1 == **S7-200 Smart Serial** ==
2
3 **V-BOX setting**
4
5 (% style="width:1323.87px" %)
6 |**Items**|**Settings**|**Note**
7 |Protocol|(% style="width:783px" %)Siemens S7-200 CPU22x/Smart PPI|
8 |Connection|(% style="width:783px" %)RS485|
9 |Baud rate|(% style="width:783px" %)9600|
10 |Data bit|(% style="width:783px" %)8|
11 |Parity|(% style="width:783px" %)EVEN|
12 |Stop bit|(% style="width:783px" %)1|
13 |PLC station No.|(% style="width:783px" %)2|
14
15 (% style="text-align:center" %)
16 [[image:西门子200串口.png]]
17
18 **Address List **
19
20 |**Type**|**Device register**|**Format**|**Range**|**Note**
21 |(% rowspan="9" %)Bit|I|I ddddd.o|0.0~~99999.7|
22 |Q|Q ddddd.o|0.0~~99999.7|
23 |V|VWbit ddddd.o|0.0~~99999.7|
24 |V|V ddddd.o|0.0~~99999.7|
25 |M|M ddddd.o|0.0~~99999.7|
26 |SM|ddddd.o|0.0~~99999.7|
27 |S|ddddd.o|0.0~~99999.7|Read only
28 |T|ddddd|0~~99999|Timer state, read only
29 |C|ddddd|0~~99999|Counter state, read only
30 |(% rowspan="12" %)Word|I|IW ddddd|0~~99999|
31 |Q|QW ddddd|0~~99999|
32 |AI|AIW ddddd|0~~99999|
33 |AQ|VB ddddd|0~~99999|
34 |V|VW ddddd|0~~99998|(((
35 VW0=VB (0~~1)
36
37 VW2=VB (2~~3)
38
39 Address value is a multiple of 2
40 )))
41 |V|VD ddddd|0~~99998|(((
42 VD0=VB (0~~3)
43
44 VD2=VB (4~~7)
45
46 Address value is a multiple of 4
47 )))
48 |M|MB ddddd|0~~99999|
49 |M|MW ddddd|0~~99999|(((
50 MW0=MB(0~~1)
51
52 MW2=MB(2~~3)
53
54 Address value is a multiple of 2
55 )))
56 |M|MD ddddd|0~~99999|(((
57 MD0=MB(0~~3)
58
59 MD4=MB(4~~7)
60
61 Address value is a multiple of 4
62 )))
63 |T|TW ddddd|0~~99999|Value of timer
64 |C|CW ddddd|0~~99999|Value of counter
65 |W|SW ddddd|0~~99999|
66
67 **PLC setting**
68
69 (% style="text-align:center" %)
70 [[image:西门子软件版本.png]]
71
72 (% style="text-align:center" %)
73 [[image:485通讯配置.png]]
74
75 **Connect and Download**
76
77 (% style="text-align:center" %)
78 [[image:以太网 PC和PLC连接.png]]
79
80 (% style="text-align:center" %)
81 [[image:以太网下载.png]]
82
83 **Cable Wiring**
84
85 (% style="text-align:center" %)
86 [[image:485接线.png]]
87
88 == **S7-200 Smart Ethernet ** ==
89
90 **V-BOX setting**
91
92 |**Items**|**Settings**
93 |Protocol|Siemens S7-200 Smart(Ethernet)
94 |Connection|Ethernet
95 |Port No.|102
96 |PLC station No.|2
97
98 (% style="text-align:center" %)
99 [[image:西门子200smart 以太网.png]]
100
101 **PLC setting**
102
103 (% style="text-align:center" %)
104 [[image:西门子软件版本.png]]
105
106 (% style="text-align:center" %)
107 [[image:以太网通讯配置.png]]
108
109 **Connect and Download**
110
111 (% style="text-align:center" %)
112 [[image:以太网 PC和PLC连接.png]]
113
114 (% style="text-align:center" %)
115 [[image:以太网下载.png]]
116
117 **Cable Wiring**
118
119 V-Box : RJ45 Ethernet interface
120
121 PLC : RJ45 Ethernet interface
122
123 (% style="text-align:center" %)
124 [[image:以太网连接.png]]
125
126 == **S7-300 Ethernet ** ==
127
128 Supported Series: Siemens S7-300 series PLC
