Ben 52.1 1 = (% style="color:inherit; font-family:inherit" %)**WECON PLC**(%%) =
Leo Wei 1.1 2
Ben 63.1 3 == **LX3V Serial Protocol** ==
Ben 31.1 4
Ben 20.1 5 Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
Leo Wei 1.1 6
Ben 81.1 7 **1)PLC Settings**
Leo Wei 1.1 8
Ben 20.1 9 |**Item**|**Settings**|**Note**
10 |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
11 |Connection|RS422/RS485|
12 |Baud rate|9600|
13 |Data bit|7|
14 |Parity|EVEN|
15 |Stop bit|1|
16 |PLC station No.|1|
Leo Wei 1.1 17
Ben 82.1 18 **2)PLC Address List**
Ben 20.1 19
20 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
21 |(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
22 |Y|Y|Y o|0~~303237|
23 |M|M|M d|0~~99999|
24 |T|T|T d|0~~99999|
25 |C|C|C d|0~~99999|
26 |S|S|S d|0~~99999|
27 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
28 |Y|Y|Y o|0~~303237|
29 |M|M|M d|0~~99999|
30 |T|T|T d|0~~99999|
31 |C|C|C d|0~~199|
32 |D|D|D d|0~~7999|
33 |S|S|S d|0~~99999|
34 |SD|SD|SD d|8000~~9999|
35
Ben 83.1 36 **3)Configure the communication protocol**
Ben 20.1 37
Ben 80.1 38 [[image:image-20220824152217-1.png]]
39
Ben 83.1 40 **4)hardware connection**
Ben 80.1 41
Ben 20.1 42 * **RS422**
43
Ben 69.1 44 [[image:image-20220824120614-5.png]]
Ben 20.1 45
Ben 68.1 46 * **RS485**
47
Ben 69.1 48 [[image:image-20220824120524-3.png]]
Ben 68.1 49
Ben 63.1 50 == **LX5V Serial Protocol** ==
Ben 28.1 51
Ben 84.1 52 This example introduces the establishment of serial port communication between V-BOX and LX5V. It is introduced through three parts: PLC software configuration, V-BOX software configuration, and hardware wiring.
Ben 20.1 53
54 **Software configuration of PLC**
55
56 **1)PLC programming software**
57
Ben 71.1 58 [[image:image-20220824142722-1.png]]
Ben 20.1 59
60 **2)New PLC project**
61
62 Click New Project and select the PLC model.
63
Ben 33.1 64 [[image:image-20220822172623-2.png]]
Ben 20.1 65
66 **3)Set Serial port parameters**
67
68 Follow the steps below to configure Serial port parameters
69
70 Baud rate:115200
71
72 Data bit:8
73
74 Stop bit:1
75
76 Parity:No verification
77
Ben 33.1 78 [[image:image-20220822172657-3.png]]
Ben 20.1 79
80 **4)Registers list**
81
Ben 33.1 82 [[image:image-20220822172730-4.png]]
Ben 20.1 83
Ben 33.1 84 **V-BOX software configuration**
Ben 28.1 85
Ben 35.1 86 **1)V-BOX programming software**
Ben 20.1 87
Ben 35.1 88 [[image:image-20220824104124-1.png]]
Ben 20.1 89
Ben 35.1 90 **2)V-NET add device**
Ben 20.1 91
Ben 35.1 92 Open V-NET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the access key, password and remark, to add the device.
Ben 20.1 93
Ben 35.1 94 [[image:image-20220824104909-2.png]]
Ben 20.1 95
96 **3)Set communication port parameters**
97
98 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
99
100 Baud rate:115200
101
102 Data bit:8
103
104 Stop bit:1
105
106 Parity:No verification
107
Ben 70.1 108 [[image:image-20220824142130-1.png]]
Ben 20.1 109
110 **hardware connection**
111
112 **1)Hardware wiring diagram**
113
Ben 70.1 114 [[image:image-20220824142546-2.png]]
Ben 28.1 115
Ben 70.1 116 [[image:image-20220824142643-3.png]]
Ben 28.1 117
Ben 74.1 118 The above are all the steps for establishing serial port communication between V-BOX with LX5V PLC.
Ben 20.1 119
Ben 63.1 120 == **LX5V-N Ethernet protocol** ==
Ben 20.1 121
Ben 77.1 122 This example introduces the establishment of Ethernet communication between V-BOX and LX5V-N. It is introduced through three parts: PLC software configuration, V-BOX software configuration, and hardware wiring.
