Wiki source code of Siemens

Version 52.1 by Joe on 2024/06/11 18:47

Show last authors
1 == **S7-200 Smart Serial** ==
2
3 **V-BOX setting**
4
5 (% style="width:1323.87px" %)
6 |**Items**|**Settings**|**Note**
7 |Protocol|(% style="width:783px" %)Siemens S7-200 CPU22x/Smart PPI|
8 |Connection|(% style="width:783px" %)RS485|
9 |Baud rate|(% style="width:783px" %)9600|
10 |Data bit|(% style="width:783px" %)8|
11 |Parity|(% style="width:783px" %)EVEN|
12 |Stop bit|(% style="width:783px" %)1|
13 |PLC station No.|(% style="width:783px" %)2|
14
15 (% style="text-align:center" %)
16 [[image:西门子200串口.png]]
17
18 **Address List **
19
20 |**Type**|**Device register**|**Format**|**Range**|**Note**
21 |(% rowspan="9" %)Bit|I|I ddddd.o|0.0~~99999.7|
22 |Q|Q ddddd.o|0.0~~99999.7|
23 |V|VWbit ddddd.o|0.0~~99999.7|
24 |V|V ddddd.o|0.0~~99999.7|
25 |M|M ddddd.o|0.0~~99999.7|
26 |SM|ddddd.o|0.0~~99999.7|
27 |S|ddddd.o|0.0~~99999.7|Read only
28 |T|ddddd|0~~99999|Timer state, read only
29 |C|ddddd|0~~99999|Counter state, read only
30 |(% rowspan="12" %)Word|I|IW ddddd|0~~99999|
31 |Q|QW ddddd|0~~99999|
32 |AI|AIW ddddd|0~~99999|
33 |AQ|VB ddddd|0~~99999|
34 |V|VW ddddd|0~~99998|(((
35 VW0=VB (0~~1)
36
37 VW2=VB (2~~3)
38
39 Address value is a multiple of 2
40 )))
41 |V|VD ddddd|0~~99998|(((
42 VD0=VB (0~~3)
43
44 VD2=VB (4~~7)
45
46 Address value is a multiple of 4
47 )))
48 |M|MB ddddd|0~~99999|
49 |M|MW ddddd|0~~99999|(((
50 MW0=MB(0~~1)
51
52 MW2=MB(2~~3)
53
54 Address value is a multiple of 2
55 )))
56 |M|MD ddddd|0~~99999|(((
57 MD0=MB(0~~3)
58
59 MD4=MB(4~~7)
60
61 Address value is a multiple of 4
62 )))
63 |T|TW ddddd|0~~99999|Value of timer
64 |C|CW ddddd|0~~99999|Value of counter
65 |W|SW ddddd|0~~99999|
66
67 **PLC setting**
68
69 (% style="text-align:center" %)
70 [[image:西门子软件版本.png]]
71
72 (% style="text-align:center" %)
73 [[image:485通讯配置.png]]
74
75 **Connect and Download**
76
77 (% style="text-align:center" %)
78 [[image:以太网 PC和PLC连接.png]]
79
80 (% style="text-align:center" %)
81 [[image:以太网下载.png]]
82
83 **Cable Wiring**
84
85 (% style="text-align:center" %)
86 [[image:485接线.png]]
87
88 == **S7-200 Smart Ethernet ** ==
89
90 **V-BOX setting**
91
92 |**Items**|**Settings**
93 |Protocol|Siemens S7-200 Smart(Ethernet)
94 |Connection|Ethernet
95 |Port No.|102
96 |PLC station No.|2
97
98 (% style="text-align:center" %)
99 [[image:西门子200smart 以太网.png]]
100
101 **PLC setting**
102
103 (% style="text-align:center" %)
104 [[image:西门子软件版本.png]]
105
106 (% style="text-align:center" %)
107 [[image:以太网通讯配置.png]]
108
109 **Connect and Download**
110
111 (% style="text-align:center" %)
112 [[image:以太网 PC和PLC连接.png]]
113
114 (% style="text-align:center" %)
115 [[image:以太网下载.png]]
116
117 **Cable Wiring**
118
119 V-Box : RJ45 Ethernet interface
120
121 PLC : RJ45 Ethernet interface
122
123 (% style="text-align:center" %)
124 [[image:以太网连接.png]]
125
126 == **S7-300 Ethernet ** ==
127
128 Supported Series: Siemens S7-300 series PLC
129
130 **V-BOX setting**
131
132 |**Items**|**Settings**|**Note**
133 |Protocol|Simens S7-300 Ethernet|
