08 Function parameter details

Last modified by Theodore Xu on 2024/03/27 09:41

F0 group basic parameters

F0.00Motor control modeDefault0
Setting Range0Sensorless vector control(SVC)
1V/F Control

0: Sensorless vector control(SVC)

Refers to the open loop vector. It is suitable for general high-performance control occasions, one AC drive can only drive one motor. Such as machine tools, centrifuges, wire drawing machines, injection molding machines and other loads.

1: V/F Control

It is suitable for occasions where the load requirements are not high or one AC drive drives multiple motors, such as fans and pumps.

✎Note: The motor parameter identification process must be carried out when selecting the SVC mode. Only accurate motor parameters can give full play to the advantages of it.

F0.01Command source selectionDefault0
Setting Range0Keypad control
1Terminal control
2Communication control

Select the source of AC drive control command.

AC drive commands include: start, stop, forward, reverse, jog, etc.

0: Keypad control(“LOCAL/REMOT”LED off);

Command control is performed by the RUN and STOP/RESET keys on the Keypad.

1: Terminal control(“LOCAL/REMOT”LED on);

Command control is carried out by multi-function input terminals FWD, REV, FJOG, RJOG, etc.

2: Communication control(“LOCAL/REMOT”Led blinking)

Command control is given by the upper machine through communication.

F0.02UP/DOWN standardDefault0
Setting Range0Running frequency
1Set frequency

This function is only valid for the digital setting of the frequency source. It is used to determine whether the set frequency is the current operating frequency or the current target frequency in UP/DOWN. .

F0.03Setting main frequency source XDefault1
Setting Range0Digital setting (non-retentive at power failure)
1Digital setting (retentive at power failure)
2AI1
3AI2
4Reserved
5PULSE setting DI6(Reserved)
6Multi-stage speed setting
7Simple PLC
8PID
9Communication setting

Select the main source of the AC drive’s input frequency. There are 10 main frequency sources:

0: Digital setting (non-retentive at power failure)

The initial value is 0. The frequency can be increased or decreased by the pulse knob, and the set frequency value of the inverter can be changed by the ▲/▼ keys of the keyboard (or UP and DOWN of the multi-function input terminals).

Non-retentive means that after the AC drive is powered off, the set frequency value will be restored to 0; it will be cleared after switching as the frequency source, so this parameter should not be the object of frequency source switching.

1: Digital setting (retentive at power failure)

The initial value is the value of F0.08 "Keypad setting frequency".

The set frequency value of the inverter can be changed by the ▲/▼ keys of the keyboard (or UP and DOWN of the multi-function input terminals).

Retentive means that when the AC drive is powered on again after power failure, the set frequency is the value before the last power failure (note that it is used in conjunction with F0.23).

2: AI1

3: AI2

Means that the frequency is determined by the analog input terminal. The standard unit provides 2 analog input terminals (AI1, AI2), among which AI1 is 0V~10V voltage input, AI2 can be 0V~10V voltage input, or 4mA~20mA current input, Selected by jumper J8 on the control board.

5: PULSE setting(Reserved)

The set frequency is given by the terminal pulse.

Pulse given signal specifications: voltage range 9V~30V, frequency range 0kHz~20kHz.

6: Multi-stage speed

Select multi-stage speed operation mode. Need to set the F5 group "input terminals" and FD group "multi-stage speed and PLC" parameters to determine the corresponding relationship between the given signal and the given frequency.

7: Simple PLC

Select simple PLC mode. When the frequency source is simple PLC, you need to set the FD group "multi-speed and PLC" parameters to determine the set frequency.

8: PID

Select process PID control. At this time, you need to set the F9 group "PID function of process control ". The running frequency of the inverter is the frequency value after PID action. For the meaning of PID given source, given amount, feedback source, etc., please refer to the introduction of "PID Function of process control" in F9 group.

9: Communication setting

Means that the main frequency source is given by the upper machine through communication.

F0.04Setting auxiliary frequency source YDefault0
Setting Range0Digital setting (non-retentive at power failure)
1Digital setting (retentive at power failure)
2AI1
3AI2
4Reserved
5Reserved
6Multi-stage speed setting
7Simple PLC
8PID
9Communication setting

When the auxiliary frequency source is used as an independent frequency given channel (that is, the frequency source is selected to switch from X to Y), its usage is the same as that of the main frequency source X.

When the auxiliary frequency source is used as a superimposed reference (that is, the frequency source is selected as X+Y, X to X+Y switching or Y to X+Y switching), there are the following special features:

1. When the auxiliary frequency source is digital setting or pulse knob setting, the preset frequency (F0.08) does not work. You can use the ▲/▼ keys of the keyboard (or UP, DOWN of the multi-function input terminal) to adjust up and down based on the given frequency.

2. When the auxiliary frequency source is analog input setting (AI1, AI2) or pulse input setting, 100% of the input setting corresponds to the auxiliary frequency source range (see the description of F0.05 and F0.06). If you need to adjust up and down on the basis of the main set frequency, please set the corresponding setting range of the analog input to .n%~+n%.

3. When the frequency source is pulse input setting, it is similar to analog input setting.

Tip: The selection of auxiliary frequency source Y and the main frequency source X cannot be the same, that is, the main and auxiliary frequency sources cannot use the same frequency given channel.

