Wiki source code of Siemens

Version 17.1 by Theodore Xu on 2023/08/25 15:50

Show last authors
1 = {{id name="HSiemens"/}}**Siemens ** =
2
3 == **S7-200 Smart Serial** ==
4
5 == **S7-200 Smart Ethernet ** ==
6
7 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20S7-200%20Smart.zip]]
8
9 (% class="wikigeneratedid" id="H1FF09V-BOX" %)
10 **1)V-BOX **
11
12 (% style="text-align:center" %)
13 [[image:西门子200smart 以太网.png]]
14
15 **1)PLC software**
16
17 (% style="text-align:center" %)
18 [[image:西门子软件版本.png]]
19
20 **2)Ethernet Configuration**
21
22 (% style="text-align:center" %)
23 [[image:以太网通讯配置.png]]
24
25 **3)Connect PC software**
26
27 (% style="text-align:center" %)
28 [[image:以太网下载.png]]
29
30
31 **5)wiring**
32
33
34 V-Box : RJ45 Ethernet interface
35
36 PLC : RJ45 Ethernet interface
37
38 (% style="text-align:center" %)
39 [[image:以太网连接.png]]
40
41
42 == {{id name="HS7-300Ethernet"/}}**S7-300 Ethernet ** ==
43
44 Supported Series: Siemens S7-300 series PLC
45
46 **1)V-BOX setting**
47
48 |**Items**|**Settings**|**Note**
49 |Protocol|Simens S7-300 Ethernet|
50 |Connection|Ethernet|
51 |Port No.|102|
52 |PLC station No.|2|Need to be same as the PLC setting
53
54 **2)Address List**
55
56 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
57 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
58 |Q|Q|Q ddddd.o|0.0~~99999.7|
59 |M|M|M ddddd.o|0.0~~99999.7|
60 |DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
61 nn: block number;
62
63 dddd: address;
64 )))
65 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
66 |Q|QW|QW ddddd|0~~99999|
67 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
68 |MW|MW ddddd|0~~99999|(((
69 MW0=MB(0~~1)
70
71 MW2=MB(2~~3)
72
73 Address value is a multiple of 2
74 )))
75 |MD|MD ddddd|0~~99999|(((
76 MD0=MB(0~~3)
77
78 MD4=MB(4~~7)
79
80 Address value is a multiple of 4
81 )))
82 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
83 nn: block number;
84
85 dddd: address
86 )))
87 |DBxDBW|DBxDBW nndddd|0~~99999999
88 |DBxDBD|DBxDBD nndddd|0~~99999999
89
90 **3)Configure the communication protocol**
91
92 {{id name="Iimage-20220824161345-1.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_8e00ed9483ddb629.png||alt="image-20220824161345-1.png" height="1011" width="1920"]]
93
94 **4)Cable Wiring**
95
96 {{id name="Iimage-20220824161450-2.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ac8ece9a26719fda.png||alt="image-20220824161450-2.png" height="170" width="401"]]
97
98 == {{id name="HS7-1200A0Ethernet"/}}**S7-1200 Ethernet ** ==
99
100 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]]
101
102 == {{id name="HS7-XXXEthernetl"/}}**S7-XXX Ethernet l** ==
103
104 Supported Series: Siemens S7-400, S7-1200 and S7-1500
105
106 **1)V-BOX setting**
107
108 |=**Items**|=**Settings**|=**Note**
109 |Protocol|Siemens S7-XXX|
110 |Connection|Ethernet|
111 |Port No.|102|
112 |Device No.|Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|
113 |HMI No.|Rack (Default as 0)|
114
115 Slot from TIA Portal is equal to Device No. of V-net
116
117 Rack from TIA Portal is equal to HMI No. of V-net
118
119 {{id name="Iimage-20220824162459-3.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d78bc267e5fc6394.png||alt="image-20220824162459-3.png" height="503" width="798"]]
120
121 {{id name="Iimage-20220824163305-2.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_c9ae84ef5d418580.png||alt="image-20220824163305-2.png" height="1009" width="1920"]]
122
123 **2)Address List**
124
125 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
126 |(% rowspan="4" %)Bit|I|I|M d.o|(((
127 d:0~-~-9999
128
129 o:0-7
130 )))|
131 |Q|Q|Q d.o|(((
132 d:0~-~-9999
133
134 o:0-7
135 )))|
136 |M|M|M d.o|(((
137 d:0~-~-9999
138
139 o:0-7
140 )))|
141 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
142 nn:0-9999,
143
144 dddd:0-9999,
145
146 o:0-7
147 )))|(((
148 nn:DB No.
