Wiki source code of Siemens

Version 24.1 by Theodore Xu on 2023/08/25 16:41

Show last authors
1 = {{id name="HSiemens"/}}**Siemens ** =
2
3 == **S7-200 Smart Serial** ==
4
5 **1)V-BOX Protocol:Siemens S7-200 CPU22x/Smart PPI**
6
7 (% style="text-align:center" %)
8 [[image:西门子200串口.png]]
9
10 **2)PLC software**
11
12 (% style="text-align:center" %)
13 [[image:西门子软件版本.png]]
14
15 **3)PLC Software Configuration**
16
17 (% style="text-align:center" %)
18 [[image:485通讯配置.png]]
19
20 **4)Connect and Download**
21
22 (% style="text-align:center" %)
23 [[image:以太网 PC和PLC连接.png]]
24
25 (% style="text-align:center" %)
26 [[image:以太网下载.png]]
27
28 **5)wiring**
29
30 (% style="text-align:center" %)
31 [[image:485接线.png]]
32
33 == **S7-200 Smart Ethernet ** ==
34
35 (% class="wikigeneratedid" id="H1FF09V-BOX" %)
36 **1)V-BOX Protocol:Siemens S7-200 Smart(Ethernet)**
37
38 (% style="text-align:center" %)
39 [[image:西门子200smart 以太网.png]]
40
41 **2)PLC software**
42
43 (% style="text-align:center" %)
44 [[image:西门子软件版本.png]]
45
46 **3)PLC Software Configuration**
47
48 (% style="text-align:center" %)
49 [[image:以太网通讯配置.png]]
50
51 **4)Connect PC software and Download**
52
53 (% style="text-align:center" %)
54 [[image:以太网 PC和PLC连接.png]]
55
56
57 (% style="text-align:center" %)
58 [[image:以太网下载.png]]
59
60 **5)wiring**
61
62 V-Box : RJ45 Ethernet interface
63
64 PLC : RJ45 Ethernet interface
65
66 (% style="text-align:center" %)
67 [[image:以太网连接.png]]
68
69 == {{id name="HS7-300Ethernet"/}}**S7-300 Ethernet ** ==
70
71 Supported Series: Siemens S7-300 series PLC
72
73 **1)V-BOX setting**
74
75 |**Items**|**Settings**|**Note**
76 |Protocol|Simens S7-300 Ethernet|
77 |Connection|Ethernet|
78 |Port No.|102|
79 |PLC station No.|2|Need to be same as the PLC setting
80
81 **2)Address List**
82
83 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
84 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
85 |Q|Q|Q ddddd.o|0.0~~99999.7|
86 |M|M|M ddddd.o|0.0~~99999.7|
87 |DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
88 nn: block number;
89
90 dddd: address;
91 )))
92 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
93 |Q|QW|QW ddddd|0~~99999|
94 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
95 |MW|MW ddddd|0~~99999|(((
96 MW0=MB(0~~1)
97
98 MW2=MB(2~~3)
99
100 Address value is a multiple of 2
101 )))
102 |MD|MD ddddd|0~~99999|(((
103 MD0=MB(0~~3)
104
105 MD4=MB(4~~7)
106
107 Address value is a multiple of 4
108 )))
109 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
110 nn: block number;
111
112 dddd: address
113 )))
114 |DBxDBW|DBxDBW nndddd|0~~99999999
115 |DBxDBD|DBxDBD nndddd|0~~99999999
116
117 **3)Configure the communication protocol**
118
119 {{id name="Iimage-20220824161345-1.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_8e00ed9483ddb629.png||alt="image-20220824161345-1.png" height="1011" width="1920"]]
120
121 **4)Cable Wiring**
122
123 {{id name="Iimage-20220824161450-2.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ac8ece9a26719fda.png||alt="image-20220824161450-2.png" height="170" width="401"]]
124
125 == {{id name="HS7-1200A0Ethernet"/}}**S7-1200 Ethernet ** ==
126
127 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]]
128
129 == {{id name="HS7-XXXEthernetl"/}}**S7-XXX Ethernet l** ==
130
131 Supported Series: Siemens S7-400, S7-1200 and S7-1500
132
133 **1)V-BOX setting**
134
135 |=**Items**|=**Settings**|=**Note**
136 |Protocol|Siemens S7-XXX|
137 |Connection|Ethernet|
138 |Port No.|102|
139 |Device No.|Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|
140 |HMI No.|Rack (Default as 0)|
141
142 Slot from TIA Portal is equal to Device No. of V-net
143
144 Rack from TIA Portal is equal to HMI No. of V-net
145
146 {{id name="Iimage-20220824162459-3.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d78bc267e5fc6394.png||alt="image-20220824162459-3.png" height="503" width="798"]]
147
148 {{id name="Iimage-20220824163305-2.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_c9ae84ef5d418580.png||alt="image-20220824163305-2.png" height="1009" width="1920"]]
149
150 **2)Address List**
151
152 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
153 |(% rowspan="4" %)Bit|I|I|M d.o|(((
154 d:0~-~-9999
155
156 o:0-7
157 )))|
158 |Q|Q|Q d.o|(((
159 d:0~-~-9999
160
161 o:0-7
162 )))|
163 |M|M|M d.o|(((
164 d:0~-~-9999
165
166 o:0-7
167 )))|
168 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
169 nn:0-9999,
170
171 dddd:0-9999,
172
173 o:0-7
174 )))|(((
175 nn:DB No.