134 |Connection|Ethernet|
135 |Port No.|102|
136 |PLC station No.|2|Need to be same as the PLC setting
137
138 **Address List**
139
140 |**Type**|**Device register**|**Format**|**Range**|**Note**
141 |(% rowspan="4" %)Bit|I|I ddddd.o|0.0~~99999.7|
142 |Q|Q ddddd.o|0.0~~99999.7|
143 |M|M ddddd.o|0.0~~99999.7|
144 |DB0.DB~~DB99.DB|DBxDB nndddd.o|0.0~~99999999.7|(((
145 nn: block number;
146
147 dddd: address;
148 )))
149 |(% rowspan="8" %)Word|I|IW ddddd|0~~99999|
150 |Q|QW ddddd|0~~99999|
151 |(% rowspan="3" %)M|MB ddddd|0~~99999|
152 |MW ddddd|0~~99999|(((
153 MW0=MB(0~~1)
154
155 MW2=MB(2~~3)
156
157 Address value is a multiple of 2
158 )))
159 |MD ddddd|0~~99999|(((
160 MD0=MB(0~~3)
161
162 MD4=MB(4~~7)
163
164 Address value is a multiple of 4
165 )))
166 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
167 nn: block number;
168
169 dddd: address
170 )))
171 |DBxDBW nndddd|0~~99999999
172 |DBxDBD nndddd|0~~99999999
173
174 **Configure the communication protocol**
175
176 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_8e00ed9483ddb629.png||alt="image-20220824161345-1.png" height="1011" width="1920"]]
177
178 **Cable Wiring**
179
180 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ac8ece9a26719fda.png||alt="image-20220824161450-2.png" height="170" width="401"]]
181
182 == **S7-1200 Ethernet ** ==
183
184 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]]
185
186 **V-BOX Setting**
187
188 |**Items**|**Settings**|**Note**
189 |Protocol|Siemens S7-1200|
190 |Connection|Ethernet|
191 |Port No.|102|
192 |PLC station No.|2|
193
194 (% style="text-align:center" %)
195 [[image:西门子1200协议参数.png]]
196
197 **Address List**
198
199 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
200 |(% rowspan="4" %)Bit|I|I|M d.o|(((
201 d:0~-~-9999
202
203 o:0-7
204 )))|
205 |Q|Q|Q d.o|(((
206 d:0~-~-9999
207
208 o:0-7
209 )))|
210 |M|M|M d.o|(((
211 d:0~-~-9999
212
213 o:0-7
214 )))|
215 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
216 nn:0-9999,
217
218 dddd:0-9999,
219
220 o:0-7
221 )))|(((
222 nn:DB No.
223
224 dddd:address value
225
226 o: digit address
227 )))
228 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
229 |M|MW|MW d|d:0-99999|(((
230 MW0=MB(0~~1)
231
232 MW2=MB(2~~3)
233
234 Address value is a multiple of 2
235 )))
236 |M|MD|MD d|d:0-99999|(((
237 MD0=MB(0~~3)
238
239 MD4=MB(4~~7)
240
241 Address value is a multiple of 4
242 )))
243 |I|IW|IW d|d:0-99999|
244 |Q|QW|QW d|d:0-99999|
245 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
246 nn:0-9999
247
248 dddd:0-9999
249 )))|(((
250 nn:DB No.
251
252 dddd:address value
253 )))
254 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
255 nn:0-9999
256
257 dddd:0-9999
258 )))|(((
259 nn:DB No.
260
261 dddd:address value
262
263 Address value is a multiple of 2
264 )))
265 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
266 nn:0-9999
267
268 dddd:0-9999
269 )))|(((
270 nn:DB No.
271
272 dddd:address value
273
274 Address value is a multiple of 4
275 )))
276
277 {{info}}
278 ✎Note:
279
280 * The S7-1200 supports simultaneous connection of three devices.