Ben 20.1 123
124 **Software configuration of PLC**
125
126 **1)PLC programming software**
127
Ben 72.1 128 [[image:image-20220824142722-1.png]]
Ben 20.1 129
130 **2)New PLC project**
131
132 Click New Project and select the PLC model.
133
Ben 73.1 134 [[image:image-20220824143613-1.png]]
Ben 20.1 135
136 **3)Set Ethernet port parameters**
137
138 Follow the steps below to configure Ethernet parameters
139
140 PLC IP address:192.168.39.200
141
142 default gateway:192.168.39.1
143
144 subnet mask:255.255.255.0
145
Ben 73.1 146 [[image:image-20220824143744-2.png]]
Ben 20.1 147
148 **4)Registers list**
149
Ben 74.1 150 [[image:image-20220822172730-4.png]]
Ben 20.1 151
Ben 74.1 152 (% id="cke_bm_22473S" style="display:none" %)** **(%%)**V-BOX software configuration**
Ben 20.1 153
Ben 74.1 154 **1)V-BOX programming software**
Ben 20.1 155
Ben 74.1 156 [[image:image-20220824104124-1.png]]
Ben 20.1 157
Ben 74.1 158 **2)V-NET add device**
Ben 20.1 159
Ben 74.1 160 Open V-NET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the access key, password and remark, to add the device.
Ben 20.1 161
Ben 74.1 162 [[image:image-20220824104909-2.png]]
Ben 20.1 163
Ben 79.1 164 **3)Set communication Protocol**
Ben 20.1 165
Ben 74.1 166 Click Communication to configure the LX5V plc protocol and IP address.
Ben 20.1 167
Ben 74.1 168 [[image:image-20220824144619-1.png]]
Ben 20.1 169
170 **hardware connection**
171
172 **1)Hardware wiring diagram**
173
Ben 74.1 174 [[image:image-20220824151127-2.png]]
Ben 20.1 175
Ben 74.1 176 The above are all the steps for establishing ethernet communication between V-BOX with LX5V PLC.
Ben 20.1 177
Ben 23.1 178 = **Rockwell PLC** =
Ben 22.1 179
Ben 63.1 180 == (% id="cke_bm_5621S" style="display:none" %)** **(%%)**MicroLogix Protocol** ==
Ben 37.1 181
182 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
183
Ben 87.1 184 **1)PLC Settings**
Ben 37.1 185
186 |**Item**|**Settings**|**Note**
Ben 85.1 187 |Protocol|Allen-Bradlley DF1 Advanced|
Ben 37.1 188 |Connection|RS232|
189 |Baud rate|19200|
190 |Data bit|8|
191 |Parity|None|
192 |Stop bit|1|
193 |PLC station No.|1|
194
Ben 87.1 195 **2)Address List**
Ben 37.1 196
197 |**Type**|**Device registers**|**Format**|**Range**|**Note**
198 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
199 |O|O d.d|0.0~~255.15|
200 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
201 |S|S d.d|0.0~~255.15|
202 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
203 |(% rowspan="9" %)Word|S|S d|0~~255|
204 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
205 |TP|TP nnhh|0~~ffff
206 |CS|CS nnhh|0~~ffff
207 |CP|CP nnhh|0~~ffff
208 |N|N nnhh|0~~ffff
209 |C|C nnhh|0~~ffff
210 |T|T nnhh|0~~ffff
211 |R|R nnhh|0~~ffff
212
Ben 86.1 213 **3)Configure the communication protocol**[[image:image-20220824152928-1.png]]
Ben 85.1 214
Ben 87.1 215 **4)Configure the communication protocol**
Ben 37.1 216
217 [[image:image-20220824110724-1.png]]
218
Ben 112.1 219 == **Micro850_FreeTag** ==
Ben 37.1 220
Ben 11.1 221 (((
Ben 16.1 222 (((
Ben 38.1 223 This example introduces the establishment of Ethernet communication between Wecon V-box and CompactLogix L1769. It is introduced through three parts: PLC software configuration, V-box software configuration, and hardware wiring.
Ben 16.1 224 )))
Ben 11.1 225 )))
226
227 (((
Ben 15.1 228 (% class="wikigeneratedid" id="HSoftwareconfigurationofPLC" %)
229 (((
230 **Software configuration of PLC**
Ben 11.1 231 )))
232
Ben 15.1 233 (% class="wikigeneratedid" id="HPLCprogrammingsoftware" %)
Ben 11.1 234 (((
Ben 15.1 235 **1)PLC programming software**
236 )))
Ben 11.1 237
Ben 17.1 238 [[image:image-20220714162600-1.png]]
Ben 11.1 239
Ben 15.1 240 (% class="wikigeneratedid" id="HNewPLCproject" %)
Ben 11.1 241 (((
Ben 15.1 242 **2)New PLC project**
Ben 11.1 243 )))
244
245 (((
Ben 16.1 246 (((
Ben 15.1 247 Click New Project and select the PLC model.