176
177 dddd:address value
178
179 o: digit address
180 )))
181 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
182 |M|MW|MW d|d:0-99999|(((
183 MW0=MB(0~~1)
184
185 MW2=MB(2~~3)
186
187 Address value is a multiple of 2
188 )))
189 |M|MD|MD d|d:0-99999|(((
190 MD0=MB(0~~3)
191
192 MD4=MB(4~~7)
193
194 Address value is a multiple of 4
195 )))
196 |I|IW|IW d|d:0-99999|
197 |Q|QW|QW d|d:0-99999|
198 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
199 nn:0-9999
200
201 dddd:0-9999
202 )))|(((
203 nn:DB No.
204
205 dddd:address value
206 )))
207 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
208 nn:0-9999
209
210 dddd:0-9999
211 )))|(((
212 nn:DB No.
213
214 dddd:address value
215
216 Address value is a multiple of 2
217 )))
218 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
219 nn:0-9999
220
221 dddd:0-9999
222 )))|(((
223 nn:DB No.
224
225 dddd:address value
226
227 Address value is a multiple of 4
228 )))
229
230 **3)Configure the communication protocol**
231
232 {{id name="Iimage-20220824163448-3.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_9e740a8bf83ea3bf.png||alt="image-20220824163448-3.png" height="557" width="974"]]
233
234 **✎Note:**
235
236 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three V-BOX.
237 * V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
238
239 **4)Cable Wiring**
240
241 {{id name="Iimage-20220824162342-2.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ac8ece9a26719fda.png||alt="image-20220824162342-2.png" height="170" width="401"]]
242
243 == {{id name="HLOGOEthernet"/}}**LOGO Ethernet ** ==
244
245 Supported Series: Siemens Logo 0BA0, 0BA1 series
246
247 **V-BOX Settings**
248
249 |**Items**|**Settings**|**Note**
250 |Protocol|Siemens LOGO|
251 |Connection|Ethernet|
252 |Port No.|102|
253 |PLC station No.|2|
254
255 **Address List**
256
257 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
258 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
259 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
260 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
261 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
262 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
263 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
264 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
265 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
266 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
267 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
268 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
269 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
270 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
271 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
272 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
273
274 **PLC Settings in LOGO Software:**
275
276 Click [Tools]~-~-[Ethernet Connections],shown as below.
277
278 {{id name="IPIStudio.125C.PLCprotocols.WebHome4012.PLCProtocol_html_8b9d2322edf89519.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d13df637bfedcc52.png||alt="12.PLC Protocol_html_8b9d2322edf89519.png" height="641" width="423"]]
279
280 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
281
282 {{id name="IPIStudio.125C.PLCprotocols.WebHome40image-20221228142937-4.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_316247e0130c4c55.png||alt="image-20221228142937-4.png" height="484" width="366"]]
283
284 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
285
286 {{id name="IPIStudio.125C.PLCprotocols.WebHome40image-20221228143047-5.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_facc6ee1af05162f.png||alt="image-20221228143047-5.png" height="626" width="1088"]]
287
288 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
289
290 {{id name="IPIStudio.125C.PLCprotocols.WebHome40image-20221228143246-6.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d43d2b7b2599ee64.png||alt="image-20221228143246-6.png" height="698" width="688"]]
291
292 **V-BOX Communication Settings**
293
294 Set PLC IP in [IP Address] settings;
295
296 {{id name="ILldwDGntf4.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ab570912d299c09.png||alt="LldwDGntf4.png" height="530" width="899"]]
297
298 Enable V-BOX Ethernet in [Network];
299
300 {{id name="IWgvjfWbQif.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_637860db3ca1ca1b.png||alt="WgvjfWbQif.png" height="654" width="1195"]]
301
302 TSAP setting
303
304 * The initialization script needs to set the source TSAP address and the target TSAP address, otherwise the communication will not be successful.
305
306 **function** **init**.main()
307 addr_setword("@W_0#HSW1200",8192) //~-~- Set the source TSAP address//
308 addr_setword("@W_0#HSW1201",4096) //~-~- Set the destination TSAP address//
309 **end**
310
311 Note: The name of the test script is init, 8192 and 4096 are the data used for the test, there is no HSW address in the register option, but you can directly set the value of the corresponding address through the code.
312
313 **✎Note:**
314
315 * **Communication port configuration: **
316 ** Continuous length needs to be set to 0.
317 ** Integration interval needs to be set to 1. (no change may result in data errors)
318 ** Set Port and Device Station NO.
319 ** Other set as defaulted.