspan="4" %)Bit|I|I|M d.o|(((
198 +d:0~-~-9999
199 +
200 +o:0-7
201 +)))|
202 +|Q|Q|Q d.o|(((
203 +d:0~-~-9999
204 +
205 +o:0-7
206 +)))|
207 +|M|M|M d.o|(((
208 +d:0~-~-9999
209 +
210 +o:0-7
211 +)))|
212 +|DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
213 +nn:0-9999,
214 +
215 +dddd:0-9999,
216 +
217 +o:0-7
218 +)))|(((
219 +nn:DB No.
220 +
221 +dddd:address value
222 +
223 +o: digit address
224 +)))
225 +|(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
226 +|M|MW|MW d|d:0-99999|(((
227 +MW0=MB(0~~1)
228 +
229 +MW2=MB(2~~3)
230 +
231 +Address value is a multiple of 2
232 +)))
233 +|M|MD|MD d|d:0-99999|(((
234 +MD0=MB(0~~3)
235 +
236 +MD4=MB(4~~7)
237 +
238 +Address value is a multiple of 4
239 +)))
240 +|I|IW|IW d|d:0-99999|
241 +|Q|QW|QW d|d:0-99999|
242 +|DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
243 +nn:0-9999
244 +
245 +dddd:0-9999
246 +)))|(((
247 +nn:DB No.
248 +
249 +dddd:address value
250 +)))
251 +|DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
252 +nn:0-9999
253 +
254 +dddd:0-9999
255 +)))|(((
256 +nn:DB No.
257 +
258 +dddd:address value
259 +
260 +Address value is a multiple of 2
261 +)))
262 +|DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
263 +nn:0-9999
264 +
265 +dddd:0-9999
266 +)))|(((
267 +nn:DB No.
268 +
269 +dddd:address value
270 +
271 +Address value is a multiple of 4
272 +)))
273 +
274 +**Communication Settings**
275 +
276 +Enable HMI Ethernet in [Project Settings]
277 +
186 186  == **S7-XXX Ethernet** ==
187 187  
188 188  Supported Series: Siemens S7-400, S7-1200 and S7-1500
1697099618537-157.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.AiXia
Size
... ... @@ -1,0 +1,1 @@
1 +36.4 KB
Content