Ben 11.1 248 )))
Ben 16.1 249 )))
Ben 11.1 250
251 (((
Ben 17.1 252 [[image:image-20220714162617-2.png]]
Ben 11.1 253 )))
254
255 (((
Ben 17.1 256
Ben 16.1 257
Ben 17.1 258 [[image:image-20220714162652-4.png]]
Ben 11.1 259 )))
260
261 (((
Ben 15.1 262 (% class="wikigeneratedid" id="HSetEthernetparameters" %)
263 (((
264 **3)Set Ethernet parameters**
265 )))
Ben 11.1 266
267 (((
Ben 15.1 268 (((
Ben 16.1 269 (((
Ben 11.1 270 Follow the steps below to configure Ethernet parameters
271 )))
Ben 15.1 272 )))
Ben 16.1 273 )))
Ben 11.1 274
275 (((
Ben 15.1 276 (((
Ben 16.1 277 (((
Ben 11.1 278 PLC IP address:192.168.40.101
279 )))
Ben 15.1 280 )))
Ben 16.1 281 )))
Ben 11.1 282
283 (((
Ben 15.1 284 (((
Ben 16.1 285 (((
Ben 11.1 286 default gateway:192.168.40.1
287 )))
Ben 15.1 288 )))
Ben 16.1 289 )))
Ben 11.1 290
291 (((
Ben 15.1 292 (((
Ben 16.1 293 (((
Ben 11.1 294 subnet mask:255.255.255.0
295 )))
Ben 15.1 296 )))
Ben 16.1 297 )))
Ben 11.1 298
299 (((
Ben 17.1 300 [[image:image-20220714162713-5.png]]
Ben 11.1 301 )))
302
303 (((
304
305 )))
306
307 (((
Ben 15.1 308 (% class="wikigeneratedid" id="HV-boxsoftwareconfiguration" %)
309 (((
310 **V-box software configuration**
311 )))
Ben 11.1 312
Ben 15.1 313 (% class="wikigeneratedid" id="HV-boxprogrammingsoftware" %)
314 (((
315 **1)V-box programming software**
316 )))
Ben 11.1 317
Ben 15.1 318 (% class="wikigeneratedid" %)
319 (((
Ben 17.1 320 [[image:image-20220714162725-6.png]]
Ben 15.1 321 )))
Ben 11.1 322
Ben 15.1 323 (% class="wikigeneratedid" id="HConfiguredevicenetwork" %)
324 (((
325 **2)Configure device network**
326 )))
Ben 11.1 327
328 (((
Ben 15.1 329 (((
Ben 16.1 330 (((
Ben 11.1 331 Click the Configuration Download button[[image:image-20220714115308-8.png||height="22" width="15"]], It is used to configure the device network, update the device time, obtain the device machine code, check the device network, etc.
332 )))
Ben 16.1 333
334 (((
335 In the example below, the IP address of V-Box is configured as 192.168.40.66, and the networking method is 4G connection
Ben 15.1 336 )))
Ben 16.1 337 )))
338 )))
Ben 11.1 339
340 (((
Ben 15.1 341 (((
Ben 17.1 342 [[image:image-20220714162737-7.png]]
Ben 16.1 343
344
Ben 11.1 345 )))
346 )))
347 )))
348 )))
349
Ben 15.1 350 (% class="wikigeneratedid" id="HV-netadddevice" %)
Ben 11.1 351 (((
Ben 15.1 352 **3)V-net add device**
Ben 11.1 353 )))
Ben 15.1 354 )))
Ben 11.1 355
356 (((
Ben 16.1 357 (((
Ben 21.1 358 Open VNET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the device machine code/product code, device password, and device alias to add the device.   [[image:image-20220714162752-8.png]]
Ben 11.1 359 )))
360
361
362 )))
363
364 (((
Ben 15.1 365 (% class="wikigeneratedid" id="HSetcommunicationportparameters" %)
366 (((
367 **4)Set communication port parameters**
368 )))
Ben 11.1 369
Ben 16.1 370 (((
371 In the device list on the left, find the Vbox that communicates with the L1769, click it and select configuration,communication port configuration in the main interface to add a communication protocol.
Ben 11.1 372 )))
373
Ben 17.1 374 [[image:image-20220714162805-9.png]]
Ben 16.1 375 )))
376
377 (((
Ben 11.1 378 The communication port is selected as Ethernet, the device type is selected as Allen-Bradley, the protocol is Allen-BradleyMicro850_FreeTag EthemetIP, and the IP is the internal IP address of the L1769 PLC. The port number is 44818.
