Wiki source code of Siemens

Version 51.1 by Joe on 2024/06/11 18:41

Show last authors
1 == **S7-200 Smart Serial** ==
2
3 **V-BOX setting**
4
5 (% style="width:1323.87px" %)
6 |**Items**|**Settings**|**Note**
7 |Protocol|(% style="width:783px" %)Siemens S7-200 CPU22x/Smart PPI|
8 |Connection|(% style="width:783px" %)RS485|
9 |Baud rate|(% style="width:783px" %)9600|
10 |Data bit|(% style="width:783px" %)8|
11 |Parity|(% style="width:783px" %)EVEN|
12 |Stop bit|(% style="width:783px" %)1|
13 |PLC station No.|(% style="width:783px" %)2|
14
15 (% style="text-align:center" %)
16 [[image:西门子200串口.png]]
17
18 **Address List **
19
20 |**Type**|**Device register**|**Format**|**Range**|**Note**
21 |(% rowspan="9" %)Bit|I|I ddddd.o|0.0~~99999.7|
22 |Q|Q ddddd.o|0.0~~99999.7|
23 |V|VWbit ddddd.o|0.0~~99999.7|
24 |V|V ddddd.o|0.0~~99999.7|
25 |M|M ddddd.o|0.0~~99999.7|
26 |SM|ddddd.o|0.0~~99999.7|
27 |S|ddddd.o|0.0~~99999.7|Read only
28 |T|ddddd|0~~99999|Timer state, read only
29 |C|ddddd|0~~99999|Counter state, read only
30 |(% rowspan="12" %)Word|I|IW ddddd|0~~99999|
31 |Q|QW ddddd|0~~99999|
32 |AI|AIW ddddd|0~~99999|
33 |AQ|VB ddddd|0~~99999|
34 |V|VW ddddd|0~~99998|(((
35 VW0=VB (0~~1)
36
37 VW2=VB (2~~3)
38
39 Address value is a multiple of 2
40 )))
41 |V|VD ddddd|0~~99998|(((
42 VD0=VB (0~~3)
43
44 VD2=VB (4~~7)
45
46 Address value is a multiple of 4
47 )))
48 |M|MB ddddd|0~~99999|
49 |M|MW ddddd|0~~99999|(((
50 MW0=MB(0~~1)
51
52 MW2=MB(2~~3)
53
54 Address value is a multiple of 2
55 )))
56 |M|MD ddddd|0~~99999|(((
57 MD0=MB(0~~3)
58
59 MD4=MB(4~~7)
60
61 Address value is a multiple of 4
62 )))
63 |T|TW ddddd|0~~99999|Value of timer
64 |C|CW ddddd|0~~99999|Value of counter
65 |W|SW ddddd|0~~99999|
66
67 **PLC setting**
68
69 (% style="text-align:center" %)
70 [[image:西门子软件版本.png]]
71
72 (% style="text-align:center" %)
73 [[image:485通讯配置.png]]
74
75 **Connect and Download**
76
77 (% style="text-align:center" %)
78 [[image:以太网 PC和PLC连接.png]]
79
80 (% style="text-align:center" %)
81 [[image:以太网下载.png]]
82
83 **Cable Wiring**
84
85 (% style="text-align:center" %)
86 [[image:485接线.png]]
87
88 == **S7-200 Smart Ethernet ** ==
89
90 **V-BOX setting**
91
92 |**Items**|**Settings**
93 |Protocol|Siemens S7-200 Smart(Ethernet)
94 |Connection|Ethernet
95 |Port No.|102
96 |PLC station No.|2
97
98 (% style="text-align:center" %)
99 [[image:西门子200smart 以太网.png]]
100
101 **PLC setting**
102
103 (% style="text-align:center" %)
104 [[image:西门子软件版本.png]]
105
106 (% style="text-align:center" %)
107 [[image:以太网通讯配置.png]]
108
109 **Connect and Download**
110
111 (% style="text-align:center" %)
112 [[image:以太网 PC和PLC连接.png]]
113
114 (% style="text-align:center" %)
115 [[image:以太网下载.png]]
116
117 **Cable Wiring**
118
119 V-Box : RJ45 Ethernet interface
120
121 PLC : RJ45 Ethernet interface
122
123 (% style="text-align:center" %)
124 [[image:以太网连接.png]]
125
126 == **S7-300 Ethernet ** ==
127
128 Supported Series: Siemens S7-300 series PLC
129
130 **V-BOX setting**
131
132 |**Items**|**Settings**|**Note**
133 |Protocol|Simens S7-300 Ethernet|