281 * V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (S7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
282 * S7-1200 String type, the default first two bytes are used to store the maximum character and valid characters, so the text data will be shifted back one word address. When interacting with the data, what way this address plc is displayed with is unknown. And because of an extra word of data causes us to display the wrong. The solution is if we use String, then the actual data address we want to operate on is actually shifted back two bytes, so as long as the address on the project is shifted back 2 bits to correspond with the actual data address.
283 {{/info}}
284
285 **PLC Settings**
286
287
288 In the Project tree [PLC project]→Right-click[PLC-1]→[Properties]→[General]→[PROFINE interface]→[Add new subnet]→[IP address]192.168.40.20,[Subnet mask]255.255.255.0→[OK]
289
290 (% style="text-align:center" %)
291 [[image:图片1.png]]
292
293 Open [Properties] again→[General]→[Protection&Security]→[Connection mechanisms]→Check [Permit access with PUTIGET communication remote partner ]→[OK]
294
295 (% style="text-align:center" %)
296 [[image:图片2.png]]
297
298 Create a new DB block:
299
300 [Add new block]→[Date block]→[Manual]→[OK]
301
302 (% style="text-align:center" %)
303 [[image:图片3.png]]
304
305 Right-click[DB1]→[Properties]→[General]→[Attributes]→Uncheck[Optimized block access]→[OK]
306
307 (% style="text-align:center" %)
308 [[image:图片4.png]]
309
310
311 Address settings, using BD2 as example.
312
313 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
314 * 2 represent DB block number
315 * xxxx represent address
316
317 **Such as:**
318
319 * DBxDBB20000 = DB2.DBB0
320 * DBxDBW20004 = DB2.DBW4
321
322 (% style="text-align:center" %)
323 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_8ee8d3ac3637bfc4.png]]
324
325 **How to setting String in PLC and V-net**
326 PLC configuration
327
328 choosing Data type~-~-String→add"[]" after String and input data length
329
330 (% style="text-align:center" %)
331 [[image:yUYuRVmMcL.png]]
332
333 V-box configuration
334
335 (% style="text-align:center" %)
336 [[image:BSRBeEWL0O.png]]
337
338 choosing Word and DBxDBW →input  Register Main No. →Data format is String →input data length you want to use → choosing Byte order~-~-Little-endian
339
340 (% class="box infomessage" %)
341 (((
342 Note: Register Main No. = offset in PLC + 2
343 For example, the image above has an offset of 4, so the register Main No. is 10006
344 If an offset is 8, the register Main No. is 10010
345 )))
346
347 **How to connect with S7-1200 Firmware V4.0**
348
349 PLC configuration
350
351 * Double click [device configuration] in Siemens via software
352 * Double click [protection] to enter protection configuration screen
353
354 (% style="text-align:center" %)
355 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_664a826cd356c830.png]]
356
357 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
358
359 (% style="text-align:center" %)
360 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_78026942a88f0fdb.png]]
361
362 DB settings
363
364 * Right click [DB], select [properties]
365 * Uncheck [optimized block access]
366
367 **Cable Wiring**
368
369 (% style="text-align:center" %)
370 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ac8ece9a26719fda.png]]
371
372 == **S7-XXX Ethernet** ==
373
374 Supported Series: Siemens S7-400, S7-1200 and S7-1500
375
376 **V-BOX setting**
377
378 |=**Items**|=**Settings**|=**Note**
379 |Protocol|Siemens S7-XXX|
380 |Connection|Ethernet|
381 |Port No.|102|
382 |Device No.|Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|
383 |HMI No.|Rack (Default as 0)|
384
385 Slot from TIA Portal is equal to Device No. of V-net
386
387 Rack from TIA Portal is equal to HMI No. of V-net
388
389 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d78bc267e5fc6394.png||alt="image-20220824162459-3.png" height="503" width="798"]]
390
391 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_c9ae84ef5d418580.png||alt="image-20220824163305-2.png" height="1009" width="1920"]]
392
393 **Address List**
394
395 |**Type**|**Device register**|**Format**|**Range**|**Note**
396 |(% rowspan="4" %)Bit|I|M d.o|(((
397 d:0~-~-9999
398
399 o:0-7
400 )))|
401 |Q|Q d.o|(((
402 d:0~-~-9999
403
404 o:0-7
405 )))|
406 |M|M d.o|(((
407 d:0~-~-9999
408
409 o:0-7
410 )))|
411 |DB0.DB-DB99.DB|DBxDBnndddd.o|(((
412 nn:0-9999,
413
414 dddd:0-9999,
415
416 o:0-7
417 )))|(((
418 nn:DB No.
