Wiki source code of Siemens

Version 45.1 by Theodore Xu on 2023/10/12 16:37

Show last authors
1 == **S7-200 Smart Serial** ==
2
3 **V-BOX setting**
4
5 (% style="width:1323.87px" %)
6 |**Items**|**Settings**|**Note**
7 |Protocol|(% style="width:783px" %)Siemens S7-200 CPU22x/Smart PPI|
8 |Connection|(% style="width:783px" %)RS485|
9 |Baud rate|(% style="width:783px" %)9600|
10 |Data bit|(% style="width:783px" %)8|
11 |Parity|(% style="width:783px" %)EVEN|
12 |Stop bit|(% style="width:783px" %)1|
13 |PLC station No.|(% style="width:783px" %)2|
14
15 (% style="text-align:center" %)
16 [[image:西门子200串口.png]]
17
18 **Address List **
19
20 |**Type**|**Device register**|**Format**|**Range**|**Note**
21 |(% rowspan="9" %)Bit|I|I ddddd.o|0.0~~99999.7|
22 |Q|Q ddddd.o|0.0~~99999.7|
23 |V|VWbit ddddd.o|0.0~~99999.7|
24 |V|V ddddd.o|0.0~~99999.7|
25 |M|M ddddd.o|0.0~~99999.7|
26 |SM|ddddd.o|0.0~~99999.7|
27 |S|ddddd.o|0.0~~99999.7|Read only
28 |T|ddddd|0~~99999|Timer state, read only
29 |C|ddddd|0~~99999|Counter state, read only
30 |(% rowspan="12" %)Word|I|IW ddddd|0~~99999|
31 |Q|QW ddddd|0~~99999|
32 |AI|AIW ddddd|0~~99999|
33 |AQ|VB ddddd|0~~99999|
34 |V|VW ddddd|0~~99998|(((
35 VW0=VB (0~~1)
36
37 VW2=VB (2~~3)
38
39 Address value is a multiple of 2
40 )))
41 |V|VD ddddd|0~~99998|(((
42 VD0=VB (0~~3)
43
44 VD2=VB (4~~7)
45
46 Address value is a multiple of 4
47 )))
48 |M|MB ddddd|0~~99999|
49 |M|MW ddddd|0~~99999|(((
50 MW0=MB(0~~1)
51
52 MW2=MB(2~~3)
53
54 Address value is a multiple of 2
55 )))
56 |M|MD ddddd|0~~99999|(((
57 MD0=MB(0~~3)
58
59 MD4=MB(4~~7)
60
61 Address value is a multiple of 4
62 )))
63 |T|TW ddddd|0~~99999|Value of timer
64 |C|CW ddddd|0~~99999|Value of counter
65 |W|SW ddddd|0~~99999|
66
67 **PLC setting**
68
69 (% style="text-align:center" %)
70 [[image:西门子软件版本.png]]
71
72 (% style="text-align:center" %)
73 [[image:485通讯配置.png]]
74
75 **Connect and Download**
76
77 (% style="text-align:center" %)
78 [[image:以太网 PC和PLC连接.png]]
79
80 (% style="text-align:center" %)
81 [[image:以太网下载.png]]
82
83 **Cable Wiring**
84
85 (% style="text-align:center" %)
86 [[image:485接线.png]]
87
88 == **S7-200 Smart Ethernet ** ==
89
90 **V-BOX setting**
91
92 |**Items**|**Settings**
93 |Protocol|Siemens S7-200 Smart(Ethernet)
94 |Connection|Ethernet
95 |Port No.|102
96 |PLC station No.|2
97
98 (% style="text-align:center" %)
99 [[image:西门子200smart 以太网.png]]
100
101 **PLC setting**
102
103 (% style="text-align:center" %)
104 [[image:西门子软件版本.png]]
105
106 (% style="text-align:center" %)
107 [[image:以太网通讯配置.png]]
108
109 **Connect and Download**
110
111 (% style="text-align:center" %)
112 [[image:以太网 PC和PLC连接.png]]
113
114 (% style="text-align:center" %)
115 [[image:以太网下载.png]]
116
117 **Cable Wiring**
118
119 V-Box : RJ45 Ethernet interface
120
121 PLC : RJ45 Ethernet interface
122
123 (% style="text-align:center" %)
124 [[image:以太网连接.png]]
125
126 == **S7-300 Ethernet ** ==
127
128 Supported Series: Siemens S7-300 series PLC
129
130 **V-BOX setting**
131
132 |**Items**|**Settings**|**Note**
133 |Protocol|Simens S7-300 Ethernet|
134 |Connection|Ethernet|
135 |Port No.|102|
136 |PLC station No.|2|Need to be same as the PLC setting
137
138 **Address List**
139
140 |**Type**|**Device register**|**Format**|**Range**|**Note**
141 |(% rowspan="4" %)Bit|I|I ddddd.o|0.0~~99999.7|
142 |Q|Q ddddd.o|0.0~~99999.7|
143 |M|M ddddd.o|0.0~~99999.7|
144 |DB0.DB~~DB99.DB|DBxDB nndddd.o|0.0~~99999999.7|(((
145 nn: block number;
146
147 dddd: address;
148 )))
149 |(% rowspan="8" %)Word|I|IW ddddd|0~~99999|
150 |Q|QW ddddd|0~~99999|
151 |(% rowspan="3" %)M|MB ddddd|0~~99999|
