Theodore Xu 16.1 1 == **S7-200 Smart Serial** ==
2
Theodore Xu 31.1 3 **V-BOX setting**
Theodore Xu 27.1 4
Theodore Xu 33.1 5 (% style="width:1323.87px" %)
Theodore Xu 37.1 6 |**Items**|**Settings**|**Note**
7 |Protocol|(% style="width:783px" %)Siemens S7-200 CPU22x/Smart PPI|
8 |Connection|(% style="width:783px" %)RS485|
9 |Baud rate|(% style="width:783px" %)9600|
10 |Data bit|(% style="width:783px" %)8|
11 |Parity|(% style="width:783px" %)EVEN|
12 |Stop bit|(% style="width:783px" %)1|
13 |PLC station No.|(% style="width:783px" %)2|
Theodore Xu 27.1 14
15 (% style="text-align:center" %)
16 [[image:西门子200串口.png]]
17
Theodore Xu 31.1 18 **Address List **
Theodore Xu 27.1 19
Theodore Xu 39.1 20 |**Type**|**Device register**|**Format**|**Range**|**Note**
21 |(% rowspan="9" %)Bit|I|I ddddd.o|0.0~~99999.7|
22 |Q|Q ddddd.o|0.0~~99999.7|
23 |V|VWbit ddddd.o|0.0~~99999.7|
24 |V|V ddddd.o|0.0~~99999.7|
25 |M|M ddddd.o|0.0~~99999.7|
26 |SM|ddddd.o|0.0~~99999.7|
27 |S|ddddd.o|0.0~~99999.7|Read only
28 |T|ddddd|0~~99999|Timer state, read only
29 |C|ddddd|0~~99999|Counter state, read only
30 |(% rowspan="12" %)Word|I|IW ddddd|0~~99999|
31 |Q|QW ddddd|0~~99999|
32 |AI|AIW ddddd|0~~99999|
33 |AQ|VB ddddd|0~~99999|
34 |V|VW ddddd|0~~99998|(((
Theodore Xu 26.1 35 VW0=VB (0~~1)
36
37 VW2=VB (2~~3)
38
39 Address value is a multiple of 2
40 )))
Theodore Xu 39.1 41 |V|VD ddddd|0~~99998|(((
Theodore Xu 26.1 42 VD0=VB (0~~3)
43
44 VD2=VB (4~~7)
45
46 Address value is a multiple of 4
47 )))
Theodore Xu 39.1 48 |M|MB ddddd|0~~99999|
49 |M|MW ddddd|0~~99999|(((
Theodore Xu 26.1 50 MW0=MB(0~~1)
51
52 MW2=MB(2~~3)
53
54 Address value is a multiple of 2
55 )))
Theodore Xu 39.1 56 |M|MD ddddd|0~~99999|(((
Theodore Xu 26.1 57 MD0=MB(0~~3)
58
59 MD4=MB(4~~7)
60
61 Address value is a multiple of 4
62 )))
Theodore Xu 39.1 63 |T|TW ddddd|0~~99999|Value of timer
64 |C|CW ddddd|0~~99999|Value of counter
65 |W|SW ddddd|0~~99999|
Theodore Xu 26.1 66
Theodore Xu 31.1 67 **PLC setting**
Theodore Xu 20.1 68
69 (% style="text-align:center" %)
70 [[image:西门子软件版本.png]]
71
72 (% style="text-align:center" %)
73 [[image:485通讯配置.png]]
74
Theodore Xu 31.1 75 **Connect and Download**
Theodore Xu 20.1 76
77 (% style="text-align:center" %)
78 [[image:以太网 PC和PLC连接.png]]
79
80 (% style="text-align:center" %)
81 [[image:以太网下载.png]]
82
Theodore Xu 31.1 83 **Cable Wiring**
Theodore Xu 20.1 84
85 (% style="text-align:center" %)
86 [[image:485接线.png]]
87
Theodore Xu 14.1 88 == **S7-200 Smart Ethernet ** ==
Leo Wei 2.1 89
Theodore Xu 32.1 90 **V-BOX setting**
Theodore Xu 16.1 91
Theodore Xu 34.1 92 |**Items**|**Settings**
93 |Protocol|Siemens S7-200 Smart(Ethernet)
94 |Connection|Ethernet
95 |Port No.|102
96 |PLC station No.|2
Theodore Xu 29.1 97
Theodore Xu 16.1 98 (% style="text-align:center" %)
99 [[image:西门子200smart 以太网.png]]
100
Theodore Xu 32.1 101 **PLC setting**
Theodore Xu 14.1 102
103 (% style="text-align:center" %)
104 [[image:西门子软件版本.png]]
105
106 (% style="text-align:center" %)
107 [[image:以太网通讯配置.png]]
108
Theodore Xu 32.1 109 **Connect and Download**