419
420 dddd:address value
421
422 o: digit address
423 )))
424 |(% rowspan="8" %)Word|M|MB d|d:0-99999|
425 |M|MW d|d:0-99999|(((
426 MW0=MB(0~~1)
427
428 MW2=MB(2~~3)
429
430 Address value is a multiple of 2
431 )))
432 |M|MD d|d:0-99999|(((
433 MD0=MB(0~~3)
434
435 MD4=MB(4~~7)
436
437 Address value is a multiple of 4
438 )))
439 |I|IW d|d:0-99999|
440 |Q|QW d|d:0-99999|
441 |DB0.DB-DB99.DB|DBxDBBnndddd|(((
442 nn:0-9999
443
444 dddd:0-9999
445 )))|(((
446 nn:DB No.
447
448 dddd:address value
449 )))
450 |DB0.DB-DB99.DB|DBxDBWnndddd|(((
451 nn:0-9999
452
453 dddd:0-9999
454 )))|(((
455 nn:DB No.
456
457 dddd:address value
458
459 Address value is a multiple of 2
460 )))
461 |DB0.DB-DB99.DB|DBxDBDnndddd|(((
462 nn:0-9999
463
464 dddd:0-9999
465 )))|(((
466 nn:DB No.
467
468 dddd:address value
469
470 Address value is a multiple of 4
471 )))
472
473 **Configure the communication protocol**
474
475 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_9e740a8bf83ea3bf.png||alt="image-20220824163448-3.png" height="557" width="974"]]
476
477 **✎Note:**
478
479 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three V-BOX.
480 * V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
481
482 **Cable Wiring**
483
484 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ac8ece9a26719fda.png||alt="image-20220824162342-2.png" height="170" width="401"]]
485
486 == {{id name="HLOGOEthernet"/}}**LOGO Ethernet ** ==
487
488 Supported Series: Siemens Logo 0BA0, 0BA1 series
489
490 **V-BOX Settings**
491
492 |**Items**|**Settings**|**Note**
493 |Protocol|Siemens LOGO|
494 |Connection|Ethernet|
495 |Port No.|102|
496 |PLC station No.|2|
497
498 **Address List**
499
500 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
501 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
502 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
503 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
504 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
505 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
506 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
507 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
508 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
509 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
510 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
511 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
512 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
513 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
514 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
515 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
516
517 **PLC Settings in LOGO Software:**
518
519 Click [Tools]~-~-[Ethernet Connections],shown as below.
520
521 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d13df637bfedcc52.png||alt="12.PLC Protocol_html_8b9d2322edf89519.png" height="641" width="423"]]
522
523 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
524
525
526 (% style="text-align:center" %)
527 [[image:1iZSZTpAdk.png]]
528
529 **TSAP set**: The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite, shown as below.
530
531 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_facc6ee1af05162f.png||alt="image-20221228143047-5.png" height="626" width="1088"]]
532
533 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
534
535 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d43d2b7b2599ee64.png||alt="image-20221228143246-6.png" height="698" width="688"]]
536
537 **V-BOX Communication Settings**
538
539 Set PLC IP in [IP Address] settings;
540
541 (% style="text-align:center" %)
542 [[image:V-NET_Client logo.png]]
543
544 TSAP setting
545
546 * The initialization script needs to set the source TSAP address and the target TSAP address, otherwise the communication will not be successful.
547
548 You can copy the following script into V-net directly.
549
550 (% class="box successmessage" %)
551 (((
552 **function** **init**.main()
553 addr_setword("@W_0#HSW1200",8192) //~-~- Set the source TSAP address//
554 addr_setword("@W_0#HSW1201",4096) //~-~- Set the destination TSAP address//
555 **end**
556 )))
557
558 (% class="box infomessage" %)
559 (((
560 Note:
561 The name of the test script must be “init”, 8192 and 4096 are the data used for the test, there is no HSW address in the register option, but you can directly set the value of the corresponding address through the code.
562 )))
563
564 **✎Note:**
565
566 * **Communication port configuration: **
567 ** Continuous length needs to be set to 0.
568 ** Integration interval needs to be set to 1. (no change may result in data errors)
569 ** Set Port and Device Station NO.
570 ** Other set as defaulted.