Wiki source code of Siemens

Version 18.1 by Theodore Xu on 2023/08/25 15:51

Show last authors
1 = {{id name="HSiemens"/}}**Siemens ** =
2
3 == **S7-200 Smart Serial** ==
4
5 == **S7-200 Smart Ethernet ** ==
6
7 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20S7-200%20Smart.zip]]
8
9 (% class="wikigeneratedid" id="H1FF09V-BOX" %)
10 **1)V-BOX **
11
12 (% style="text-align:center" %)
13 [[image:西门子200smart 以太网.png]]
14
15 **2)PLC software**
16
17 (% style="text-align:center" %)
18 [[image:西门子软件版本.png]]
19
20 **3)Ethernet Configuration**
21
22 (% style="text-align:center" %)
23 [[image:以太网通讯配置.png]]
24
25 **4)Connect PC software**
26
27 (% style="text-align:center" %)
28 [[image:以太网下载.png]]
29
30
31 **5)wiring**
32
33 V-Box : RJ45 Ethernet interface
34
35 PLC : RJ45 Ethernet interface
36
37 (% style="text-align:center" %)
38 [[image:以太网连接.png]]
39
40 == {{id name="HS7-300Ethernet"/}}**S7-300 Ethernet ** ==
41
42 Supported Series: Siemens S7-300 series PLC
43
44 **1)V-BOX setting**
45
46 |**Items**|**Settings**|**Note**
47 |Protocol|Simens S7-300 Ethernet|
48 |Connection|Ethernet|
49 |Port No.|102|
50 |PLC station No.|2|Need to be same as the PLC setting
51
52 **2)Address List**
53
54 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
55 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
56 |Q|Q|Q ddddd.o|0.0~~99999.7|
57 |M|M|M ddddd.o|0.0~~99999.7|
58 |DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
59 nn: block number;
60
61 dddd: address;
62 )))
63 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
64 |Q|QW|QW ddddd|0~~99999|
65 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
66 |MW|MW ddddd|0~~99999|(((
67 MW0=MB(0~~1)
68
69 MW2=MB(2~~3)
70
71 Address value is a multiple of 2
72 )))
73 |MD|MD ddddd|0~~99999|(((
74 MD0=MB(0~~3)
75
76 MD4=MB(4~~7)
77
78 Address value is a multiple of 4
79 )))
80 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
81 nn: block number;
82
83 dddd: address
84 )))
85 |DBxDBW|DBxDBW nndddd|0~~99999999
86 |DBxDBD|DBxDBD nndddd|0~~99999999
87
88 **3)Configure the communication protocol**
89
90 {{id name="Iimage-20220824161345-1.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_8e00ed9483ddb629.png||alt="image-20220824161345-1.png" height="1011" width="1920"]]
91
92 **4)Cable Wiring**
93
94 {{id name="Iimage-20220824161450-2.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ac8ece9a26719fda.png||alt="image-20220824161450-2.png" height="170" width="401"]]
95
96 == {{id name="HS7-1200A0Ethernet"/}}**S7-1200 Ethernet ** ==
97
98 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]]
99
100 == {{id name="HS7-XXXEthernetl"/}}**S7-XXX Ethernet l** ==
101
102 Supported Series: Siemens S7-400, S7-1200 and S7-1500
103
104 **1)V-BOX setting**
105
106 |=**Items**|=**Settings**|=**Note**
107 |Protocol|Siemens S7-XXX|
108 |Connection|Ethernet|
109 |Port No.|102|
110 |Device No.|Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|
111 |HMI No.|Rack (Default as 0)|
112
113 Slot from TIA Portal is equal to Device No. of V-net
114
115 Rack from TIA Portal is equal to HMI No. of V-net
116
117 {{id name="Iimage-20220824162459-3.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d78bc267e5fc6394.png||alt="image-20220824162459-3.png" height="503" width="798"]]
118
119 {{id name="Iimage-20220824163305-2.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_c9ae84ef5d418580.png||alt="image-20220824163305-2.png" height="1009" width="1920"]]
120
121 **2)Address List**
122
123 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
124 |(% rowspan="4" %)Bit|I|I|M d.o|(((
125 d:0~-~-9999
126
127 o:0-7
128 )))|
129 |Q|Q|Q d.o|(((
130 d:0~-~-9999
131
132 o:0-7
133 )))|
134 |M|M|M d.o|(((
135 d:0~-~-9999
136
137 o:0-7
138 )))|
139 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
140 nn:0-9999,
141
142 dddd:0-9999,
143
144 o:0-7
145 )))|(((
146 nn:DB No.