129
130 **V-BOX setting**
131
132 |**Items**|**Settings**|**Note**
133 |Protocol|Simens S7-300 Ethernet|
134 |Connection|Ethernet|
135 |Port No.|102|
136 |PLC station No.|2|Need to be same as the PLC setting
137
138 **Address List**
139
140 |**Type**|**Device register**|**Format**|**Range**|**Note**
141 |(% rowspan="4" %)Bit|I|I ddddd.o|0.0~~99999.7|
142 |Q|Q ddddd.o|0.0~~99999.7|
143 |M|M ddddd.o|0.0~~99999.7|
144 |DB0.DB~~DB99.DB|DBxDB nndddd.o|0.0~~99999999.7|(((
145 nn: block number;
146
147 dddd: address;
148 )))
149 |(% rowspan="8" %)Word|I|IW ddddd|0~~99999|
150 |Q|QW ddddd|0~~99999|
151 |(% rowspan="3" %)M|MB ddddd|0~~99999|
152 |MW ddddd|0~~99999|(((
153 MW0=MB(0~~1)
154
155 MW2=MB(2~~3)
156
157 Address value is a multiple of 2
158 )))
159 |MD ddddd|0~~99999|(((
160 MD0=MB(0~~3)
161
162 MD4=MB(4~~7)
163
164 Address value is a multiple of 4
165 )))
166 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
167 nn: block number;
168
169 dddd: address
170 )))
171 |DBxDBW nndddd|0~~99999999
172 |DBxDBD nndddd|0~~99999999
173
174 **Configure the communication protocol**
175
176 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_8e00ed9483ddb629.png||alt="image-20220824161345-1.png" height="1011" width="1920"]]
177
178 **Cable Wiring**
179
180 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ac8ece9a26719fda.png||alt="image-20220824161450-2.png" height="170" width="401"]]
181
182 == **S7-1200 Ethernet ** ==
183
184 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]]
185
186 **V-BOX Setting**
187
188 |**Items**|**Settings**|**Note**
189 |Protocol|Siemens S7-1200|
190 |Connection|Ethernet|
191 |Port No.|102|
192 |PLC station No.|2|
193
194 (% style="text-align:center" %)
195 [[image:西门子1200协议参数.png]]
196
197 **Address List**
198
199 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
200 |(% rowspan="4" %)Bit|I|I|M d.o|(((
201 d:0~-~-9999
202
203 o:0-7
204 )))|
205 |Q|Q|Q d.o|(((
206 d:0~-~-9999
207
208 o:0-7
209 )))|
210 |M|M|M d.o|(((
211 d:0~-~-9999
212
213 o:0-7
214 )))|
215 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
216 nn:0-9999,
217
218 dddd:0-9999,
219
220 o:0-7
221 )))|(((
222 nn:DB No.
223
224 dddd:address value
225
226 o: digit address
227 )))
228 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
229 |M|MW|MW d|d:0-99999|(((
230 MW0=MB(0~~1)
231
232 MW2=MB(2~~3)
233
234 Address value is a multiple of 2
235 )))
236 |M|MD|MD d|d:0-99999|(((
237 MD0=MB(0~~3)
238
239 MD4=MB(4~~7)
240
241 Address value is a multiple of 4
242 )))
243 |I|IW|IW d|d:0-99999|
244 |Q|QW|QW d|d:0-99999|
245 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
246 nn:0-9999
247
248 dddd:0-9999
249 )))|(((
250 nn:DB No.
251
252 dddd:address value
253 )))
254 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
255 nn:0-9999
256
257 dddd:0-9999
258 )))|(((
259 nn:DB No.
