6 Modbus and PNP/NPN conversion

Version 1.1 by Theodore Xu on 2023/11/27 17:12

1.Communication specifications

ItemContent
Communication protocolModbus protocol
Standard specificationsModbus-RTU slave station communication protocol
Maximum connections247
Topological structureBus type
Slave station functionNumber of messages that can be received and requested at the same time1

2. Hardware configurationfile:///C:\Users\Administrator\AppData\Local\Temp\ksohtml8080\wps1.png

Terminal identificationTerminal nameFunction descriptionJumper/dialing position
J5485 communication terminal resistance setting jumperMatch terminal resistance

modbus 跳线帽.png

Modbus communication port of this product is located on the control panel, as shown in the following figure:

modbus 电路.png

RS485 Connection Topology

RS485 bus connection topology is shown in the following figure. 485 bus is recommended to use shielded twisted pair (STP), 485+, 485-: Adopt twisted pair to connect; Only 120 Ω terminal matching resistors are connected at both ends of the bus to prevent signal reflection; All node 485 signal grounds are connected together; Connect 128 nodes at most, and the distance between branches of each node should be less than 3m.

Multi-node connection mode

When the number of nodes is large, 485 bus must be daisy chain connection. If branch connection is needed, the branch length from bus to node had better be short. It is recommended that it should not exceed 3m. Star connection should be forbidden. The diagram of common bus structure is as follows:

Daisy chain connection

分支链接.png

星型链接.png