Theodore Xu 14.1 110
111 (% style="text-align:center" %)
Theodore Xu 19.1 112 [[image:以太网 PC和PLC连接.png]]
113
114 (% style="text-align:center" %)
Theodore Xu 14.1 115 [[image:以太网下载.png]]
116
Theodore Xu 32.1 117 **Cable Wiring**
Theodore Xu 15.1 118
119 V-Box : RJ45 Ethernet interface
120
121 PLC : RJ45 Ethernet interface
122
123 (% style="text-align:center" %)
124 [[image:以太网连接.png]]
125
Theodore Xu 41.1 126 == **S7-300 Ethernet ** ==
Leo Wei 2.1 127
128 Supported Series: Siemens S7-300 series PLC
129
Theodore Xu 41.1 130 **V-BOX setting**
Leo Wei 2.1 131
132 |**Items**|**Settings**|**Note**
133 |Protocol|Simens S7-300 Ethernet|
134 |Connection|Ethernet|
135 |Port No.|102|
136 |PLC station No.|2|Need to be same as the PLC setting
137
Theodore Xu 41.1 138 **Address List**
Leo Wei 2.1 139
Theodore Xu 40.1 140 |**Type**|**Device register**|**Format**|**Range**|**Note**
141 |(% rowspan="4" %)Bit|I|I ddddd.o|0.0~~99999.7|
142 |Q|Q ddddd.o|0.0~~99999.7|
143 |M|M ddddd.o|0.0~~99999.7|
144 |DB0.DB~~DB99.DB|DBxDB nndddd.o|0.0~~99999999.7|(((
Leo Wei 2.1 145 nn: block number;
146
147 dddd: address;
148 )))
Theodore Xu 40.1 149 |(% rowspan="8" %)Word|I|IW ddddd|0~~99999|
150 |Q|QW ddddd|0~~99999|
151 |(% rowspan="3" %)M|MB ddddd|0~~99999|
152 |MW ddddd|0~~99999|(((
Leo Wei 2.1 153 MW0=MB(0~~1)
154
155 MW2=MB(2~~3)
156
157 Address value is a multiple of 2
158 )))
Theodore Xu 40.1 159 |MD ddddd|0~~99999|(((
Leo Wei 2.1 160 MD0=MB(0~~3)
161
162 MD4=MB(4~~7)
163
164 Address value is a multiple of 4
165 )))
Theodore Xu 40.1 166 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
Leo Wei 2.1 167 nn: block number;
168
169 dddd: address
170 )))
Theodore Xu 40.1 171 |DBxDBW nndddd|0~~99999999
172 |DBxDBD nndddd|0~~99999999
Leo Wei 2.1 173
Theodore Xu 41.1 174 **Configure the communication protocol**
Leo Wei 2.1 175
Theodore Xu 41.1 176 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_8e00ed9483ddb629.png||alt="image-20220824161345-1.png" height="1011" width="1920"]]
Leo Wei 2.1 177
Theodore Xu 41.1 178 **Cable Wiring**
Leo Wei 2.1 179
Theodore Xu 41.1 180 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ac8ece9a26719fda.png||alt="image-20220824161450-2.png" height="170" width="401"]]
Leo Wei 2.1 181
Theodore Xu 45.1 182 == **S7-1200 Ethernet ** ==
Leo Wei 2.1 183
184 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]]
185
Theodore Xu 45.1 186 **V-BOX Setting**
187
188 |**Items**|**Settings**|**Note**
189 |Protocol|Siemens S7-1200|
190 |Connection|Ethernet|
191 |Port No.|102|
192 |PLC station No.|2|
193
Theodore Xu 46.1 194 (% style="text-align:center" %)
195 [[image:西门子1200协议参数.png]]
196
Theodore Xu 45.1 197 **Address List**
198
199 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
200 |(% rowspan="4" %)Bit|I|I|M d.o|(((
201 d:0~-~-9999
202
203 o:0-7
204 )))|
205 |Q|Q|Q d.o|(((
206 d:0~-~-9999
207
208 o:0-7
209 )))|
210 |M|M|M d.o|(((
211 d:0~-~-9999
212
213 o:0-7
214 )))|
215 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
216 nn:0-9999,
217
218 dddd:0-9999,
219
220 o:0-7
221 )))|(((
222 nn:DB No.
