Wiki source code of Siemens

Version 21.1 by Theodore Xu on 2023/08/25 16:29

Show last authors
1 = {{id name="HSiemens"/}}**Siemens ** =
2
3 == **S7-200 Smart Serial** ==
4
5 **1)V-BOX Protocol:Siemens S7-200 CPU22x/Smart PPI**
6
7 (% style="text-align:center" %)
8 [[image:西门子200串口.png]]
9
10 **2)PLC software**
11
12 (% style="text-align:center" %)
13 [[image:西门子软件版本.png]]
14
15 **3)PLC Software Configuration**
16
17 (% style="text-align:center" %)
18 [[image:485通讯配置.png]]
19
20 **4)Connect PC software and Download**
21
22 (% style="text-align:center" %)
23 [[image:以太网 PC和PLC连接.png]]
24
25 (% style="text-align:center" %)
26 [[image:以太网下载.png]]
27
28 **5)wiring**
29
30 (% style="text-align:center" %)
31 [[image:485接线.png]]
32
33 == **S7-200 Smart Ethernet ** ==
34
35 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20S7-200%20Smart.zip]]
36
37 (% class="wikigeneratedid" id="H1FF09V-BOX" %)
38 **1)V-BOX **
39
40 (% style="text-align:center" %)
41 [[image:西门子200smart 以太网.png]]
42
43 **2)PLC software**
44
45 (% style="text-align:center" %)
46 [[image:西门子软件版本.png]]
47
48 **3)PLC Software Configuration**
49
50 (% style="text-align:center" %)
51 [[image:以太网通讯配置.png]]
52
53 **4)Connect PC software and Download**
54
55 (% style="text-align:center" %)
56 [[image:以太网 PC和PLC连接.png]]
57
58
59 (% style="text-align:center" %)
60 [[image:以太网下载.png]]
61
62 **5)wiring**
63
64 V-Box : RJ45 Ethernet interface
65
66 PLC : RJ45 Ethernet interface
67
68 (% style="text-align:center" %)
69 [[image:以太网连接.png]]
70
71 == {{id name="HS7-300Ethernet"/}}**S7-300 Ethernet ** ==
72
73 Supported Series: Siemens S7-300 series PLC
74
75 **1)V-BOX setting**
76
77 |**Items**|**Settings**|**Note**
78 |Protocol|Simens S7-300 Ethernet|
79 |Connection|Ethernet|
80 |Port No.|102|
81 |PLC station No.|2|Need to be same as the PLC setting
82
83 **2)Address List**
84
85 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
86 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
87 |Q|Q|Q ddddd.o|0.0~~99999.7|
88 |M|M|M ddddd.o|0.0~~99999.7|
89 |DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
90 nn: block number;
91
92 dddd: address;
93 )))
94 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
95 |Q|QW|QW ddddd|0~~99999|
96 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
97 |MW|MW ddddd|0~~99999|(((
98 MW0=MB(0~~1)
99
100 MW2=MB(2~~3)
101
102 Address value is a multiple of 2
103 )))
104 |MD|MD ddddd|0~~99999|(((
105 MD0=MB(0~~3)
106
107 MD4=MB(4~~7)
108
109 Address value is a multiple of 4
110 )))
111 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
112 nn: block number;
113
114 dddd: address
115 )))
116 |DBxDBW|DBxDBW nndddd|0~~99999999
117 |DBxDBD|DBxDBD nndddd|0~~99999999
118
119 **3)Configure the communication protocol**
120
121 {{id name="Iimage-20220824161345-1.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_8e00ed9483ddb629.png||alt="image-20220824161345-1.png" height="1011" width="1920"]]
122
123 **4)Cable Wiring**
124
125 {{id name="Iimage-20220824161450-2.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ac8ece9a26719fda.png||alt="image-20220824161450-2.png" height="170" width="401"]]
126
127 == {{id name="HS7-1200A0Ethernet"/}}**S7-1200 Ethernet ** ==
128
129 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]]
130
131 == {{id name="HS7-XXXEthernetl"/}}**S7-XXX Ethernet l** ==
132
133 Supported Series: Siemens S7-400, S7-1200 and S7-1500
134
135 **1)V-BOX setting**
136
137 |=**Items**|=**Settings**|=**Note**
138 |Protocol|Siemens S7-XXX|
139 |Connection|Ethernet|
140 |Port No.|102|
141 |Device No.|Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|
142 |HMI No.|Rack (Default as 0)|
143
144 Slot from TIA Portal is equal to Device No. of V-net
145
146 Rack from TIA Portal is equal to HMI No. of V-net
147
148 {{id name="Iimage-20220824162459-3.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d78bc267e5fc6394.png||alt="image-20220824162459-3.png" height="503" width="798"]]
149
150 {{id name="Iimage-20220824163305-2.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_c9ae84ef5d418580.png||alt="image-20220824163305-2.png" height="1009" width="1920"]]
151
152 **2)Address List**
153
154 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
155 |(% rowspan="4" %)Bit|I|I|M d.o|(((
156 d:0~-~-9999
157
158 o:0-7
159 )))|
160 |Q|Q|Q d.o|(((
161 d:0~-~-9999
162
163 o:0-7
164 )))|
165 |M|M|M d.o|(((
166 d:0~-~-9999
167
168 o:0-7
169 )))|
170 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
171 nn:0-9999,
172
173 dddd:0-9999,
174
175 o:0-7
176 )))|(((
177 nn:DB No.