F0.05Range of auxiliary frequency source YDefault0
Setting Range0Relative to the maximum frequency
1Relative to the frequency source X
F0.06Percentage range of auxiliary frequency source YDefault0
Setting Range0%~150%

When the frequency source is selected as the frequency superposition setting (F0.07 is set to 1, 3 or 4), it is used to determine the adjustment range of the auxiliary frequency source. F0.05 is used to determine the relative object of the range. If it is relative to the maximum frequency (F0.10), its range is a fixed value; if it is relative to the main frequency source X, its range will follow the change of main frequency source X.

F0.07Frequency reference selectionDefault0
Setting RangeOne’s digitSelection of frequency source
0main frequency source X
1main and auxiliary calculation results(The calculation relationship is determined by the ten’s digits)
2Switchover between X and Y
3Switchover between X and main (X) & auxiliary(Y) calculation
4Switchover between Y and main (X) & auxiliary(Y) calculation
Ten’s digitX and Y calculation relationship
0X+Y
1X-Y
2MAX(X, Y)
3MIN(X, Y)
4X* Y

Use this parameter to select the frequency given channel. The frequency setting is realized by the combination of the main frequency source X and the auxiliary frequency source Y.

One’s digit: Selection of frequency source

0: Main frequency source X

The main frequency X is used as the target frequency.

1: Main and auxiliary calculation results

The main and auxiliary calculation result is used as the target frequency (The calculation relationship is determined by the ten’s digits).

2: Switchover between X and Y

When the multi-function input terminal 18: frequency source switching is invalid, the main frequency source X is taken as the target frequency.

When the multi-function input terminal 18: frequency source switching is valid, the auxiliary frequency source Y is taken as the target frequency.

3: Switchover between X and main (X) & auxiliary(Y) calculation

When the multi-function input terminal 18: frequency source switching is invalid, the main frequency source X is taken as the target frequency.

When the multi-function input terminal 18: frequency source switching is valid, the main and auxiliary calculation result is taken as the target frequency.

4: Switchover between Y and main (X) & auxiliary(Y) calculation

When the multi-function input terminal 18: Frequency source switching is invalid, the auxiliary frequency source Y is taken as the target frequency.

When the multi-function input terminal 18: Frequency source switching is valid, the main and auxiliary calculation result is taken as the target frequency.

Ten’s digit:X and Y calculation relationship:

0: X+Y

The sum of the main frequency source X and the auxiliary frequency source Y serves as the target frequency. Realize frequency superposition given function.

1: X-Y

The difference between the main frequency source X and the auxiliary frequency source Y serves as the target frequency.

2: MAX(X, Y)

Take the main frequency source X and auxiliary frequency source Y with the largest absolute value as the target frequency.

3: MIN(X, Y)

Take the main frequency source X and the auxiliary frequency source Y with the smallest absolute value as the target frequency.

4: X * Y

The result of multiplying the main frequency source X by the auxiliary frequency source Y is used as the target frequency.

F0.08Keypad setting frequencyDefault50.00Hz
Setting Range0.00~Maximum frequency F0.10 (valid for digital setting for frequency source selection)

When the frequency source is selected as "digital setting" or "terminal UP/DOWN", the function code value is the initial value of the frequency digital setting of the inverter.

F0.09Running direction selectionDefault0
Setting Range0Forward direction
1Reverse direction

By changing this parameter, the rotation direction of the motor can be changed without changing any other parameters. Its function is equivalent to realizing the conversion of the rotation direction of the motor by adjusting any two cables of the motor (U, V, W).

Tip: After the parameters are initialized, the motor running direction will return to the original state. Use it with caution when it is forbidden to change the rotation of the motor after the system is debugged.

F0.10Maximum FrequencyDefault50.00 Hz
Setting Range50.00Hz~500.00Hz
F0.11Source of frequency upper limitDefault0
Setting Range0Set by F0.12
1AI1
2AI2
3Reserved
4Reserved
5Communication setting

Define the source of the upper limit frequency. The upper limit frequency can come from the digital setting (F0.12) or the analog input channel. When using the analog input to set the upper limit frequency, 100% of the analog input setting corresponds to F0.12.

For example, in torque control, speed control is invalid. In order to avoid "overspeeding" due to material disconnection, the upper limit frequency can be set by analog. When the inverter runs to the upper limit frequency value, the torque control is invalid and the inverter continues to run at the upper limit frequency.

F0.12Frequency upper limitDefault50.00Hz
Setting RangeFrequency lower limit (F0.14)~F0.10
F0.13Upper limit frequency offsetDefault0.00Hz
Setting Range0.00Hz ~F0.10

When the upper limit frequency is given by the analog input, this parameter is used as the offset of the upper limit frequency calculation, and this upper limit frequency offset is added to the set value of the analog upper limit frequency as the final upper limit frequency setting value.

F0.14Frequency lower limitDefault0.00Hz
Setting Range0.00Hz~F0.12

When the inverter starts to run, it starts from the starting frequency. If the given frequency is less than the lower limit frequency during operation, the inverter will run at the lower limit frequency, stop or run at zero speed. You can set which operating mode to use through F0.15.

F0.15The function of frequency lower limitDefault0
Setting Range0Running at frequency lower limit
1Stop
2Standby(Running at 0 Hz)

Select the running state of the AC drive when the set frequency is lower than the lower limit frequency. In order to prevent the motor from running at low speed for a long time, this function can be used to choose to stop.

Carrier frequency

 F0.16Carrier FrequencyDefaultModel Dependent
Setting Range0.5kHz~16.0kHz

This function adjusts the carrier frequency of the AC drive. By adjusting the carrier frequency, the motor noise can be reduced, the resonance point of the mechanical system can be avoided, the leakage current of the line to the ground and the interference caused by the inverter can be reduced.

