... ... @@ -156,3 +156,101 @@
156 156  
157 157  (% style="text-align:center" %)
158 158  [[image:VB 大功率 NPN 改.png||height="399" width="1082"]]
159 +
160 +=== **3.Wiring instructions for common control methods** ===
161 +
162 +(1)Two-wire type 1 mode controls forward and reverse rotation
163 +
164 +|**Correlation parameter**|**Name**|**Set value**|**Function description**
165 +|F5.16|(((
166 +Terminal
167 +
168 +command mode
169 +)))|0|Two-wire type 1
170 +|F5.00|(((
171 +DI1 Terminal
172 +
173 +Function Selected
174 +)))|1|Forward running( FWD)
175 +|F5.01|(((
176 +DI2 Terminal
177 +
178 +Function Selected
179 +)))|2|Reverses run( REV)
180 +
181 +**Two-wire mode 1**: This mode is the most commonly used two-wire mode. For example, the DI1 terminal is assigned the forward running function, and the DI2 terminal is assigned the reverse running function. Connect the forward running switch to DI1 terminal and the reverse running switch to DI2 terminal.
182 +
183 +(% style="text-align:center" %)
184 +[[image:Two-wire mode 2图片.png||height="310" width="407"]]
185 +
186 +Refer to the following table for running commands corresponding to switching signals:
187 +
188 +|**K1**|**K2**|**Run command**
189 +|0|0|STOP
190 +|1|1|STOP
191 +|1|0|Forward running
192 +|0|1|Reverses running
193 +
194 +(2)Two-wire type 2 mode controls forward and reverse rotation
195 +
196 +|**Correlation parameter**|**Name**|**Set value**|**Function description**
197 +|F5.16|(((
198 +Terminal
199 +
200 +command mode
201 +)))|1|Two-wire type 2
202 +|F5.00|DI1 Terminal Function    Selected|1|Run command
203 +|F5.01|DI2 Terminal Function    Selected|2|Forward and reverse direction
204 +
205 +Two-wire mode 2:In this mode,the DI1 terminal assigns the command function, and the DI2 terminal assigns the forward and reverse direction function.
206 +
207 +
208 +(% style="text-align:center" %)
209 +[[image:Two-wire mode 2图片.png||height="326" width="428"]]
210 +
211 +Refer to the following table for running commands corresponding to switching signals:
212 +
213 +|**K1**|**K2**|**Run command**
214 +|0|0|STOP
215 +|0|1|STOP
216 +|1|0|Forward running
217 +|1|1|Reverses running
218 +
219 +(3)Three-wire type 1 mode controls forward and reverse rotation
220 +
221 +|**Correlation parameter**|**Name**|**Set value**|**Function description**
222 +|F5.16|(((
223 +Terminal
224 +
225 +command mode
226 +)))|2|Three-wire type 1
227 +|F5.00|DI1 Terminal Function    Selected|1|Forward running( FWD)
228 +|F5.01|DI2 Terminal Function    Selected|2|Reverses run( REV)
229 +|F5.02|DI3 Terminal Function    Selected|3|Three-wire operation control
230 +
231 +Three-wire control mode 1: In this mode,the DI3 terminal allocates the three-wire operation control function, the DI1 terminal allocates the forward operation function, and the DI2 terminal allocates the reverse operation function. This control mode requires the frequency converter to use an external button as the start-stop switch of the frequency converter. Connect the start-stop button to DI3 terminal, the forward running button to DI1 terminal, and the reverse running button to DI2 terminal.
232 +
233 +
234 +(% style="text-align:center" %)
235 +[[image:Three-wire control mode 1.png||height="328" width="431"]]
236 +
237 +**Among them: **SB1 forward button; SB2 reverse button; SB3 Stop button;
238 +
239 +(4)Three-wire type 2 mode controls forward and reverse rotation
240 +
241 +|**Correlation parameter**|**Name**|**Set value**|**Function description**
242 +|F5.16|(((
243 +Terminal
244 +
245 +command mode
246 +)))|3|Three-wire type 2
247 +|F5.00|DI1 Terminal Function    Selected|1|Run command
248 +|F5.01|DI2 Terminal Function    Selected|2|Forward and reverse direction
249 +|F5.02|DI3 Terminal Function    Selected|3|Three-wire operation control
250 +
251 +Three-wire control mode 2: For example, the DI3 terminal allocates the three-wire running control function, the DI1 terminal allocates the command function, and the DI2 terminal allocates the forward/reverse running direction function. Connect the start-stop button to DI3 terminal, and enable the operation to connect to DI1 terminal; Connect the forward/reverse operation button to the DI2 terminal.
252 +
253 +(% style="text-align:center" %)
254 +[[image:Three-wire control mode 2.png||height="332" width="436"]]
255 +
256 +**Among them: **SB1 Stop button;SB2 Reverse and reverse control buttons SB3 Run button;
Three-wire control mode 1.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.AiXia
Size
... ... @@ -1,0 +1,1 @@
1 +39.7 KB
Content
Three-wire control mode 2.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.AiXia
Size
... ... @@ -1,0 +1,1 @@
1 +44.1 KB
Content
Two-wire mode 2图片.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.AiXia
Size
... ... @@ -1,0 +1,1 @@
1 +37.0 KB
Content