152 |MW ddddd|0~~99999|(((
153 MW0=MB(0~~1)
154
155 MW2=MB(2~~3)
156
157 Address value is a multiple of 2
158 )))
159 |MD ddddd|0~~99999|(((
160 MD0=MB(0~~3)
161
162 MD4=MB(4~~7)
163
164 Address value is a multiple of 4
165 )))
166 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
167 nn: block number;
168
169 dddd: address
170 )))
171 |DBxDBW nndddd|0~~99999999
172 |DBxDBD nndddd|0~~99999999
173
174 **Configure the communication protocol**
175
176 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_8e00ed9483ddb629.png||alt="image-20220824161345-1.png" height="1011" width="1920"]]
177
178 **Cable Wiring**
179
180 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ac8ece9a26719fda.png||alt="image-20220824161450-2.png" height="170" width="401"]]
181
182 == **S7-1200 Ethernet ** ==
183
184 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]]
185
186 **V-BOX Setting**
187
188 |**Items**|**Settings**|**Note**
189 |Protocol|Siemens S7-1200|
190 |Connection|Ethernet|
191 |Port No.|102|
192 |PLC station No.|2|
193
194 **Address List**
195
196 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
197 |(% rowspan="4" %)Bit|I|I|M d.o|(((
198 d:0~-~-9999
199
200 o:0-7
201 )))|
202 |Q|Q|Q d.o|(((
203 d:0~-~-9999
204
205 o:0-7
206 )))|
207 |M|M|M d.o|(((
208 d:0~-~-9999
209
210 o:0-7
211 )))|
212 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
213 nn:0-9999,
214
215 dddd:0-9999,
216
217 o:0-7
218 )))|(((
219 nn:DB No.
220
221 dddd:address value
222
223 o: digit address
224 )))
225 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
226 |M|MW|MW d|d:0-99999|(((
227 MW0=MB(0~~1)
228
229 MW2=MB(2~~3)
230
231 Address value is a multiple of 2
232 )))
233 |M|MD|MD d|d:0-99999|(((
234 MD0=MB(0~~3)
235
236 MD4=MB(4~~7)
237
238 Address value is a multiple of 4
239 )))
240 |I|IW|IW d|d:0-99999|
241 |Q|QW|QW d|d:0-99999|
242 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
243 nn:0-9999
244
245 dddd:0-9999
246 )))|(((
247 nn:DB No.
248
249 dddd:address value
250 )))
251 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
252 nn:0-9999
253
254 dddd:0-9999
255 )))|(((
256 nn:DB No.
257
258 dddd:address value
259
260 Address value is a multiple of 2
261 )))
262 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
263 nn:0-9999
264
265 dddd:0-9999
266 )))|(((
267 nn:DB No.
268
269 dddd:address value
270
271 Address value is a multiple of 4
272 )))
273
274 **Communication Settings**
275
276 Enable HMI Ethernet in [Project Settings]
277
278 == **S7-XXX Ethernet** ==
279
280 Supported Series: Siemens S7-400, S7-1200 and S7-1500
281
282 **V-BOX setting**
283
284 |=**Items**|=**Settings**|=**Note**
285 |Protocol|Siemens S7-XXX|
286 |Connection|Ethernet|
287 |Port No.|102|
288 |Device No.|Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|
289 |HMI No.|Rack (Default as 0)|
290
291 Slot from TIA Portal is equal to Device No. of V-net
292
293 Rack from TIA Portal is equal to HMI No. of V-net
294
295 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d78bc267e5fc6394.png||alt="image-20220824162459-3.png" height="503" width="798"]]
296
297 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_c9ae84ef5d418580.png||alt="image-20220824163305-2.png" height="1009" width="1920"]]
298
299 **Address List**
300
301 |**Type**|**Device register**|**Format**|**Range**|**Note**
302 |(% rowspan="4" %)Bit|I|M d.o|(((
303 d:0~-~-9999
304
305 o:0-7
306 )))|
307 |Q|Q d.o|(((
308 d:0~-~-9999
309
310 o:0-7
311 )))|
312 |M|M d.o|(((
313 d:0~-~-9999
314
315 o:0-7
316 )))|
317 |DB0.DB-DB99.DB|DBxDBnndddd.o|(((
318 nn:0-9999,
319
320 dddd:0-9999,
321
322 o:0-7
323 )))|(((
324 nn:DB No.