134 |Connection|Ethernet|
135 |Port No.|102|
136 |PLC station No.|2|Need to be same as the PLC setting
137
138 **Address List**
139
140 |**Type**|**Device register**|**Format**|**Range**|**Note**
141 |(% rowspan="4" %)Bit|I|I ddddd.o|0.0~~99999.7|
142 |Q|Q ddddd.o|0.0~~99999.7|
143 |M|M ddddd.o|0.0~~99999.7|
144 |DB0.DB~~DB99.DB|DBxDB nndddd.o|0.0~~99999999.7|(((
145 nn: block number;
146
147 dddd: address;
148 )))
149 |(% rowspan="8" %)Word|I|IW ddddd|0~~99999|
150 |Q|QW ddddd|0~~99999|
151 |(% rowspan="3" %)M|MB ddddd|0~~99999|
152 |MW ddddd|0~~99999|(((
153 MW0=MB(0~~1)
154
155 MW2=MB(2~~3)
156
157 Address value is a multiple of 2
158 )))
159 |MD ddddd|0~~99999|(((
160 MD0=MB(0~~3)
161
162 MD4=MB(4~~7)
163
164 Address value is a multiple of 4
165 )))
166 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
167 nn: block number;
168
169 dddd: address
170 )))
171 |DBxDBW nndddd|0~~99999999
172 |DBxDBD nndddd|0~~99999999
173
174 **Configure the communication protocol**
175
176 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_8e00ed9483ddb629.png||alt="image-20220824161345-1.png" height="1011" width="1920"]]
177
178 **Cable Wiring**
179
180 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ac8ece9a26719fda.png||alt="image-20220824161450-2.png" height="170" width="401"]]
181
182 == **S7-1200 Ethernet ** ==
183
184 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]]
185
186 **V-BOX Setting**
187
188 |**Items**|**Settings**|**Note**
189 |Protocol|Siemens S7-1200|
190 |Connection|Ethernet|
191 |Port No.|102|
192 |PLC station No.|2|
193
194 (% style="text-align:center" %)
195 [[image:西门子1200协议参数.png]]
196
197 **Address List**
198
199 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
200 |(% rowspan="4" %)Bit|I|I|M d.o|(((
201 d:0~-~-9999
202
203 o:0-7
204 )))|
205 |Q|Q|Q d.o|(((
206 d:0~-~-9999
207
208 o:0-7
209 )))|
210 |M|M|M d.o|(((
211 d:0~-~-9999
212
213 o:0-7
214 )))|
215 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
216 nn:0-9999,
217
218 dddd:0-9999,
219
220 o:0-7
221 )))|(((
222 nn:DB No.
223
224 dddd:address value
225
226 o: digit address
227 )))
228 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
229 |M|MW|MW d|d:0-99999|(((
230 MW0=MB(0~~1)
231
232 MW2=MB(2~~3)
233
234 Address value is a multiple of 2
235 )))
236 |M|MD|MD d|d:0-99999|(((
237 MD0=MB(0~~3)
238
239 MD4=MB(4~~7)
240
241 Address value is a multiple of 4
242 )))
243 |I|IW|IW d|d:0-99999|
244 |Q|QW|QW d|d:0-99999|
245 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
246 nn:0-9999
247
248 dddd:0-9999
249 )))|(((
250 nn:DB No.
251
252 dddd:address value
253 )))
254 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
255 nn:0-9999
256
257 dddd:0-9999
258 )))|(((
259 nn:DB No.
260
261 dddd:address value
262
263 Address value is a multiple of 2
264 )))
265 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
266 nn:0-9999
267
268 dddd:0-9999
269 )))|(((
270 nn:DB No.
271
272 dddd:address value
273
274 Address value is a multiple of 4
275 )))
276
277 {{info}}
278 ✎Note:
279
280 * The S7-1200 supports simultaneous connection of three devices.