223
224 dddd:address value
225
226 o: digit address
227 )))
228 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
229 |M|MW|MW d|d:0-99999|(((
230 MW0=MB(0~~1)
231
232 MW2=MB(2~~3)
233
234 Address value is a multiple of 2
235 )))
236 |M|MD|MD d|d:0-99999|(((
237 MD0=MB(0~~3)
238
239 MD4=MB(4~~7)
240
241 Address value is a multiple of 4
242 )))
243 |I|IW|IW d|d:0-99999|
244 |Q|QW|QW d|d:0-99999|
245 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
246 nn:0-9999
247
248 dddd:0-9999
249 )))|(((
250 nn:DB No.
251
252 dddd:address value
253 )))
254 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
255 nn:0-9999
256
257 dddd:0-9999
258 )))|(((
259 nn:DB No.
260
261 dddd:address value
262
263 Address value is a multiple of 2
264 )))
265 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
266 nn:0-9999
267
268 dddd:0-9999
269 )))|(((
270 nn:DB No.
271
272 dddd:address value
273
274 Address value is a multiple of 4
275 )))
276
Theodore Xu 46.1 277 {{info}}
278 ✎Note:
Theodore Xu 45.1 279
Theodore Xu 46.1 280 * The S7-1200 supports simultaneous connection of three devices.
281 * V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (S7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
282 * S7-1200 String type, the default first two bytes are used to store the maximum character and valid characters, so the text data will be shifted back one word address. When interacting with the data, what way this address plc is displayed with is unknown. And because of an extra word of data causes us to display the wrong. The solution is if we use String, then the actual data address we want to operate on is actually shifted back two bytes, so as long as the address on the project is shifted back 2 bits to correspond with the actual data address.
283 {{/info}}
Theodore Xu 45.1 284
Theodore Xu 46.1 285 **PLC Settings**
286
287
Joe 51.1 288 In the Project tree [PLC project]→Right-click[PLC-1]→[Properties]→[General]→[PROFINE interface]→[Add new subnet]→[IP address]192.168.40.20,[Subnet mask]255.255.255.0→[OK]
Theodore Xu 46.1 289
290 (% style="text-align:center" %)
Joe 51.1 291 [[image:图片1.png]]
Theodore Xu 46.1 292
Joe 51.1 293 Open [Properties] again→[General]→[Protection&Security]→[Connection mechanisms]→Check [Permit access with PUTIGET communication remote partner ]→[OK]
294
295 (% style="text-align:center" %)
296 [[image:图片2.png]]
297
Joe 52.1 298 Create a new DB block:
Joe 51.1 299
Joe 52.1 300 [Add new block]→[Date block]→[Manual]→[OK]
301
302 (% style="text-align:center" %)
303 [[image:图片3.png]]
304
305 Right-click[DB1]→[Properties]→[General]→[Attributes]→Uncheck[Optimized block access]→[OK]
306
307 (% style="text-align:center" %)
308 [[image:图片4.png]]
309
310
Theodore Xu 46.1 311 Address settings, using BD2 as example.
