6 Modbus and PNP/NPN conversion

Version 19.1 by Theodore Xu on 2023/11/28 11:26

1.Modbus

Communication specifications

ItemContent
Communication protocolModbus protocol
Standard specificationsModbus-RTU slave station communication protocol
Maximum connections247
Topological structureBus type
Slave station functionNumber of messages that can be received and requested at the same time1

Hardware configuration

Terminal identificationTerminal nameFunction descriptionJumper/dialing position
J5485 communication terminal resistance setting jumperMatch terminal resistance

modbus 跳线帽.png

Modbus communication port of this product is located on the control panel, as shown in the following figure:

modbus 电路.png

RS485 Connection Topology

RS485 bus connection topology is shown in the following figure. 485 bus is recommended to use shielded twisted pair (STP), 485+, 485-: Adopt twisted pair to connect; Only 120 Ω terminal matching resistors are connected at both ends of the bus to prevent signal reflection; All node 485 signal grounds are connected together; Connect 128 nodes at most, and the distance between branches of each node should be less than 3m.

Multi-node connection mode

When the number of nodes is large, 485 bus must be daisy chain connection. If branch connection is needed, the branch length from bus to node had better be short. It is recommended that it should not exceed 3m. Star connection should be forbidden. The diagram of common bus structure is as follows:

Figure1 Daisy chain connection

Daisy chain connection

Figure2 Branch connection

分支链接.png

Figure3  Star connection (Forbidden) 

星型链接.png

Transmission distance

The maximum number of nodes and transmission distance supported by our standard RS485 circuit at different rates are shown in the following table.

Transmission distance (m)Rate (kbps)Number of nodesWire diameter
100115.2128AWG26
100019.2128AWG26

2.PNP/NPN

VM series

✎Note:VM series manufactured after April 2023 can support this feature!!

NPN/PNP switching has been added to the VM series machines, enabling fast switching between the two modes.

原理图.png

The NPN/PNP mode can be switched manually at the illustration to realize the compatibility of external signals. Where the upper two pins are shorted for NPN, the lower two pins are shorted for PNP mode. 

Product model

0.75~2.2(KW)

VM小功率.png

4~7.5(KW)

VM大功率.png

VM PNP mode

VM pnp 改.png

VM NPN mode

✎Note:VM NPN external DC does not suppot.

VM PNP 内部改.png

VB series

The control signals of VB series products are compatible with both NPN and PNP signal types.

Scheme

FunctionAddress definitionData meaning
Adapted power

220V:0.75-2.2kW

380V:0.75-7.5kW

380V:11-400kW
NPN signalDefault CompatibleDefault Compatible
PNP signalAdd expansion board

Changing OP terminal

Add an expansion card for PNP signal compatibility for small control board.

Introduce of expansion module

(1)Name:PNP signal compatible expansion board

(2)Picture:

PNP 模块.png

(3)Application Principle:VB 0.75kW-7.5kW PNP mode

VB 小功率 PNP.png

VB 0.75kW-7.5kW NPN mode

✎Note:VB 0.75kW-11kW NPN external DC does not suppot.

VB 小功率NPN 改.png

VB 11kW-400kW PNP mode

VB 大功率 PNP 改1.1.png

VB 11kW-400kW NPN mode

VB 大功率 NPN 改.png