When the carrier frequency is low, the higher harmonic components of the output current increase, the motor loss increases, and the motor temperature rise increases.

When the carrier frequency is high, the motor loss will decrease and the motor temperature rise will decrease, but the AC drive loss will increase, the AC drive temperature rise will increase, and the interference will increase.

The effect of adjusting the carrier frequency on the following performance:

Carrier FrequencyLow  → High
Motor NoiseMuch → Little
Output Current WaveformBad  → Good
Motor Temperature RiseHigh  →  Low
AC Drive Temperature RiseLow  → High
Leakage CurrentLow  → High
External Radiation InterferenceLow  → High
 F0.17PWM Output Method SelectionDefault0
Setting Range

0:5/7-stage automatic switching

1:7-stage

Method selection of PWM Output Method

F0.18Acceleration Time 1DefaultModel Dependent
Setting Range0.0s~6500.0s
F0.19Deceleration Time 1DefaultModel Dependent
Setting Range0.0s~6500.0s

The acceleration time refers to the time required to accelerate from zero frequency to the acceleration/deceleration base frequency (determined by F0.24), see t1 in Figure 6-1-1.

The deceleration time refers to the time required to decelerate from the acceleration/deceleration base frequency (determined by F0.24) to zero frequency, see t2 in Figure 6-1-1.

CHAPTER 7 FUNCTIONAL PARAMETER DETAILS_html_a0c9063bc45a4ec4.png

Figure 6-1-1 Schematic diagram of acceleration and deceleration time

Pay attention to the difference between actual acceleration and deceleration time and set acceleration and deceleration time.

There are 4 groups of acceleration and deceleration time options

Group 1: F0.18. F0.19;

Group 2: F8.03. F8.04;

Group 3: F8.05. F8.06;

Group 4: F8.07. F8.08.

The acceleration and deceleration time can be selected through the multi-function digital input terminals (F5.00~F5.05).

F0.20Default setting restoringDefault0
Setting Range0No operation
1Restore to factory default setting (not including motor parameters )
2clear fault record 

After changing this parameter to 1 or 2, all parameters will be initialized, and then this parameter will be reset to 0 automatically.

1: Restoring default settings,not including the F2 group parameters and error records.

2: Cleaning error records.

Cleaning error records. accumulative running time(F7.09). accumulative power-on time(F7.13). accumulative power consumption(F7.14).

F0.21Function code modification attributeDefault0
Setting range0Modifiable
1Non-modifiable

Function code modification attribute,After locking, it can prevent the parameter value from being changed by mistake

0:All parameters can be changed

1:All parameters can only be viewed,but not changed,except F0.21

F0.22Digital setting frequency shutdown memory selectionDefault1
Setting range0Non-retentive
1Retentive

This function is only valid when frequency source is digital setting

0: Non-retentive, Refers to the digital set frequency value restored to the set value of F0.08 after the AC drive stops.

1: Retentive, Refers to the digital set frequency value restored to the set frequency after the AC drive stops.

F0.23Acceleration & deceleration time unitDefault1
Setting range01s
10.1s
20.01s

This function is used to determine all acceleration and deceleration time units. Note that when the value is modified, the actual acceleration/deceleration time will also change accordingly (the position of the decimal point changes, and the actual display digits remain unchanged), so it is necessary to readjust the size of various acceleration/deceleration settings according to the situation. Pay attention to the following function codes: F0.18, F0.19, F8.01, F8.02, F8.03, F8.04, F8.05, F8.06, F8.07, F8.08.

F0.24Base Frequency of Acceleration & Deceleration TimeDefault0
Setting range0Maximum frequency(F0.10)
1Set Frequency
2100Hz

Define the frequency range corresponding to the acceleration and deceleration time. See Figure 6.1 Acceleration and deceleration time diagram

F0.25Cooling Fan Running OptionDefault0
Setting range0Automatic running
1Keep running when power on

This function is used to set the operating mode of the cooling fan. This setting can be adjusted according to changes in operating conditions to achieve a balance between maintaining continuous maximum heat dissipation and extending fan life.

0: Automatic running.When the motor is running, the fan runs; when the motor stops, the fan stops running after a delay of 30 seconds. When the temperature of the AC drive module exceeds 50 degrees, the fan also starts to run.

1: Keep running .The fan will keep running after AC drive is powered on

F0.26Frequency Command Decimal PointDefault2
Setting range1One Decimal Place
2Two Decimal Place

The decimal place of the control frequency related instruction, the default is 2 decimal places. After the parameter is set, the decimal place of the parameter associated with the frequency is automatically adjusted. This parameter is not affected by F0.20.

F1 group start & stop control

F1.00Starting modeDefault0
Setting range0Start directly(When the starting DC braking time is not 0, the DC braking will be performed first)
1Speed tracing and start
2Pre-excitation start(When the pre-excitation time is not 0, first pre-excitation and then start)

0: Start directly

if F1.06 startup DC braking/pre-excitation time, when it is set to 0, start from the startup frequency. When the setting is not 0, implement DC braking first and then start, which can solve the problem of reverse rotation when starting with small inertia load.

1: Speed tracing and start

The AC drive first detects the rotation and speed of the motor, and then starts according to the real-time speed. It is suitable for restarting after instantaneous power failure with large inertial loads or for smooth restarting of rotating equipment. Set accurate F2 group motor parameters to obtain better speed tracking and restart performance.