312
313 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
314 * 2 represent DB block number
315 * xxxx represent address
316
317 **Such as:**
318
319 * DBxDBB20000 = DB2.DBB0
320 * DBxDBW20004 = DB2.DBW4
321
322 (% style="text-align:center" %)
323 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_8ee8d3ac3637bfc4.png]]
324
Joe 49.3 325 **How to setting String in PLC and V-net**
326 PLC configuration
327
328 choosing Data type~-~-String→add"[]" after String and input data length
329
330 (% style="text-align:center" %)
331 [[image:yUYuRVmMcL.png]]
332
333 V-box configuration
334
335 (% style="text-align:center" %)
336 [[image:BSRBeEWL0O.png]]
337
Joe 49.4 338 choosing Word and DBxDBW →input  Register Main No. →Data format is String →input data length you want to use → choosing Byte order~-~-Little-endian
Joe 49.3 339
Joe 49.4 340 (% class="box infomessage" %)
341 (((
342 Note: Register Main No. = offset in PLC + 2
343 For example, the image above has an offset of 4, so the register Main No. is 10006
344 If an offset is 8, the register Main No. is 10010
345 )))
346
Theodore Xu 46.1 347 **How to connect with S7-1200 Firmware V4.0**
348
349 PLC configuration
350
351 * Double click [device configuration] in Siemens via software
352 * Double click [protection] to enter protection configuration screen
353
354 (% style="text-align:center" %)
355 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_664a826cd356c830.png]]
356
357 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
358
359 (% style="text-align:center" %)
360 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_78026942a88f0fdb.png]]
361
362 DB settings
363
364 * Right click [DB], select [properties]
365 * Uncheck [optimized block access]
366
367 **Cable Wiring**
368
369 (% style="text-align:center" %)
370 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ac8ece9a26719fda.png]]
371
Leo Wei 25.2 372 == **S7-XXX Ethernet** ==
Leo Wei 2.1 373
374 Supported Series: Siemens S7-400, S7-1200 and S7-1500
375
Theodore Xu 44.1 376 **V-BOX setting**
Leo Wei 2.1 377
378 |=**Items**|=**Settings**|=**Note**
379 |Protocol|Siemens S7-XXX|
380 |Connection|Ethernet|
381 |Port No.|102|
382 |Device No.|Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|
383 |HMI No.|Rack (Default as 0)|
384
385 Slot from TIA Portal is equal to Device No. of V-net
386
387 Rack from TIA Portal is equal to HMI No. of V-net
388
Theodore Xu 44.1 389 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d78bc267e5fc6394.png||alt="image-20220824162459-3.png" height="503" width="798"]]
Leo Wei 2.1 390
Theodore Xu 44.1 391 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_c9ae84ef5d418580.png||alt="image-20220824163305-2.png" height="1009" width="1920"]]
Leo Wei 2.1 392
Theodore Xu 44.1 393 **Address List**
Leo Wei 2.1 394
Theodore Xu 42.1 395 |**Type**|**Device register**|**Format**|**Range**|**Note**
396 |(% rowspan="4" %)Bit|I|M d.o|(((
Leo Wei 2.1 397 d:0~-~-9999
398
399 o:0-7
400 )))|
Theodore Xu 42.1 401 |Q|Q d.o|(((
Leo Wei 2.1 402 d:0~-~-9999
403
404 o:0-7
405 )))|
Theodore Xu 42.1 406 |M|M d.o|(((
Leo Wei 2.1 407 d:0~-~-9999
408
409 o:0-7
410 )))|
Theodore Xu 42.1 411 |DB0.DB-DB99.DB|DBxDBnndddd.o|(((
Leo Wei 2.1 412 nn:0-9999,
413
414 dddd:0-9999,
415
416 o:0-7
417 )))|(((
418 nn:DB No.
419
420 dddd:address value
421
422 o: digit address
423 )))
Theodore Xu 42.1 424 |(% rowspan="8" %)Word|M|MB d|d:0-99999|
425 |M|MW d|d:0-99999|(((
Leo Wei 2.1 426 MW0=MB(0~~1)
427
428 MW2=MB(2~~3)
429
430 Address value is a multiple of 2
431 )))
Theodore Xu 42.1 432 |M|MD d|d:0-99999|(((
Leo Wei 2.1 433 MD0=MB(0~~3)
434
435 MD4=MB(4~~7)
436
437 Address value is a multiple of 4
438 )))
Theodore Xu 42.1 439 |I|IW d|d:0-99999|
440 |Q|QW d|d:0-99999|
441 |DB0.DB-DB99.DB|DBxDBBnndddd|(((
Leo Wei 2.1 442 nn:0-9999
443
444 dddd:0-9999
445 )))|(((
446 nn:DB No.