281 * V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (S7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
282 * S7-1200 String type, the default first two bytes are used to store the maximum character and valid characters, so the text data will be shifted back one word address. When interacting with the data, what way this address plc is displayed with is unknown. And because of an extra word of data causes us to display the wrong. The solution is if we use String, then the actual data address we want to operate on is actually shifted back two bytes, so as long as the address on the project is shifted back 2 bits to correspond with the actual data address.
283 {{/info}}
284
285 **PLC Settings**
286
287
288 In the Project tree [PLC project]→Right-click[PLC-1]→[Properties]→[General]→[PROFINE interface]→[Add new subnet]→[IP address]192.168.40.20,[Subnet mask]255.255.255.0→[OK]
289
290 (% style="text-align:center" %)
291 [[image:图片1.png]]
292
293 Open [Properties] again→[General]→[Protection&Security]→[Connection mechanisms]→Check [Permit access with PUTIGET communication remote partner ]→[OK]
294
295 (% style="text-align:center" %)
296 [[image:图片2.png]]
297
298
299 Address settings, using BD2 as example.
300
301 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
302 * 2 represent DB block number
303 * xxxx represent address
304
305 **Such as:**
306
307 * DBxDBB20000 = DB2.DBB0
308 * DBxDBW20004 = DB2.DBW4
309
310 (% style="text-align:center" %)
311 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_8ee8d3ac3637bfc4.png]]
312
313 **How to setting String in PLC and V-net**
314 PLC configuration
315
316 choosing Data type~-~-String→add"[]" after String and input data length
317
318 (% style="text-align:center" %)
319 [[image:yUYuRVmMcL.png]]
320
321 V-box configuration
322
323 (% style="text-align:center" %)
324 [[image:BSRBeEWL0O.png]]
325
326 choosing Word and DBxDBW →input  Register Main No. →Data format is String →input data length you want to use → choosing Byte order~-~-Little-endian
327
328 (% class="box infomessage" %)
329 (((
330 Note: Register Main No. = offset in PLC + 2
331 For example, the image above has an offset of 4, so the register Main No. is 10006
332 If an offset is 8, the register Main No. is 10010
333 )))
334
335 **How to connect with S7-1200 Firmware V4.0**
336
337 PLC configuration
338
339 * Double click [device configuration] in Siemens via software
340 * Double click [protection] to enter protection configuration screen
341
342 (% style="text-align:center" %)
343 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_664a826cd356c830.png]]
344
345 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
346
347 (% style="text-align:center" %)
348 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_78026942a88f0fdb.png]]
349
350 DB settings
351
352 * Right click [DB], select [properties]
353 * Uncheck [optimized block access]
354
355 **Cable Wiring**
356
357 (% style="text-align:center" %)
358 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ac8ece9a26719fda.png]]
359
360 == **S7-XXX Ethernet** ==
361
362 Supported Series: Siemens S7-400, S7-1200 and S7-1500
363
364 **V-BOX setting**
365
366 |=**Items**|=**Settings**|=**Note**
367 |Protocol|Siemens S7-XXX|
368 |Connection|Ethernet|
369 |Port No.|102|
370 |Device No.|Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|
371 |HMI No.|Rack (Default as 0)|
372
373 Slot from TIA Portal is equal to Device No. of V-net
374
375 Rack from TIA Portal is equal to HMI No. of V-net
376
377 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d78bc267e5fc6394.png||alt="image-20220824162459-3.png" height="503" width="798"]]
378
379 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_c9ae84ef5d418580.png||alt="image-20220824163305-2.png" height="1009" width="1920"]]
380
381 **Address List**
382
383 |**Type**|**Device register**|**Format**|**Range**|**Note**
384 |(% rowspan="4" %)Bit|I|M d.o|(((
385 d:0~-~-9999
386
387 o:0-7
388 )))|
389 |Q|Q d.o|(((
390 d:0~-~-9999
391
392 o:0-7
393 )))|
394 |M|M d.o|(((
395 d:0~-~-9999
396
397 o:0-7
398 )))|
399 |DB0.DB-DB99.DB|DBxDBnndddd.o|(((
400 nn:0-9999,
401
402 dddd:0-9999,
403
404 o:0-7
405 )))|(((
406 nn:DB No.