Ben 16.1 379 )))
Ben 11.1 380
Ben 97.1 381 [[image:image-20220824164346-1.png]]
Ben 11.1 382
383
Ben 16.1 384 (((
Ben 22.1 385 After adding the protocol Allen-BradleyMicro850_FreeTag, click[[image:image-20220714143838-2.png]]icon add label.[[image:image-20220714162827-11.png]]
Ben 16.1 386 )))
Ben 14.1 387
Ben 16.1 388 (% class="wikigeneratedid" id="HEngineeringproduction" %)
389 (((
390 **5)Engineering production**
391 )))
Ben 14.1 392
Ben 16.1 393 (% class="wikigeneratedid" %)
394 (((
395 (((
396 According to your own needs, use the V-NET client software to edit the required data monitoring points.
397 )))
Ben 14.1 398
Ben 17.1 399 [[image:image-20220714162841-12.png]]
Ben 14.1 400
Ben 16.1 401
402 (((
403 **hardware connection**
404 )))
405 )))
406
407 (((
408 **1)Hardware wiring diagram**
409 )))
410
411 (((
412 (((
413 This example introduces Wecon V-box with Allen-Bradley L1769 PLC to establish communication through Ethernet. The connection diagram is as follows:
414 )))
415
Ben 17.1 416 [[image:image-20220714162856-13.png]]
Ben 16.1 417
418 (((
Ben 41.1 419 The above are all the steps for establishing Ethernet communication between Wecon V-box with CompactLogix L1769 PLC.
Ben 26.1 420
421
422 == **Allen-Bradley Ethernet DF1** ==
423
424 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Allen-Bradley%20Ethernet%20DF1.zip]]
425
426
427 = **Siemens PLC** =
Ben 61.1 428
Ben 63.1 429 == **S7-200 Smart Ethernet Protocol** ==
Ben 61.1 430
431 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20S7-200%20Smart.zip]]
Ben 88.1 432
433
Ben 99.1 434 == **S7-300 Ethernet Protocol** ==
Ben 88.1 435
436 Supported Series: Siemens S7-300 series PLC
437
Ben 90.1 438 **1)PLC Setting**
Ben 88.1 439
440 |**Items**|**Settings**|**Note**
441 |Protocol|Simens S7-300 Ethernet|
442 |Connection|Ethernet|
443 |Port No.|102|
444 |PLC station No.|2|Need to be same as the PLC setting
445
Ben 90.1 446 **2)Address List**
Ben 88.1 447
448 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
449 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
450 |Q|Q|Q ddddd.o|0.0~~99999.7|
451 |M|M|M ddddd.o|0.0~~99999.7|
452 |DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
453 nn: block number;
454
455 dddd: address;
Ben 16.1 456 )))
Ben 88.1 457 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
458 |Q|QW|QW ddddd|0~~99999|
459 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
460 |MW|MW ddddd|0~~99999|(((
461 MW0=MB(0~~1)
462
463 MW2=MB(2~~3)
464
465 Address value is a multiple of 2
Ben 16.1 466 )))
Ben 88.1 467 |MD|MD ddddd|0~~99999|(((
468 MD0=MB(0~~3)
Ben 16.1 469
Ben 88.1 470 MD4=MB(4~~7)
471
472 Address value is a multiple of 4
473 )))
474 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
475 nn: block number;
476
477 dddd: address
478 )))
479 |DBxDBW|DBxDBW nndddd|0~~99999999
480 |DBxDBD|DBxDBD nndddd|0~~99999999
481
Ben 90.1 482 **3)Configure the communication protocol**
Ben 88.1 483
Ben 90.1 484 [[image:image-20220824161345-1.png]]
Ben 88.1 485
Ben 96.1 486 **4)Cable Wiring**
Ben 88.1 487
Ben 90.1 488 [[image:image-20220824161450-2.png]]
Ben 88.1 489 )))
490 )))
491
Ben 63.1 492 == **S7-1200 Ethernet Protocol** ==
Leo Wei 1.1 493
494 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]]
495
Ben 93.1 496 == **S7-XXX Ethernet Protocol** ==
Ben 91.1 497
498 Supported Series: Siemens S7-400, S7-1200 and S7-1500
499
Ben 95.1 500 **1)PLC Setting**
Ben 91.1 501
502 |=**Items**|=**Settings**|=**Note**
503 |Protocol|Siemens S7-XXX|
504 |Connection|Ethernet|
505 |Port No.|102|
506 |Device No.|Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|
507 |HMI No.|Rack (Default as 0)|
508
Ben 94.1 509 Slot from TIA Portal is equal to Device No. of V-net
Ben 91.1 510
Ben 94.1 511 Rack from TIA Portal is equal to HMI No. of V-net
Ben 91.1 512
Ben 92.1 513 [[image:image-20220824162459-3.png]]
Ben 91.1 514
Ben 94.1 515 [[image:image-20220824163305-2.png]]
516
Ben 95.1 517 **2)Address List**
Ben 91.1 518
519 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
520 |(% rowspan="4" %)Bit|I|I|M d.o|(((
521 d:0~-~-9999
522
523 o:0-7
524 )))|
525 |Q|Q|Q d.o|(((
526 d:0~-~-9999
527
528 o:0-7
529 )))|
530 |M|M|M d.o|(((
531 d:0~-~-9999
532
533 o:0-7
534 )))|
535 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
536 nn:0-9999,
537
538 dddd:0-9999,
539
540 o:0-7
541 )))|(((
542 nn:DB No.