260
261 dddd:address value
262
263 Address value is a multiple of 2
264 )))
265 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
266 nn:0-9999
267
268 dddd:0-9999
269 )))|(((
270 nn:DB No.
271
272 dddd:address value
273
274 Address value is a multiple of 4
275 )))
276
277 {{info}}
278 ✎Note:
279
280 * The S7-1200 supports simultaneous connection of three devices.
281 * V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (S7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
282 * S7-1200 String type, the default first two bytes are used to store the maximum character and valid characters, so the text data will be shifted back one word address. When interacting with the data, what way this address plc is displayed with is unknown. And because of an extra word of data causes us to display the wrong. The solution is if we use String, then the actual data address we want to operate on is actually shifted back two bytes, so as long as the address on the project is shifted back 2 bits to correspond with the actual data address.
283 {{/info}}
284
285 **PLC Settings**
286
287 Add BD
288
289 * Please uncheck [Symbolic access only] option;
290
291 (% style="text-align:center" %)
292 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_872ec32d12b55aa.png]]
293
294 Address settings, using BD2 as example.
295
296 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
297 * 2 represent DB block number
298 * xxxx represent address
299
300 **Such as:**
301
302 * DBxDBB20000 = DB2.DBB0
303 * DBxDBW20004 = DB2.DBW4
304
305 (% style="text-align:center" %)
306 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_8ee8d3ac3637bfc4.png]]
307
308 **How to connect with S7-1200 Firmware V4.0**
309
310 PLC configuration
311
312 * Double click [device configuration] in Siemens via software
313 * Double click [protection] to enter protection configuration screen
314
315 (% style="text-align:center" %)
316 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_664a826cd356c830.png]]
317
318 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
319
320 (% style="text-align:center" %)
321 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_78026942a88f0fdb.png]]
322
323 DB settings
324
325 * Right click [DB], select [properties]
326 * Uncheck [optimized block access]
327
328 **Cable Wiring**
329
330 (% style="text-align:center" %)
331 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ac8ece9a26719fda.png]]
332
333 == **S7-XXX Ethernet** ==
334
335 Supported Series: Siemens S7-400, S7-1200 and S7-1500
336
337 **V-BOX setting**
338
339 |=**Items**|=**Settings**|=**Note**
340 |Protocol|Siemens S7-XXX|
341 |Connection|Ethernet|
342 |Port No.|102|
343 |Device No.|Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|
344 |HMI No.|Rack (Default as 0)|
345
346 Slot from TIA Portal is equal to Device No. of V-net
347
348 Rack from TIA Portal is equal to HMI No. of V-net
349
350 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d78bc267e5fc6394.png||alt="image-20220824162459-3.png" height="503" width="798"]]
351
352 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_c9ae84ef5d418580.png||alt="image-20220824163305-2.png" height="1009" width="1920"]]
353
354 **Address List**
355
356 |**Type**|**Device register**|**Format**|**Range**|**Note**
357 |(% rowspan="4" %)Bit|I|M d.o|(((
358 d:0~-~-9999
359
360 o:0-7
361 )))|
362 |Q|Q d.o|(((
363 d:0~-~-9999
364
365 o:0-7
366 )))|
367 |M|M d.o|(((
368 d:0~-~-9999
369
370 o:0-7
371 )))|
372 |DB0.DB-DB99.DB|DBxDBnndddd.o|(((
373 nn:0-9999,
374
375 dddd:0-9999,
376
377 o:0-7
378 )))|(((
379 nn:DB No.
380
381 dddd:address value
382
383 o: digit address
384 )))
385 |(% rowspan="8" %)Word|M|MB d|d:0-99999|
386 |M|MW d|d:0-99999|(((
387 MW0=MB(0~~1)
388
389 MW2=MB(2~~3)
390
391 Address value is a multiple of 2
392 )))
393 |M|MD d|d:0-99999|(((
394 MD0=MB(0~~3)
395
396 MD4=MB(4~~7)
397
398 Address value is a multiple of 4
399 )))
400 |I|IW d|d:0-99999|
401 |Q|QW d|d:0-99999|
402 |DB0.DB-DB99.DB|DBxDBBnndddd|(((
403 nn:0-9999
404
405 dddd:0-9999
406 )))|(((
407 nn:DB No.