407
408 dddd:address value
409
410 o: digit address
411 )))
412 |(% rowspan="8" %)Word|M|MB d|d:0-99999|
413 |M|MW d|d:0-99999|(((
414 MW0=MB(0~~1)
415
416 MW2=MB(2~~3)
417
418 Address value is a multiple of 2
419 )))
420 |M|MD d|d:0-99999|(((
421 MD0=MB(0~~3)
422
423 MD4=MB(4~~7)
424
425 Address value is a multiple of 4
426 )))
427 |I|IW d|d:0-99999|
428 |Q|QW d|d:0-99999|
429 |DB0.DB-DB99.DB|DBxDBBnndddd|(((
430 nn:0-9999
431
432 dddd:0-9999
433 )))|(((
434 nn:DB No.
435
436 dddd:address value
437 )))
438 |DB0.DB-DB99.DB|DBxDBWnndddd|(((
439 nn:0-9999
440
441 dddd:0-9999
442 )))|(((
443 nn:DB No.
444
445 dddd:address value
446
447 Address value is a multiple of 2
448 )))
449 |DB0.DB-DB99.DB|DBxDBDnndddd|(((
450 nn:0-9999
451
452 dddd:0-9999
453 )))|(((
454 nn:DB No.
455
456 dddd:address value
457
458 Address value is a multiple of 4
459 )))
460
461 **Configure the communication protocol**
462
463 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_9e740a8bf83ea3bf.png||alt="image-20220824163448-3.png" height="557" width="974"]]
464
465 **✎Note:**
466
467 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three V-BOX.
468 * V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
469
470 **Cable Wiring**
471
472 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ac8ece9a26719fda.png||alt="image-20220824162342-2.png" height="170" width="401"]]
473
474 == {{id name="HLOGOEthernet"/}}**LOGO Ethernet ** ==
475
476 Supported Series: Siemens Logo 0BA0, 0BA1 series
477
478 **V-BOX Settings**
479
480 |**Items**|**Settings**|**Note**
481 |Protocol|Siemens LOGO|
482 |Connection|Ethernet|
483 |Port No.|102|
484 |PLC station No.|2|
485
486 **Address List**
487
488 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
489 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
490 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
491 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
492 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
493 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
494 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
495 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
496 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
497 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
498 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
499 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
500 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
501 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
502 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
503 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
504
505 **PLC Settings in LOGO Software:**
506
507 Click [Tools]~-~-[Ethernet Connections],shown as below.
508
509 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d13df637bfedcc52.png||alt="12.PLC Protocol_html_8b9d2322edf89519.png" height="641" width="423"]]
510
511 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
512
513
514 (% style="text-align:center" %)
515 [[image:1iZSZTpAdk.png]]
516
517 **TSAP set**: The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite, shown as below.
518
519 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_facc6ee1af05162f.png||alt="image-20221228143047-5.png" height="626" width="1088"]]
520
521 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
522
523 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d43d2b7b2599ee64.png||alt="image-20221228143246-6.png" height="698" width="688"]]
524
525 **V-BOX Communication Settings**
526
527 Set PLC IP in [IP Address] settings;
528
529 (% style="text-align:center" %)
530 [[image:V-NET_Client logo.png]]
531
532 TSAP setting
533
534 * The initialization script needs to set the source TSAP address and the target TSAP address, otherwise the communication will not be successful.
535
536 You can copy the following script into V-net directly.
537
538 (% class="box successmessage" %)
539 (((
540 **function** **init**.main()
541 addr_setword("@W_0#HSW1200",8192) //~-~- Set the source TSAP address//
542 addr_setword("@W_0#HSW1201",4096) //~-~- Set the destination TSAP address//
543 **end**
544 )))
545
546 (% class="box infomessage" %)
547 (((
548 Note:
549 The name of the test script must be “init”, 8192 and 4096 are the data used for the test, there is no HSW address in the register option, but you can directly set the value of the corresponding address through the code.
550 )))
551
552 **✎Note:**
553
554 * **Communication port configuration: **
555 ** Continuous length needs to be set to 0.
556 ** Integration interval needs to be set to 1. (no change may result in data errors)
557 ** Set Port and Device Station NO.
558 ** Other set as defaulted.