2: Pre-excitation start(Asynchronous motor)

Pre-excitation current and time share function codes with DC braking current and time.

If F1.06 startup DC braking/pre-excitation time, when it is set to 0, start from the starting frequency. When the setting is not 0, the pre-excitation is performed first and then the start is performed to improve the dynamic response speed.

F1.01Speed tracking modeDefault0
Setting Range0Start with the frequency of input power failure
1Start at zero speed
2Start at the maximum frequency F0.10
3Excitation search

Provide 4 speed tracking methods:

0: Tracking down from the frequency during a power outage, this method is usually used.

1: Start tracking upwards from 0 frequency, use in the case of a longer power outage and restart

2: Track down from the maximum frequency, generally used for generating loads

3: Output the excitation current to estimate the current frequency of the motor. After the estimation is successful, the inverter will start at the estimated frequency

F1.02Speed tracking coefficientDefault20
Setting Range1~100

In speed tracking restart mode, set the speed of speed tracking. The larger the parameter setting, the faster the tracking speed. But too large may cause unreliable tracking.

F1.03Starting frequencyDefault0.00Hz
Setting Range0.00Hz~10.00Hz
F1.04Hold time of starting frequencyDefault0.0s
Setting Range0.0s~100.0s

To ensure the torque at startup, please set an appropriate startup frequency. In addition, in order to wait for the magnetic flux to be established when the motor starts, the starting frequency is maintained for a certain period of time and then the acceleration starts. The starting frequency value F1.03 is not limited by the lower limit frequency. If the given frequency (frequency source) is less than the starting frequency, the inverter cannot be started and is in the standby state. When switching between forward and reverse, the start frequency holding time has no effect. The hold time is not included in the acceleration time, but is included in the running time of the simple PLC.

F1.05DC braking current at start-up/Pre-excitation currentDefault0%
Setting Range0%~100%
F1.06DC braking time at start-up/Pre-excitation timeDefault0.0s
Setting Range0.0s~100.0s

Starting DC braking is generally used to completely stop the motor before starting. Pre-excitation is generally used to establish a magnetic field before starting the motor to improve response speed.

If the start mode is direct start, the AC drive will first perform DC braking according to the set start DC braking current when starting, and then start running after the set start DC braking time. If the DC braking time is set to 0, it will start directly without DC braking. The greater the DC braking current, the greater the braking force. If the start mode is asynchronous motor pre-excitation start, the AC drive will first establish the magnetic field according to the set start pre-excitation current when starting, and then start running after the set start pre-excitation time. If the pre-excitation time is set to 0, it will start directly without pre-excitation. Start DC braking/pre-excitation current refers to the percentage relative to the AC drive rated current.

F1.07Acceleration & deceleration methodDefault0
Setting Range0Linear acceleration/deceleration
1S-curve acceleration/deceleration A
2S-curve acceleration/deceleration B

Select the frequency change mode of the AC drive during the start and stop process.

0:Linear acceleration/deceleration

The output frequency increases or decreases linearly. The acceleration/deceleration time changes according to the set acceleration/deceleration time. VB series AC drive provides 4 kinds of acceleration and deceleration time. The acceleration and deceleration time can be selected through the multi-function digital input terminals (F5.00~F5.05).

1: S-curve acceleration/deceleration A

The output frequency increases or decreases according to the S curve. S curve is generally used in places where the start and stop process is relatively gentle, such as elevators and conveyor belts. Function codes F1.08 and F1.09 respectively define the time proportions of the start and end segments of S curve acceleration and deceleration

2: S-curve acceleration/deceleration B

In this acceleration and deceleration curve, the rated motor frequency fb is always the inflection point of the S curve. As shown in Figure 6-3. Generally used in the high-speed area above the rated frequency, where short-term acceleration and deceleration are required.

When the set frequency is above the rated frequency, the acceleration and deceleration time is:

CHAPTER 7 FUNCTIONAL PARAMETER DETAILS_html_840ad38ebbb1d9bd.gif

Among them, f is the set frequency; fb is the rated frequency of the motor;

T is the time to accelerate from 0 frequency to rated frequency fb.

F1.08Time proportion of S-curve start segmentDefault30.0%
Setting Range0.0%~70.0%
F1.09Time proportion of S-curve end segmentDefault30.0%
Setting Range0.0%~70.0%

The function codes F1.08 and F1.09 respectively define the time proportions of the start section and the end section of S-curve acceleration/deceleration A, and both meet: F1.08 + F1.09 ≤ 100.0%.

In Figure 6.2-1, t1 is the parameter defined by parameter F1.08. During this period of time, the slope of the output frequency change gradually increases. t2 is the time defined by parameter F1.09, during which the slope of the output frequency change gradually changes to 0. During the time between t1 and t2, the slope of the output frequency change is fixed.

图片1.png

Figure 6-2-1 S Schematic diagram of curve acceleration and deceleration A

图片2.png

Figure 6-2-2 S Schematic diagram of curve acceleration and deceleration B

F1.10Stop modeDefault0
Setting Range0Decelerate to stop 
1Free stopping

0: Decelerate to stop 

After the stop command is valid, the AC drive will reduce the output frequency according to the deceleration mode and the defined acceleration/deceleration time, and stop after the frequency drops to 0.

1: Free stopping

After the stop command is valid, the AC drive immediately terminates the output. The load stops freely according to mechanical inertia.