543
544 dddd:address value
545
546 o: digit address
547 )))
548 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
549 |M|MW|MW d|d:0-99999|(((
550 MW0=MB(0~~1)
551
552 MW2=MB(2~~3)
553
554 Address value is a multiple of 2
555 )))
556 |M|MD|MD d|d:0-99999|(((
557 MD0=MB(0~~3)
558
559 MD4=MB(4~~7)
560
561 Address value is a multiple of 4
562 )))
563 |I|IW|IW d|d:0-99999|
564 |Q|QW|QW d|d:0-99999|
565 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
566 nn:0-9999
567
568 dddd:0-9999
569 )))|(((
570 nn:DB No.
571
572 dddd:address value
573 )))
574 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
575 nn:0-9999
576
577 dddd:0-9999
578 )))|(((
579 nn:DB No.
580
581 dddd:address value
582
583 Address value is a multiple of 2
584 )))
585 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
586 nn:0-9999
587
588 dddd:0-9999
589 )))|(((
590 nn:DB No.
591
592 dddd:address value
593
594 Address value is a multiple of 4
595 )))
596
Ben 95.1 597 **3)Configure the communication protocol**
Ben 91.1 598
Ben 94.1 599 [[image:image-20220824163448-3.png]]
Ben 91.1 600
601 **✎Note:**
602
Ben 94.1 603 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three V-BOX.
604 * V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
Ben 91.1 605
Ben 95.1 606 **4)Cable Wiring**
Ben 91.1 607
Ben 92.1 608 [[image:image-20220824162342-2.png]]
Ben 91.1 609
Ben 98.1 610
Ben 56.1 611 = **Mitsubishi PLC** =
612
Ben 104.1 613 == **FX1S,1N,2N Serial Protocol** ==
Ben 103.1 614
Ben 105.1 615 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
Ben 103.1 616
Ben 105.1 617 **1)V-BOX Settings**
Ben 103.1 618
Ben 105.1 619 |**Item**|**Settings**|**Note**
620 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
621 |Connection|RS422/RS485/RS232|
622 |Baud rate|9600~~115200|
623 |Data bit|7/8|
624 |Parity|EVEN/Odd/None|
625 |Stop bit|1/2|
626 |PLC station No.|1~~255|
Ben 104.1 627
Ben 105.1 628 **2)Address List**
Ben 104.1 629
Ben 105.1 630 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
631 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
632 |Y|Y|Y o|0~~303237|
633 |M|M|M d|0~~99999|
634 |T|T|T d|0~~99999|
635 |C|C|C d|0~~99999|
Ben 104.1 636 |S|S|S d|0~~99999|
Ben 105.1 637 |SM|SM|SM d|8000~~9999|
638 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
639 |Y|Y|Y o|0~~303237|
640 |M|M|M d|0~~99999|
641 |T|T|T d|0~~99999|
642 |C|C|C d|0~~199|
643 |D|D|D d|0~~7999|
Ben 104.1 644 |S|S|S d|0~~99999|
Ben 105.1 645 |SD|SD|SD d|8000~~9999|
Ben 104.1 646
Ben 106.1 647 **3)Configure the communication protocol**
Ben 104.1 648
Ben 107.1 649 [[image:image-20220825102844-3.png]]
Ben 106.1 650
651 **4)Cable Wiring**
652
Ben 104.1 653 * **RS422**
654
Ben 107.1 655 [[image:image-20220825103350-4.png]]
Ben 104.1 656
657 [[image:image-20220825100845-4.png]]
658
659
Ben 106.1 660 == **FX3U,3G,3GA Serial Protocol** ==
Ben 56.1 661
Ben 106.1 662 Supported Series: Mitsubishi FX3U, FX3G, FX3GA series
Ben 56.1 663
Ben 106.1 664 **1)V-BOX Settings**
665
666 |**Item**|**Settings**|**Note**
667 |Protocol|Mitsubishi FX3U/3G/3GA|
668 |Connection|RS422/RS485/RS232|
669 |Baud rate|9600~~115200|
670 |Data bit|7/8|
671 |Parity|EVEN/Odd/None|
672 |Stop bit|1/2|