447
448 dddd:address value
449 )))
Theodore Xu 42.1 450 |DB0.DB-DB99.DB|DBxDBWnndddd|(((
Leo Wei 2.1 451 nn:0-9999
452
453 dddd:0-9999
454 )))|(((
455 nn:DB No.
456
457 dddd:address value
458
459 Address value is a multiple of 2
460 )))
Theodore Xu 42.1 461 |DB0.DB-DB99.DB|DBxDBDnndddd|(((
Leo Wei 2.1 462 nn:0-9999
463
464 dddd:0-9999
465 )))|(((
466 nn:DB No.
467
468 dddd:address value
469
470 Address value is a multiple of 4
471 )))
472
Theodore Xu 44.1 473 **Configure the communication protocol**
Leo Wei 2.1 474
Theodore Xu 44.1 475 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_9e740a8bf83ea3bf.png||alt="image-20220824163448-3.png" height="557" width="974"]]
Leo Wei 2.1 476
477 **✎Note:**
478
479 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three V-BOX.
480 * V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
481
Theodore Xu 44.1 482 **Cable Wiring**
Leo Wei 2.1 483
Theodore Xu 44.1 484 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ac8ece9a26719fda.png||alt="image-20220824162342-2.png" height="170" width="401"]]
Leo Wei 2.1 485
486 == {{id name="HLOGOEthernet"/}}**LOGO Ethernet ** ==
487
488 Supported Series: Siemens Logo 0BA0, 0BA1 series
489
490 **V-BOX Settings**
491
492 |**Items**|**Settings**|**Note**
493 |Protocol|Siemens LOGO|
494 |Connection|Ethernet|
495 |Port No.|102|
496 |PLC station No.|2|
497
498 **Address List**
499
500 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
501 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
502 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
503 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
504 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
505 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
506 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
507 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
508 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
509 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
510 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
511 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
512 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
513 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
514 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
515 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
516
517 **PLC Settings in LOGO Software:**
518
519 Click [Tools]~-~-[Ethernet Connections],shown as below.
520
Theodore Xu 46.1 521 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d13df637bfedcc52.png||alt="12.PLC Protocol_html_8b9d2322edf89519.png" height="641" width="423"]]
Leo Wei 2.1 522
523 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
Joe 50.2 524
Leo Wei 2.1 525
Joe 48.2 526 (% style="text-align:center" %)
Joe 50.2 527 [[image:1iZSZTpAdk.png]]
Leo Wei 2.1 528
Joe 50.2 529 **TSAP set**: The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite, shown as below.
Leo Wei 2.1 530
Theodore Xu 46.1 531 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_facc6ee1af05162f.png||alt="image-20221228143047-5.png" height="626" width="1088"]]
Leo Wei 2.1 532
533 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
534
Theodore Xu 46.1 535 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d43d2b7b2599ee64.png||alt="image-20221228143246-6.png" height="698" width="688"]]
Leo Wei 2.1 536
537 **V-BOX Communication Settings**
538
539 Set PLC IP in [IP Address] settings;
540
Theodore Xu 47.1 541 (% style="text-align:center" %)
Theodore Xu 48.1 542 [[image:V-NET_Client logo.png]]
Leo Wei 2.1 543
544 TSAP setting
545
546 * The initialization script needs to set the source TSAP address and the target TSAP address, otherwise the communication will not be successful.
547
Joe 48.2 548 You can copy the following script into V-net directly.
549
550 (% class="box successmessage" %)
551 (((
Leo Wei 2.1 552 **function** **init**.main()
553 addr_setword("@W_0#HSW1200",8192) //~-~- Set the source TSAP address//
554 addr_setword("@W_0#HSW1201",4096) //~-~- Set the destination TSAP address//
Theodore Xu 17.1 555 **end**
Joe 48.2 556 )))
Leo Wei 2.1 557
Joe 48.2 558 (% class="box infomessage" %)
559 (((
560 Note:
561 The name of the test script must be “init”, 8192 and 4096 are the data used for the test, there is no HSW address in the register option, but you can directly set the value of the corresponding address through the code.
562 )))
Leo Wei 2.1 563
564 **✎Note:**
565
566 * **Communication port configuration: **
567 ** Continuous length needs to be set to 0.
568 ** Integration interval needs to be set to 1. (no change may result in data errors)
569 ** Set Port and Device Station NO.
570 ** Other set as defaulted.