F1.11Trigging frequency of DC braking at stopDefault0.00Hz
Setting Range0.00Hz~max.frequency 
F1.12Waiting time of DC braking at stopDefault0.0s
Setting Range0.0s~36.0s
F1.13The current of DC braking at stopDefault0%
Setting Range0%~100%
F1.14The time of DC braking at stopDefault0.0s
Setting Range0.0s~36.0s

Trigging frequency of DC braking at stop: During deceleration to stop, when the output frequency is less than this frequency, the DC braking process at stop will start.

Waiting time of DC braking at stop: When the output frequency is reduced to the start frequency of F1.11 stop DC braking during stop, the AC drive will stop output and start timing. After the delay time set by F1.12, DC will start again brake. It is used to prevent over-current faults caused by DC braking when the speed is high.

The current of DC braking at stop: refers to the added DC braking amount. The larger the value, the stronger the DC braking effect.

The time of DC braking at stop: the time added by the DC braking amount. When this value is 0, it means that there is no DC braking process and the AC drive will stop according to the set deceleration stop process.

CHAPTER 7 FUNCTIONAL PARAMETER DETAILS_html_fcb1f31274fca2cb.png

Figure 6-2-3 Schematic diagram of DC braking at stop

F1.15Brake use rateDefault100%
Setting Range0%~100%

It is valid for inverters with built-in braking unit. The braking effect of the dynamic braking function can be adjusted.

F1.16Zero frequency output selectionDefault1
Setting Range0Open
1Closed

Setting whether the AC drive has output when running frequency is 0

F2 group motor parameters

F2.00Motor type selectionDefault0
Setting Range0Ordinary asynchronous motor
1Variable frequency asynchronous motor
2Permanent magnet synchronous motor
3Single-phase asynchronous motor
F2.01Motor rated powerDefaultModel Dependent
Setting Range0.1kW~400.0kW
F2.02Motor rated VoltageDefaultModel Dependent
Setting Range0V~440V
F2.03Motor rated currentDefaultModel Dependent
Setting Range

0.01A~655.35A(AC drive<=55kW)

0.1A~6553.5A(AC drive >55kW)

F2.04Motor rated frequencyDefaultModel Dependent
Setting Range0.00Hz~Maximum frequency F0.10
F2.05Motor rated speedDefaultModel Dependent
Setting Range0rpm~36000rpm
 Caution

1. Please set according to the nameplate parameters of the motor.

2. The excellent control performance of vector control requires accurate motor parameters, and accurate parameter identification comes from the correct setting of motor rated parameters.

3. In order to ensure the control performance, please configure the motor according to the standard adapted motor of the AC drive. If the power of the motor is too far from the standard adapted motor, the control performance of the inverter will be significantly reduced.

F2.06Asynchronous motor stator resistanceDefaultModel Dependent
Setting Range

0.001Ω~65.535Ω(AC drive<=55kW)

0.0001Ω~6.5535Ω(AC drive >55kW)

F2.07Asynchronous motor rotator resistanceDefaultModel Dependent
Setting Range

0.001Ω~65.535Ω(AC drive<=55kW)

0.0001Ω~6.5535Ω(AC drive >55kW)

F2.08Asynchronous motor leakage inductanceDefaultModel Dependent
Setting Range

0.01mH~655.35mH(AC drive<=55kW)

0.001mH~65.535mH(AC drive >55kW)

F2.09Asynchronous motor mutual inductanceDefaultModel Dependent
Setting Range

0.1mH~6553.5mH(AC drive<=55kW)

0.01mH~655.35mH(AC drive >55kW)

F2.10Asynchronous motor no-load currentDefaultModel Dependent
Setting Range

0.01A~F2.03(AC drive<=55kW)

0.1A~F2.03(AC drive >55kW)

After the automatic tuning ends normally, the setting values of the asynchronous motor parameters (F2.06~F2.10) are automatically updated.

After changing the motor rated power F2.01 each time, the AC drive will automatically restore the default standard motor parameters from F2.06 to F2.10. (Four-pole Y series asynchronous motor)

If it is impossible to tune the asynchronous motor in the site, you can manually input it with reference to the known parameters of similar motors.

F2.11Tuning selectionDefault0
Setting Range00:No operation
11:The asynchronous machine static tuning.
22:The asynchronous machine is fully tuned

✎Note: Before tuning, you must set the correct motor type and rated parameters (F2.00-F2.05)

0: No operation, that is, tuning is prohibited.

1: The asynchronous motor is statically tuned, which is suitable for occasions where the motor and the load are not easily disconnected and cannot be rotated and tuned.

Action description: After setting the function code to 1, and pressing the RUN key to confirm, the AC drive will perform static tuning.

2: Complete tuning of asynchronous motor. In order to ensure the dynamic control performance of the AC drive, please select complete tuning, the motor must be disconnected from the load (no load) during rotary tuning.

After the complete tuning is selected, the AC drive will perform static tuning first. After the static tuning, the motor will accelerate to 80% of the rated frequency of the motor according to the acceleration time set by F0.18, and hold for a period of time, and then follow the deceleration time set by F0.19 Decelerate to zero speed and end the rotation tuning.

Action description: After setting the function code to 2, and pressing the RUN key to confirm, the AC drive will perform rotary tuning.

Tuning instructions:

When F2.11 is set to 1 or 2 and then press the ENT key, "TUNE" is displayed and flashes at this time, and then press the RUN key to start parameter tuning, and the displayed "TUNE" stops flashing at this time. When the tuning is over, the display returns to the stop state interface. During the tuning process, you can press the STOP button to stop tuning. When the tuning is completed, the value of F2.11 automatically returns to 0.