673 |PLC station No.|1~~255|
674
675 **2)Address List**
676
677 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
678 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
679 |Y|Y|Y o|0~~303237|
680 |M|M|M d|0~~99999|
681 |T|T|T d|0~~99999|
682 |C|C|C d|0~~99999|
683 |S|S|S d|0~~99999|
684 |SM|SM|SM d|8000~~9999|
685 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
686 |Y|Y|Y o|0~~303237|
687 |M|M|M d|0~~99999|
688 |T|T|T d|0~~99999|
689 |C|C|C d|0~~199|
690 |D|D|D d|0~~7999|
691 |S|S|S d|0~~99999|
692 |SD|SD|SD d|8000~~9999|
693
694 **3)Configure the communication protocol**
695
Ben 107.1 696 [[image:image-20220825102649-2.png]]
Ben 106.1 697
698 **4)Cable Wiring**
699
700 * **RS422**
701
Ben 107.1 702 [[image:image-20220825103421-5.png]]
Ben 106.1 703
704 [[image:image-20220825100845-4.png]]
705
706
Ben 103.1 707 == **FX5U Serial Protocol** ==
708
Ben 107.1 709 Mitsubishi FX5U series PLC
Ben 103.1 710
Ben 108.1 711 **1)V-BOX Settings**
Ben 107.1 712
713 |**Item**|**Settings**|**Note**
714 |Protocol|Mitsubishi FX5U|
715 |Connection|RS422/RS485|
716 |Baud rate|9600|
717 |Data bit|7|
718 |Parity|Odd|
719 |Stop bit|1|
720 |PLC station No.|1~~255|Need to be the same as PLC settings
721
Ben 108.1 722 **2)Address List**
Ben 107.1 723
724 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
725 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
726 |Y|Y|Y o|0~~303237|
727 |M|M|M d|0~~99999|
728 |B|B|B h|0~~7FFF|
729 |F|F|F d|0~~32767|
730 |SB|SB|SB h|0~~7FFF|
731 |TS|TS|TS d|0~~1023|
732 |TC|TC|TC d|0~~1023|
733 |STS|STS|STS d|0~~1023|
734 |STC|STC|STS d|0~~1023|
735 |CS|CS|CS d|0~~1023|
736 |CC|CC|CC d|0~~1023|
737 |SM|SM|SM d|0~~9999|
738 |L|L|L d|0~~32767|
739 |S|S|S d|0~~4095|
740 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
741 |TN|TN|TN d|0~~1023|
742 |STN|STN|STN d|0~~1023|
743 |CN|CN|CN d|0~~1023|
744 |R|R|R d|0~~32767|
745 |SW|SW|SW h|0~~7FFF|
746 |Z|Z|Z d|0~~23|
747 |D|D|D d|0~~7999|
748 |SD|SD|SD d|0~~11999|
749
Ben 108.1 750 **3)PLC Settings (GX Works 3)**
Ben 107.1 751
752 Create a blank FX5U project
753
754 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
755
756 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5c9cb13fac1e6c93.png?width=200&height=462&rev=1.1||alt="12.PLC Protocol_html_5c9cb13fac1e6c93.png" height="462" width="200"]]
757
758 Select protocol in the setting item, and set parameters.
759
760 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_de942589ca070228.png?width=600&height=324&rev=1.1||alt="12.PLC Protocol_html_de942589ca070228.png" height="324" width="600"]]
761
762 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
763
764 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_387ec7d00b5feb59.png?width=600&height=323&rev=1.1||alt="12.PLC Protocol_html_387ec7d00b5feb59.png" height="323" width="600"]]
765
766 Click the [Apply] button to finish the setting.
767
768 Click download and select the items as below, then click [execute] to download the configuration to PLC.
769
770 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_cdef1c5ec8cc2105.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_cdef1c5ec8cc2105.png" height="434" width="600"]]