178
179 dddd:address value
180
181 o: digit address
182 )))
183 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
184 |M|MW|MW d|d:0-99999|(((
185 MW0=MB(0~~1)
186
187 MW2=MB(2~~3)
188
189 Address value is a multiple of 2
190 )))
191 |M|MD|MD d|d:0-99999|(((
192 MD0=MB(0~~3)
193
194 MD4=MB(4~~7)
195
196 Address value is a multiple of 4
197 )))
198 |I|IW|IW d|d:0-99999|
199 |Q|QW|QW d|d:0-99999|
200 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
201 nn:0-9999
202
203 dddd:0-9999
204 )))|(((
205 nn:DB No.
206
207 dddd:address value
208 )))
209 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
210 nn:0-9999
211
212 dddd:0-9999
213 )))|(((
214 nn:DB No.
215
216 dddd:address value
217
218 Address value is a multiple of 2
219 )))
220 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
221 nn:0-9999
222
223 dddd:0-9999
224 )))|(((
225 nn:DB No.
226
227 dddd:address value
228
229 Address value is a multiple of 4
230 )))
231
232 **3)Configure the communication protocol**
233
234 {{id name="Iimage-20220824163448-3.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_9e740a8bf83ea3bf.png||alt="image-20220824163448-3.png" height="557" width="974"]]
235
236 **✎Note:**
237
238 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three V-BOX.
239 * V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
240
241 **4)Cable Wiring**
242
243 {{id name="Iimage-20220824162342-2.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ac8ece9a26719fda.png||alt="image-20220824162342-2.png" height="170" width="401"]]
244
245 == {{id name="HLOGOEthernet"/}}**LOGO Ethernet ** ==
246
247 Supported Series: Siemens Logo 0BA0, 0BA1 series
248
249 **V-BOX Settings**
250
251 |**Items**|**Settings**|**Note**
252 |Protocol|Siemens LOGO|
253 |Connection|Ethernet|
254 |Port No.|102|
255 |PLC station No.|2|
256
257 **Address List**
258
259 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
260 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
261 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
262 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
263 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
264 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
265 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
266 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
267 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
268 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
269 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
270 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
271 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
272 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
273 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
274 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
275
276 **PLC Settings in LOGO Software:**
277
278 Click [Tools]~-~-[Ethernet Connections],shown as below.
279
280 {{id name="IPIStudio.125C.PLCprotocols.WebHome4012.PLCProtocol_html_8b9d2322edf89519.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d13df637bfedcc52.png||alt="12.PLC Protocol_html_8b9d2322edf89519.png" height="641" width="423"]]
281
282 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
283
284 {{id name="IPIStudio.125C.PLCprotocols.WebHome40image-20221228142937-4.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_316247e0130c4c55.png||alt="image-20221228142937-4.png" height="484" width="366"]]
285
286 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
287
288 {{id name="IPIStudio.125C.PLCprotocols.WebHome40image-20221228143047-5.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_facc6ee1af05162f.png||alt="image-20221228143047-5.png" height="626" width="1088"]]
289
290 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
291
292 {{id name="IPIStudio.125C.PLCprotocols.WebHome40image-20221228143246-6.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d43d2b7b2599ee64.png||alt="image-20221228143246-6.png" height="698" width="688"]]
293
294 **V-BOX Communication Settings**
295
296 Set PLC IP in [IP Address] settings;
297
298 {{id name="ILldwDGntf4.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ab570912d299c09.png||alt="LldwDGntf4.png" height="530" width="899"]]
299
300 Enable V-BOX Ethernet in [Network];
301
302 {{id name="IWgvjfWbQif.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_637860db3ca1ca1b.png||alt="WgvjfWbQif.png" height="654" width="1195"]]
303
304 TSAP setting
305
306 * The initialization script needs to set the source TSAP address and the target TSAP address, otherwise the communication will not be successful.
307
308 **function** **init**.main()
309 addr_setword("@W_0#HSW1200",8192) //~-~- Set the source TSAP address//
310 addr_setword("@W_0#HSW1201",4096) //~-~- Set the destination TSAP address//
311 **end**
312
313 Note: The name of the test script is init, 8192 and 4096 are the data used for the test, there is no HSW address in the register option, but you can directly set the value of the corresponding address through the code.
314
315 **✎Note:**
316
317 * **Communication port configuration: **
318 ** Continuous length needs to be set to 0.
319 ** Integration interval needs to be set to 1. (no change may result in data errors)
320 ** Set Port and Device Station NO.
321 ** Other set as defaulted.
322 * **Notes on the use of registers:**
323 ** Register VD: Use only registers that are multiples of 4, such as 0, 4, 8, etc.
324 ** Register VW: Use only registers thay are multiples of 2, such as 0, 2, 4 etc. (Using an odd-length register may result in data errors, such as 2 3 4 )