✎Note: Tuning can only be effective in keyboard control mode, and the factory default value of acceleration and deceleration time is recommended.

F2.12G/P type selectionDefaultModel dependent
Setting Range1General model (G) (constant torque load model)
2Pump model (P) (draught fan, water pump type load model)

This parameter is only for users to view the factory model and cannot be changed.

1: Suitable for constant torque load with specified rated parameters

2: Suitable for variable torque loads with specified rated parameters (fans, water pump loads)

F2.13Single-phase motor turns ratioDefault140
Setting Range50~200

The main and auxiliary winding currents can be changed by adjusting the single-phase motor turns ratio. Generally, reducing the single-phase motor turns ratio can increase the main winding current, reduce the auxiliary winding current, and reduce the motor heating (only effective when F2.00 = 3) .

F3 group vector control parameters

F3 group function codes are only valid in vector control mode, that is, it is valid when F0.00=0, and it is invalid when F0.00=1.

F3.00Speed loop proportional gain 1Default30
Setting range1~100
F3.01Speed loop integral time 1Default0.50s
Setting range0.01s~10.00s
F3.02Switchover frequency 1Default5.00Hz
Setting range0.00~F3.05
F3.03Speed loop proportional gain 2Default20
Setting range0~100
F3.04Speed loop integral time 2Default1.00s
Setting range0.01s~10.00s  
F3.05Switchover frequency 2Default10.00Hz
Setting rangeF3.02~Maximum frequency F0.10

F3.00 and F3.01 are PI adjustment parameters when the running frequency is lower than switchover frequency 1 (F3.02).

F3.03 and F4.04 are PI adjustment parameters for the frequency band between the operating frequency greater than the switchover frequency 2.

The PI parameters in the frequency band between switchover frequency 1 and switchover frequency 2 are linear switching of two sets of PI parameters, as shown in the following figure:

CHAPTER 7 FUNCTIONAL PARAMETER DETAILS_html_3a0fe23ce96d4424.png

Figure 6-4-1 Schematic diagram of PI parameters

By setting the proportional coefficient and integral time of the speed regulator, the speed dynamic response characteristics of the vector control can be adjusted. Increasing the proportional gain and reducing the integral time can speed up the dynamic response of the speed loop. If the proportional gain is too large or the integral time is too small, the system may oscillate.

Suggested adjustment method:

If the factory parameters cannot meet the requirements, fine-tune the parameters based on the factory value: first increase the proportional gain to ensure that the system does not oscillate; then reduce the integration time to make the system have faster response characteristics and smaller overshoot.

Note: Improper setting of PI parameters may result in excessive speed overshoot. Even when the overshoot falls back, an overvoltage fault occurs.

F3.06Slip compensation coefficient of vector controlDefault100%
Setting range50%~200%

In the speed sensorless vector control mode, this parameter is used to adjust the speed stability accuracy of the motor. When the speed of the motor is heavy, increase this parameter, otherwise decrease this parameter.

F3.07Speed loop filter time constant.Default0.000s
Setting range0.000s~0.100s  

In vector control mode, the output of the speed loop regulator is the torque current command, and this parameter is used to filter the torque command. Generally, this parameter does not need to be adjusted. When the speed fluctuates greatly, the filter time can be appropriately increased; if the motor oscillates, the parameter should be appropriately reduced.

The speed loop filter time constant is small, the output torque of the AC drive may vary greatly, but the response is fast.

F3.08Speed control torque upper limitDefault150.0%
Setting range0.0%~200.0% 

In speed control mode, the maximum output torque of the inverter is controlled by F3.08.

F3.09Speed/torque controlDefault0
Setting range0Speed Control
1Torque Control

To select whether the AC drive control mode is speed control or torque control, this function code needs to be judged together with terminal function 29: torque control prohibition and 46: speed control/torque control switching.

When the torque control prohibition is valid, the AC drive is speed control.

When the torque control prohibition is invalid, if the speed control/torque control switch is invalid, the control mode is determined by F3.09; if the speed control/torque control switch is valid, the value of F3.09 is reversed.

When it is torque control, the AC drive running frequency is given by F3.12, F3.13, and the acceleration/deceleration time is given by F3.14, F3.15.

F3.10Torque upper limit source in torque controlDefault0
Setting range0Digital setting(F3.11)
1AI1
2AI2
3Reserved
4Reserved
5Communication setting
6MIN(AI1,AI2)
7MAX(AI1,AI2)
The full scale of options 1~7 corresponds to F3.11
F3.11Digital setting of torque upper limit in torque controlDefault150.0%
Setting range-200.0%~200.0%

F3.10 is used to select the torque upper limit setting source in the torque control mode. When setting by analog, 100% of analog input setting corresponds to F3.11, and 100% of setting corresponds to AC drive matching motor rated torque.

F3.12Forward maximum frequency of torque controlDefault50.00Hz
Setting range0.00Hz~Maximum Frequency(F0.10)
F3.13Reverse maximum frequency of torque controlDefault50.00Hz
Setting range0.00Hz~Maximum Frequency(F0.10) 

Set the maximum forward or reverse running frequency of the AC drive in torque control mode.

F3.14Acceleration time of torque controlDefault0.00s
Setting range0.00s~65000s
F3.15Deceleration time of torque controlDefault0.00s
Setting range0.00s~65000s 

Set the frequency acceleration/deceleration time of the AC drive in torque control mode.

