How to Calibrate AI Analog?

Last modified by Minh Phat Tran Viet on 2024/12/27 12:45

Operating steps

  1. Check F7.11 and enter the value to FF.00
  2. Set FF.11 = 111 then modify AC.00, AC.01, AC.04, AC.05 for 0, modify AC.02, AC.03, AC.06, AC.07 for 10.000 .
  3. Calibrate AI1: AI1 does not access the voltage, check D0.09 display voltage, put the display value you see into AC.01, then provide 10V voltage, put the display value you see into AC.03.
  4. Calibrate AI2: AI2 does not access the voltage, check D0.10 display voltage, put the display value you see into AC.05, then provide 10V voltage, put the display value you see into AC.07.