408
409 dddd:address value
410 )))
411 |DB0.DB-DB99.DB|DBxDBWnndddd|(((
412 nn:0-9999
413
414 dddd:0-9999
415 )))|(((
416 nn:DB No.
417
418 dddd:address value
419
420 Address value is a multiple of 2
421 )))
422 |DB0.DB-DB99.DB|DBxDBDnndddd|(((
423 nn:0-9999
424
425 dddd:0-9999
426 )))|(((
427 nn:DB No.
428
429 dddd:address value
430
431 Address value is a multiple of 4
432 )))
433
434 **Configure the communication protocol**
435
436 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_9e740a8bf83ea3bf.png||alt="image-20220824163448-3.png" height="557" width="974"]]
437
438 **✎Note:**
439
440 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three V-BOX.
441 * V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
442
443 **Cable Wiring**
444
445 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ac8ece9a26719fda.png||alt="image-20220824162342-2.png" height="170" width="401"]]
446
447 == {{id name="HLOGOEthernet"/}}**LOGO Ethernet ** ==
448
449 Supported Series: Siemens Logo 0BA0, 0BA1 series
450
451 **V-BOX Settings**
452
453 |**Items**|**Settings**|**Note**
454 |Protocol|Siemens LOGO|
455 |Connection|Ethernet|
456 |Port No.|102|
457 |PLC station No.|2|
458
459 **Address List**
460
461 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
462 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
463 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
464 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
465 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
466 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
467 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
468 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
469 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
470 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
471 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
472 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
473 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
474 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
475 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
476 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
477
478 **PLC Settings in LOGO Software:**
479
480 Click [Tools]~-~-[Ethernet Connections],shown as below.
481
482 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d13df637bfedcc52.png||alt="12.PLC Protocol_html_8b9d2322edf89519.png" height="641" width="423"]]
483
484 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
485
486 (% style="text-align:center" %)
487 [[image:hXadxkZTuR.png]]
488
489 **TSAP set**: The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
490
491 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_facc6ee1af05162f.png||alt="image-20221228143047-5.png" height="626" width="1088"]]
492
493 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
494
495 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d43d2b7b2599ee64.png||alt="image-20221228143246-6.png" height="698" width="688"]]
496
497 **V-BOX Communication Settings**
498
499 Set PLC IP in [IP Address] settings;
500
501 (% style="text-align:center" %)
502 [[image:V-NET_Client logo.png]]
503
504 TSAP setting
505
506 * The initialization script needs to set the source TSAP address and the target TSAP address, otherwise the communication will not be successful.
507
508 You can copy the following script into V-net directly.
509
510 (% class="box successmessage" %)
511 (((
512 **function** **init**.main()
513 addr_setword("@W_0#HSW1200",8192) //~-~- Set the source TSAP address//
514 addr_setword("@W_0#HSW1201",4096) //~-~- Set the destination TSAP address//
515 **end**
516 )))
517
518 (% class="box infomessage" %)
519 (((
520 Note:
521 The name of the test script must be “init”, 8192 and 4096 are the data used for the test, there is no HSW address in the register option, but you can directly set the value of the corresponding address through the code.
522 )))
523
524 **✎Note:**
525
526 * **Communication port configuration: **
527 ** Continuous length needs to be set to 0.
528 ** Integration interval needs to be set to 1. (no change may result in data errors)
529 ** Set Port and Device Station NO.
530 ** Other set as defaulted.
531 * **Notes on the use of registers:**
532 ** Register VD: Use only registers that are multiples of 4, such as 0, 4, 8, etc.
533 ** Register VW: Use only registers they are multiples of 2, such as 0, 2, 4 etc. (Using an odd-length register may result in data errors, such as 2 3 4 )