F3.16Torque stiffness coefficientDefault100.00%
Setting range10.0%~120.0% 

In the torque control mode, when the set torque is small, this coefficient can be appropriately reduced to obtain a stable control effect, otherwise, the coefficient can be appropriately increased to obtain a stable control effect.

F3.17M axis current loop proportional gainDefault2000
Setting range0~60000 
F3.18M axis current loop integral gainDefault1300
Setting range0~60000 
F3.19T axis current loop proportional gainDefault2000
Setting range0~60000  
F3.20T axis current loop integral gainDefault1300
Setting range0~60000  

The current loop control parameters in the MT coordinate system and the synchronous motor dq coordinate system will be automatically identified after complete parameter identification, and generally do not need to be modified.

The bandwidth of the current loop directly determines the response speed of the electromagnetic torque. If the adjustment parameters are too strong, the current loop will be out of adjustment, causing the entire control loop to oscillate; when the current oscillates and torque fluctuations are large, you can manually adjust this group of parameters to improve the effect .

F3.21The speed loop integral separationDefault0
Setting range0Invalid
1Valid
F3.24Torque control static friction compensation coefficientDefault100
Setting range100~300
F3.25Torque mode friction compensation timeDefault0
Setting range0~100s

During startup, torque command 1 = F3.11 * F3.24 / 100; after maintaining time F3.25 seconds, it will be restored to torque command 2 = F3.11; torque command 1/2 switching requires torque acceleration and deceleration time F3.14/F3.15.

F4 group v/f control parameters

This group of function codes is only valid for V/F control (F0.00=1), and invalid for vector control.

V/F control is suitable for general loads such as fans and water pumps, or applications where one AC drive has multiple motors, or the power of the AC drive is one level lower or two levels higher than the motor power.

F4.00V/F curve settingDefault0
Setting Range0Linear V/F
1Multi-point V/F
2Square V/F
3~9Reserved
10V/F complete separation
11V/F half separation

For fans and pumps, you can choose square V/F control.

Common VF control method

0: Straight line V/F curve. Suitable for ordinary constant torque load.

1: Multi-point V/F curve. Suitable for special loads such as dehydrators and centrifuges.

2: Square V/F curve. Suitable for centrifugal loads such as fans and pumps.

VF separation control method

10: VF complete separation mode. At this time, the output voltage is set separately according to the setting mode of F4.13 (VF separation voltage source).

11: VF semi-separated mode.

In this case, V and F are proportional, and the voltage source is only used to adjust the slope of V/F. At this time, the relationship between V and F is related to the rated voltage and rated frequency of the motor set in group F2. If the voltage source input is X (X is a value of 0~100%), then: V/F=2 * X * (motor rated voltage)/(motor rated frequency)

F4.01Torque boostDefaultModel dependent
Setting Range0.0%~30%  
F4.02Cut-off frequency of torque boostDefault50.00Hz
Setting Range0.00Hz~Maximum frequencyF0.10

In order to compensate the low-frequency torque characteristics of V/F control, some boost compensation is made for the AC drive output voltage at low frequency.

If the torque boost is set too large, the motor will easily overheat and the AC drive will easily overcurrent. Generally, the torque boost should not exceed 8.0%. Effective adjustment of this parameter can effectively avoid overcurrent during starting. For larger loads, it is recommended to increase this parameter, and reduce this parameter setting when the load is lighter. When the torque boost is set to 0.0, the AC drive is automatic torque boost. Torque boost torque cut-off frequency: below this frequency, the torque boost torque is valid, if the set frequency is exceeded, the torque boost is invalid, as shown in Figure 6.6.

Output frequency

CHAPTER 7 FUNCTIONAL PARAMETER DETAILS_html_9a72975cd3987dca.png

Figure 6-5-1 Schematic diagram of manual torque boost

F4.03Multipoint V/F frequency 1Default3.00Hz
Setting Range0.00Hz~F4.05 
F4.04Multipoint V/F voltage 1Default10.0%
Setting Range0.0%~100.0%
F4.05Multipoint V/F frequency 2Default5.00Hz
Setting RangeF4.03~F4.07 
F4.06Multipoint V/F voltage 2Default15.0%
Setting Range0.0%~100.0%
F4.07Multipoint V/F frequency 3Default8.00Hz
Setting RangeF4.05~Motor rated frequency(F2.04)
F4.08Multipoint V/F voltage 3Default22.0%
Setting Range0.0%~100.0%

Six parameters F4.03~F4.08 define multi-segment V/F curve. The set value of the V/F curve is usually set according to the load characteristics of the motor. Note: V1<V2<V3, F1<F2<F3. Setting the voltage too high at low frequency may cause the motor to overheat or even burn, and the AC drive may over-current stall or over-current

protection.

CHAPTER 7 FUNCTIONAL PARAMETER DETAILS_html_f550fcd15ecbb3b8.png

Figure 6-5-2 Schematic diagram of V/F curve setting

F4.09V/F slip compensationDefault0.0%
Setting Range0%~200.0%

Effective for V/F control. Setting this parameter can compensate for the slip caused by the load during V/F control, and reduce the change in motor speed with load changes during V/F control. Generally 100% corresponds to the rated slip when the motor is loaded with rated load. The slip coefficient can be adjusted according to the following principles: when the load is rated load and the slip compensation coefficient is set to 100%, the speed of the motor with the inverter is basically close to the given speed.