149
150 dddd:address value
151
152 o: digit address
153 )))
154 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
155 |M|MW|MW d|d:0-99999|(((
156 MW0=MB(0~~1)
157
158 MW2=MB(2~~3)
159
160 Address value is a multiple of 2
161 )))
162 |M|MD|MD d|d:0-99999|(((
163 MD0=MB(0~~3)
164
165 MD4=MB(4~~7)
166
167 Address value is a multiple of 4
168 )))
169 |I|IW|IW d|d:0-99999|
170 |Q|QW|QW d|d:0-99999|
171 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
172 nn:0-9999
173
174 dddd:0-9999
175 )))|(((
176 nn:DB No.
177
178 dddd:address value
179 )))
180 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
181 nn:0-9999
182
183 dddd:0-9999
184 )))|(((
185 nn:DB No.
186
187 dddd:address value
188
189 Address value is a multiple of 2
190 )))
191 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
192 nn:0-9999
193
194 dddd:0-9999
195 )))|(((
196 nn:DB No.
197
198 dddd:address value
199
200 Address value is a multiple of 4
201 )))
202
203 **3)Configure the communication protocol**
204
205 {{id name="Iimage-20220824163448-3.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_9e740a8bf83ea3bf.png||alt="image-20220824163448-3.png" height="557" width="974"]]
206
207 **✎Note:**
208
209 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three V-BOX.
210 * V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
211
212 **4)Cable Wiring**
213
214 {{id name="Iimage-20220824162342-2.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ac8ece9a26719fda.png||alt="image-20220824162342-2.png" height="170" width="401"]]
215
216 == {{id name="HLOGOEthernet"/}}**LOGO Ethernet ** ==
217
218 Supported Series: Siemens Logo 0BA0, 0BA1 series
219
220 **V-BOX Settings**
221
222 |**Items**|**Settings**|**Note**
223 |Protocol|Siemens LOGO|
224 |Connection|Ethernet|
225 |Port No.|102|
226 |PLC station No.|2|
227
228 **Address List**
229
230 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
231 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
232 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
233 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
234 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
235 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
236 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
237 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
238 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
239 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
240 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
241 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
242 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
243 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
244 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
245 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
246
247 **PLC Settings in LOGO Software:**
248
249 Click [Tools]~-~-[Ethernet Connections],shown as below.
250
251 {{id name="IPIStudio.125C.PLCprotocols.WebHome4012.PLCProtocol_html_8b9d2322edf89519.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d13df637bfedcc52.png||alt="12.PLC Protocol_html_8b9d2322edf89519.png" height="641" width="423"]]
252
253 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
254
255 {{id name="IPIStudio.125C.PLCprotocols.WebHome40image-20221228142937-4.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_316247e0130c4c55.png||alt="image-20221228142937-4.png" height="484" width="366"]]
256
257 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
258
259 {{id name="IPIStudio.125C.PLCprotocols.WebHome40image-20221228143047-5.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_facc6ee1af05162f.png||alt="image-20221228143047-5.png" height="626" width="1088"]]
260
261 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
262
263 {{id name="IPIStudio.125C.PLCprotocols.WebHome40image-20221228143246-6.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d43d2b7b2599ee64.png||alt="image-20221228143246-6.png" height="698" width="688"]]
264
265 **V-BOX Communication Settings**
266
267 Set PLC IP in [IP Address] settings;
268
269 {{id name="ILldwDGntf4.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ab570912d299c09.png||alt="LldwDGntf4.png" height="530" width="899"]]
270
271 Enable V-BOX Ethernet in [Network];
272
273 {{id name="IWgvjfWbQif.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_637860db3ca1ca1b.png||alt="WgvjfWbQif.png" height="654" width="1195"]]
274
275 TSAP setting
276
277 * The initialization script needs to set the source TSAP address and the target TSAP address, otherwise the communication will not be successful.
278
279 **function** **init**.main()
280 addr_setword("@W_0#HSW1200",8192) //~-~- Set the source TSAP address//
281 addr_setword("@W_0#HSW1201",4096) //~-~- Set the destination TSAP address//
282 **end**
283
284 Note: The name of the test script is init, 8192 and 4096 are the data used for the test, there is no HSW address in the register option, but you can directly set the value of the corresponding address through the code.
285
286 **✎Note:**
287
288 * **Communication port configuration: **
289 ** Continuous length needs to be set to 0.
290 ** Integration interval needs to be set to 1. (no change may result in data errors)
291 ** Set Port and Device Station NO.
292 ** Other set as defaulted.
293 * **Notes on the use of registers:**
294 ** Register VD: Use only registers that are multiples of 4, such as 0, 4, 8, etc.
295 ** Register VW: Use only registers thay are multiples of 2, such as 0, 2, 4 etc. (Using an odd-length register may result in data errors, such as 2 3 4 )