771
772 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
773
774 Done.
775
Ben 108.1 776 **4)Configure the communication protocol**
Ben 107.1 777
Ben 108.1 778 [[image:image-20220825104904-1.png]]
Ben 107.1 779
Ben 108.1 780 **5)Cable Wiring**
Ben 107.1 781
782
783 * **RS422**
784
Ben 108.1 785 [[image:image-20220825105105-2.png]]
Ben 107.1 786
Ben 108.1 787 [[image:image-20220825105533-3.png]]
Ben 107.1 788
Ben 100.1 789 == **FX5U Ethernet Protocol** ==
790
791 Mitsubishi FX5U series PLC
792
Ben 110.1 793 **1)V-BOX Settings**
Ben 100.1 794
795 |**Items**|**Settings**|**Note**
796 |Protocol|Mitsubishi FX5U|
797 |Connection|Ethernet|
798 |Port No.|5002|Must be the same as the PLC setting
799 |PLC station No.|0|
800
Ben 110.1 801 **2)Address List**
Ben 100.1 802
803 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
804 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
805 |Y|Y|Y o|0~~303237|
806 |M|M|M d|0~~99999|
807 |B|B|B h|0~~7FFF|
808 |F|F|F d|0~~32767|
809 |SB|SB|SB h|0~~7FFF|
810 |TS|TS|TS d|0~~1023|
811 |TC|TC|TC d|0~~1023|
812 |STS|STS|STS d|0~~1023|
813 |STC|STC|STS d|0~~1023|
814 |CS|CS|CS d|0~~1023|
815 |CC|CC|CC d|0~~1023|
816 |SM|SM|SM d|0~~9999|
817 |L|L|L d|0~~32767|
818 |S|S|S d|0~~4095|
819 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
820 |TN|TN|TN d|0~~1023|
821 |STN|STN|STN d|0~~1023|
822 |CN|CN|CN d|0~~1023|
823 |R|R|R d|0~~32767|
824 |SW|SW|SW h|0~~7FFF|
825 |Z|Z|Z d|0~~23|
826 |D|D|D d|0~~7999|
827 |SD|SD|SD d|0~~11999|
828
Ben 110.1 829 **3)PLC Settings (GX Works 3)**
Ben 100.1 830
831 Find the [Ethernet port] in the navigation area.
832
Ben 109.1 833 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8e8f85ace087346c.png?width=300&height=593&rev=1.1||alt="12.PLC Protocol_html_8e8f85ace087346c.png" height="593" width="300"]]
Ben 100.1 834
835 Select [Own Node Settings] in the [Setting Item List];
836
837 Set [IP Address], [Subnet Mask], [Default Gateway];
838
839 Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows;
840
Ben 109.1 841 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5d98495052c8c10e.png?width=600&height=339&rev=1.1||alt="12.PLC Protocol_html_5d98495052c8c10e.png" height="339" width="600"]]
Ben 100.1 842
843 Select [SLMP Connection Module] and add into host station as below picture shows;
844
845 Set Port number as 5002 (this is necessary settings);
846
847 Click [Close with Reflecting the Setting] to save and close window;
848
Ben 109.1 849 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_14b489fdc6c6589d.png?width=600&height=350&rev=1.1||alt="12.PLC Protocol_html_14b489fdc6c6589d.png" height="350" width="600"]]
Ben 100.1 850
851 Click [Apply] to completed Etherenet settings;
852
853 Switch to the [On line data operation] interface as below, check the item and click [Execute] to download.
854
Ben 109.1 855 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_c93025a968a8a9e7.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_c93025a968a8a9e7.png" height="434" width="600"]]
Ben 100.1 856
Ben 110.1 857 **4)Configure the communication protocol**
858
Ben 111.1 859 [[image:image-20220825112403-1.png]]
Ben 110.1 860
861 **5)Cable Wiring**
862
Ben 109.1 863 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
Ben 100.1 864
Ben 26.1 865 = **Delta PLC** =
866
Ben 64.1 867 == **DVP Ethernet Protocol** ==
Leo Wei 1.1 868
869 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Delta%20DVP%20Ethernet.zip]]
870
Ben 63.1 871 == **DVP Serial Protocol** ==
Leo Wei 1.1 872
873 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Delta%20DVP%20Ethernet.zip]]
874
Ben 48.1 875 = **Omron PLC** =
876
Ben 65.1 877 == **CP1 Series Protocol** ==
Jim 7.1 878
Jim 8.1 879 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CP1%20Series.zip]]
Jim 7.1 880
Ben 65.1 881 == **CJ2M Series Protocol** ==
Jim 7.1 882
Jim 8.1 883 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CJ2M.zip]]
Jim 7.1 884
Ben 50.1 885 = **Modbus RTU** =
886
Ben 53.1 887 == **V-BOX as master** ==
Ben 50.1 888
889 Select the protocol “(% class="mark" %)Modbus RTU Slave(All Fuction)”,
890
891 (% class="mark" %)then set BaudRate,Port,Stop Bit,Data Bit,Parity
892
893 (% style="text-align:center" %)
894 [[image:1624342015914-382.png||height="486" width="800" class="img-thumbnail"]]
895
Ben 53.1 896 == **V-BOX as slave** ==
Ben 50.1 897
898 Select the protocol “(% class="mark" %)**Modbus RTU Master”**,
899