325
326 dddd:address value
327
328 o: digit address
329 )))
330 |(% rowspan="8" %)Word|M|MB d|d:0-99999|
331 |M|MW d|d:0-99999|(((
332 MW0=MB(0~~1)
333
334 MW2=MB(2~~3)
335
336 Address value is a multiple of 2
337 )))
338 |M|MD d|d:0-99999|(((
339 MD0=MB(0~~3)
340
341 MD4=MB(4~~7)
342
343 Address value is a multiple of 4
344 )))
345 |I|IW d|d:0-99999|
346 |Q|QW d|d:0-99999|
347 |DB0.DB-DB99.DB|DBxDBBnndddd|(((
348 nn:0-9999
349
350 dddd:0-9999
351 )))|(((
352 nn:DB No.
353
354 dddd:address value
355 )))
356 |DB0.DB-DB99.DB|DBxDBWnndddd|(((
357 nn:0-9999
358
359 dddd:0-9999
360 )))|(((
361 nn:DB No.
362
363 dddd:address value
364
365 Address value is a multiple of 2
366 )))
367 |DB0.DB-DB99.DB|DBxDBDnndddd|(((
368 nn:0-9999
369
370 dddd:0-9999
371 )))|(((
372 nn:DB No.
373
374 dddd:address value
375
376 Address value is a multiple of 4
377 )))
378
379 **Configure the communication protocol**
380
381 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_9e740a8bf83ea3bf.png||alt="image-20220824163448-3.png" height="557" width="974"]]
382
383 **✎Note:**
384
385 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three V-BOX.
386 * V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
387
388 **Cable Wiring**
389
390 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ac8ece9a26719fda.png||alt="image-20220824162342-2.png" height="170" width="401"]]
391
392 == {{id name="HLOGOEthernet"/}}**LOGO Ethernet ** ==
393
394 Supported Series: Siemens Logo 0BA0, 0BA1 series
395
396 **V-BOX Settings**
397
398 |**Items**|**Settings**|**Note**
399 |Protocol|Siemens LOGO|
400 |Connection|Ethernet|
401 |Port No.|102|
402 |PLC station No.|2|
403
404 **Address List**
405
406 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
407 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
408 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
409 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
410 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
411 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
412 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
413 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
414 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
415 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
416 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
417 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
418 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
419 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
420 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
421 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
422
423 **PLC Settings in LOGO Software:**
424
425 Click [Tools]~-~-[Ethernet Connections],shown as below.
426
427 {{id name="IPIStudio.125C.PLCprotocols.WebHome4012.PLCProtocol_html_8b9d2322edf89519.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d13df637bfedcc52.png||alt="12.PLC Protocol_html_8b9d2322edf89519.png" height="641" width="423"]]
428
429 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
430
431 {{id name="IPIStudio.125C.PLCprotocols.WebHome40image-20221228142937-4.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_316247e0130c4c55.png||alt="image-20221228142937-4.png" height="484" width="366"]]
432
433 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
434
435 {{id name="IPIStudio.125C.PLCprotocols.WebHome40image-20221228143047-5.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_facc6ee1af05162f.png||alt="image-20221228143047-5.png" height="626" width="1088"]]
436
437 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
438
439 {{id name="IPIStudio.125C.PLCprotocols.WebHome40image-20221228143246-6.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d43d2b7b2599ee64.png||alt="image-20221228143246-6.png" height="698" width="688"]]
440
441 **V-BOX Communication Settings**
442
443 Set PLC IP in [IP Address] settings;
444
445 {{id name="ILldwDGntf4.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ab570912d299c09.png||alt="LldwDGntf4.png" height="530" width="899"]]
446
447 Enable V-BOX Ethernet in [Network];
448
449 {{id name="IWgvjfWbQif.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_637860db3ca1ca1b.png||alt="WgvjfWbQif.png" height="654" width="1195"]]
450
451 TSAP setting
452
453 * The initialization script needs to set the source TSAP address and the target TSAP address, otherwise the communication will not be successful.
454
455 **function** **init**.main()
456 addr_setword("@W_0#HSW1200",8192) //~-~- Set the source TSAP address//
457 addr_setword("@W_0#HSW1201",4096) //~-~- Set the destination TSAP address//
458 **end**
459
460 Note: The name of the test script is init, 8192 and 4096 are the data used for the test, there is no HSW address in the register option, but you can directly set the value of the corresponding address through the code.
461
462 **✎Note:**
463
464 * **Communication port configuration: **
465 ** Continuous length needs to be set to 0.
466 ** Integration interval needs to be set to 1. (no change may result in data errors)
467 ** Set Port and Device Station NO.
468 ** Other set as defaulted.