147
148 dddd:address value
149
150 o: digit address
151 )))
152 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
153 |M|MW|MW d|d:0-99999|(((
154 MW0=MB(0~~1)
155
156 MW2=MB(2~~3)
157
158 Address value is a multiple of 2
159 )))
160 |M|MD|MD d|d:0-99999|(((
161 MD0=MB(0~~3)
162
163 MD4=MB(4~~7)
164
165 Address value is a multiple of 4
166 )))
167 |I|IW|IW d|d:0-99999|
168 |Q|QW|QW d|d:0-99999|
169 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
170 nn:0-9999
171
172 dddd:0-9999
173 )))|(((
174 nn:DB No.
175
176 dddd:address value
177 )))
178 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
179 nn:0-9999
180
181 dddd:0-9999
182 )))|(((
183 nn:DB No.
184
185 dddd:address value
186
187 Address value is a multiple of 2
188 )))
189 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
190 nn:0-9999
191
192 dddd:0-9999
193 )))|(((
194 nn:DB No.
195
196 dddd:address value
197
198 Address value is a multiple of 4
199 )))
200
201 **3)Configure the communication protocol**
202
203 {{id name="Iimage-20220824163448-3.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_9e740a8bf83ea3bf.png||alt="image-20220824163448-3.png" height="557" width="974"]]
204
205 **✎Note:**
206
207 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three V-BOX.
208 * V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
209
210 **4)Cable Wiring**
211
212 {{id name="Iimage-20220824162342-2.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ac8ece9a26719fda.png||alt="image-20220824162342-2.png" height="170" width="401"]]
213
214 == {{id name="HLOGOEthernet"/}}**LOGO Ethernet ** ==
215
216 Supported Series: Siemens Logo 0BA0, 0BA1 series
217
218 **V-BOX Settings**
219
220 |**Items**|**Settings**|**Note**
221 |Protocol|Siemens LOGO|
222 |Connection|Ethernet|
223 |Port No.|102|
224 |PLC station No.|2|
225
226 **Address List**
227
228 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
229 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
230 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
231 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
232 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
233 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
234 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
235 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
236 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
237 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
238 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
239 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
240 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
241 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
242 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
243 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
244
245 **PLC Settings in LOGO Software:**
246
247 Click [Tools]~-~-[Ethernet Connections],shown as below.
248
249 {{id name="IPIStudio.125C.PLCprotocols.WebHome4012.PLCProtocol_html_8b9d2322edf89519.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d13df637bfedcc52.png||alt="12.PLC Protocol_html_8b9d2322edf89519.png" height="641" width="423"]]
250
251 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
252
253 {{id name="IPIStudio.125C.PLCprotocols.WebHome40image-20221228142937-4.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_316247e0130c4c55.png||alt="image-20221228142937-4.png" height="484" width="366"]]
254
255 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
256
257 {{id name="IPIStudio.125C.PLCprotocols.WebHome40image-20221228143047-5.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_facc6ee1af05162f.png||alt="image-20221228143047-5.png" height="626" width="1088"]]
258
259 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
260
261 {{id name="IPIStudio.125C.PLCprotocols.WebHome40image-20221228143246-6.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d43d2b7b2599ee64.png||alt="image-20221228143246-6.png" height="698" width="688"]]
262
263 **V-BOX Communication Settings**
264
265 Set PLC IP in [IP Address] settings;
266
267 {{id name="ILldwDGntf4.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ab570912d299c09.png||alt="LldwDGntf4.png" height="530" width="899"]]
268
269 Enable V-BOX Ethernet in [Network];
270
271 {{id name="IWgvjfWbQif.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_637860db3ca1ca1b.png||alt="WgvjfWbQif.png" height="654" width="1195"]]
272
273 TSAP setting
274
275 * The initialization script needs to set the source TSAP address and the target TSAP address, otherwise the communication will not be successful.
276
277 **function** **init**.main()
278 addr_setword("@W_0#HSW1200",8192) //~-~- Set the source TSAP address//
279 addr_setword("@W_0#HSW1201",4096) //~-~- Set the destination TSAP address//
280 **end**
281
282 Note: The name of the test script is init, 8192 and 4096 are the data used for the test, there is no HSW address in the register option, but you can directly set the value of the corresponding address through the code.
283
284 **✎Note:**
285
286 * **Communication port configuration: **
287 ** Continuous length needs to be set to 0.
288 ** Integration interval needs to be set to 1. (no change may result in data errors)
289 ** Set Port and Device Station NO.
290 ** Other set as defaulted.
291 * **Notes on the use of registers:**
292 ** Register VD: Use only registers that are multiples of 4, such as 0, 4, 8, etc.
293 ** Register VW: Use only registers thay are multiples of 2, such as 0, 2, 4 etc. (Using an odd-length register may result in data errors, such as 2 3 4 )