900 (% class="mark" %)then set BaudRate,Port,Stop Bit,Data Bit,Parity
901
902 (% style="text-align:center" %)
903 [[image:1624348709622-711.png||queryString="width=809&height=493" height="488" width="800" class="img-thumbnail"]]
904
905 **Address List**
906
907 (% class="table-bordered" %)
908 |**Type**|**Register**|**Function code & Description**
909 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
910 |06 (write single register: write a binary value to a holding register)
911 |10 (write values to multiple addresses )
912 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
913 |06 (write single register: write a binary value to a holding register)
914 |10 (write values to multiple addresses )
915 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
916 |06 (write single register: write a binary value to a holding register)
917 |10 (write values to multiple addresses )
918 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
919 |10 (write values to multiple addresses )
920 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
921 |05 (Force a single coil to force the on/off state of a logic coil)
922 |0F (Write multiple bits, ie write continuously)
923 |(% rowspan="3" %)1|02 (Read the input state)
924 |05 (Force a single coil to force the on/off state of a logic coil)
925 |0F (Write multiple bits)
926 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
927 |05 (Force a single coil to force the on/off state of a logic coil)
928 |0F (Write multiple bits)
929 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
930 |0F (Write multiple bits)
931
Ben 55.1 932 == **communicate with VB inverter** ==
Ben 52.1 933
934 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20VB%20inverter.zip]]
935
Ben 51.1 936 = **User define protocol** =
Leo Wei 1.1 937
Stone Wu 19.1 938 More serial port script instruction,please refer manual:[[Lua script function>>doc:V-BOX.V-Net.Manual.04 Lua Script.01 Lua Functions.WebHome]]~-~-->[[3.Serial port operation>>url:http://docs.we-con.com.cn/wiki/vbox/view/HMI/04.Lua%20script%20%20function%20and%20operation/01.Lua%20script%20function/#H3.Serialportoperation]]
Leo Wei 1.1 939
Stone Wu 10.1 940 == **Read the temperature sensor.** ==
Leo Wei 1.1 941
942 the commond format is as beliow:
943
944 Send commond:01 03 02 00 00 03 04 73
945
946 Feedback commond:01 03 06 07 F7 0E 7E B7 35
947
948 Temperature data:07 F7,desimal = 2039,it means temperature is 20.39℃.
949
950 Humidity data:0E 7E,desimal = 3710, it mean humidity is 37.10%RH.
951
952 Script Demo:
953
954 ~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~--
955
956 function com.main()
957 ~-~-dosomething
958 openPlc()
959 end
960 function openPlc()
961 if obj then
962 ~-~- If the serial port opened,then read/write data by timing
963
964 local wri = string.pack(">HHHH",0X0103,0X0200,0X0003,0X0473)
965 local arr = reading(wri)
966 ~-~- if arr ~~=nil then
967 ~-~- if arr[1] ==33 and arr[2] ==v[2][2] and arr[3] ==v[2][3] then
968 ~-~- local A = arr[4]*256
969 ~-~- local B = A+arr[5]
970 ~-~- addr_setword(v[1],B)
971 ~-~- end
972 ~-~- end
973
974 else
975 ~-~-judge if there is a serial object, then initialize and open the serial port
976 local configs = {
977 name = 'COM1', ~-~-Select serial port COM1
978 mode = 485, ~-~-Communication mode RS485
979 baud_rate = 9600, ~-~-Baud rate 9600
980 stop_bit = 1, ~-~-stop bit 1
981 data_len = 8, ~-~-data length 8
982 check_bit = 'NONE', ~-~-no parity
983
984 }
985 obj,err = serial.open(configs) ~-~-Open serial port
986 if not obj then
987 print("serial open :failed", err) ~-~- Open serial port failed
988 end
989 end
990 end
991
992 function reading(wri)
993 obj:flush() ~-~- Clear serial port
994 obj:write(wri) ~-~- Write serial port
995 print(string.byte(wri,1,#wri))
996 obj:flush() ~-~- Clear serial port 
997 local readed =obj:read(9,1000) ~-~- Read 9 bytes, timeout 1 second
998 if readed and readed ~~= "" then 
999 ~-~- judge that a non-empty string is read
1000 print(string.byte(readed,1,#readed))
1001 a={string.byte(readed, 1, #readed)}
1002 if nil ~~= a[4] and nil ~~= a[5] and nil ~~= a[6] and nil ~~= a[7] then
1003 a1=a[4]*256+a[5]
1004 a2=a[6]*256+a[7]
1005 addr_setword("@HDW0",a1)
1006 addr_setword("@HDW1",a2)
1007 end
1008 return {string.byte(readed, 1, #readed)}
1009 elseif readed == nil then
1010 print("serial read err:", err or "")
1011 return nil
1012 end
1013 return nil
1014 end
1015
1016 ~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-