F4.10V/F over-excitation gainDefault0
Setting Range0~200

The function of the VF overexcitation gain function is to suppress the rise of the bus voltage during the deceleration of the AC drive, and to prevent the bus voltage from exceeding the overvoltage protection limit value and causing an overvoltage fault. The greater the overexcitation gain, the stronger the suppression effect. The setting instructions are as follows:

1. Generally, the overexcitation gain should be set to 0 when the inertia is small, and the overexcitation gain should be appropriately increased when the inertia is large.

2. If there is a braking resistor, please set the overexcitation gain to 0

F4.11V/F oscillation suppression gainDefaultModel dependent
Setting Range0~100

Please select this gain as 0 when the motor has no oscillation. Only when the motor obviously oscillates and cannot run normally, increase the gain appropriately. The larger the gain, the more obvious the suppression of oscillation. When using the oscillation suppression function, it is required that the motor rated current and no-load current parameter settings have little deviation from the actual values. The method of selecting the gain is to choose as small as possible under the premise of effectively suppressing the oscillation, so as not to have too much influence on the VF operation.

F4.12Voltage source for V/F separationDefault0
Setting Range0Digital setting(F4.14) 
1AI1
2AI2
3Reserved
4Reserved
5Multi-speed instructions
6Simple PLC
7PID
8Communication setting
(100% corresponds to the rated motor voltage)

Define the voltage source for VF separation. The output voltage can come from digital setting (F4.13), or from analog input channel, multi-speed command, PLC, PID or communication setting. When using non-digital setting of output voltage, 100% of the input setting corresponds to the rated voltage of the motor, and the absolute value of the input setting is taken as the effective setting value.

0: Digital setting (F4.13); The voltage is directly set through F4.13.

1: AI1 2: AI2 voltage is determined by analog input terminal, AI input 0~100% corresponds to output voltage 0V~rated voltage of motor.

4: Reserved

5: Multi-speed instructions

When the voltage source is multi-speed, you need to set the F4 group "input terminal" and FC group "multi-speed and PLC" parameters to determine the corresponding relationship between the given signal and the given voltage (100% corresponds to the rated motor voltage).

6: Simple PLC

When the voltage source is a simple PLC, you need to set the FC group "multi-speed and PLC" parameters to determine the given output voltage (100% corresponds to the rated voltage of the motor).

7: PID

Generate output voltage according to PID closed loop. For details, please refer to the introduction of FA group PID.

8: Communication setting

Refers to the voltage given by the host computer through communication (100% corresponds to the rated voltage of the motor).

F4.13Voltage digital setting for V/F separationDefault0V
Setting Range0V~F2.02

When the voltage source is digital setting, this value is directly used as the target value of the output voltage.

F4.14Voltage rise time of separationDefault0.0s
Setting Range0.0s~1000.0s

VF separation rise time refers to the time required for the output voltage to change from 0V to the rated voltage of the motor.

As Figure 6-5-3:

CHAPTER 7 FUNCTIONAL PARAMETER DETAILS_html_d312ba31a6b637aa.png

Figure 6-5-3 Schematic diagram of V/F separation

F4.16Auto voltage regulation (AVR)Default1
Setting Range

0:Invalid

1:Only valid during deceleration

2:Only valid during acceleration

3:Valid

According to the actual use, select the situation where the AVR function is enabled.

F5 group input terminals

The standard unit of the VB series inverter has 6 multi-function digital input terminals and 2 analog input terminals.

F5.00DI1 terminal function selectionDefault1(Forward Running)
F5.01DI2 terminal function selectionDefault2(Reverse Running)
F5.02DI3 terminal function selectionDefault9(Reset Faults)
F5.03DI4 terminal function selectionDefault12(Multi-speed instruction terminal 1)
F5.04DI5 terminal function selectionDefault13(Multi-speed instruction terminal 2)
F5.05DI6 terminal function selectionDefault0
F5.06~F5.09Reserved
F5.10VDI terminal function selectionDefault0

These parameters are used to set the corresponding function of the digital multi-function input terminals

Set ValueFunctionDescription
0No functionThe AC drive will not operate even if a signal is input. The unused terminals can be set to have no function to prevent malfunction.
1Forward Running(FWD)Control the forward and reverse rotation of the inverter through external terminals.
2Reverse Running(REV)
3Three-wire operation controlUse this terminal to determine that the inverter operating mode is three-wire control mode. For details, please refer to F5.16 three-wire control mode function code introduction.
4Forward point movement (FJOG)FJOG is jog forward running, RJOG is jog reverse running. Refer to the detailed description of F8.00, F8.01, F8.02 function codes for frequency and jog acceleration/deceleration time during jog operation.
5Reverse point movement(RJOG)
6Terminal UPWhen the frequency is given by the external terminal, modify the frequency increase command and decrease command. When the frequency source is set to digital setting, the set frequency can be adjusted up and down.
7Terminal DOWN
8Free stopping

The inverter blocks the output, and the motor stopping process is not controlled by the inverter. For large inertia loads and when there is no requirement for stopping time, the method is often adopted.

This method has the same meaning as the free stop described in F1.10.

9Reset FaultsExternal fault reset function. It has the same function as the RESET key on the keyboard. Use this function to realize remote fault reset.
10Run pauseThe inverter decelerates to stop, but all operating parameters are in the memory state. Such as PLC parameters, swing frequency parameters, PID parameters. After this signal disappears, the inverter will resume running to the state before stopping.
11External faults normally open inputAfter the external fault signal is sent to the inverter, the inverter reports a fault and handles it according to the fault protection action mode (FA.13~FA.16).
12Multi-speed instruction terminal 1

A total of 16-speed settings can be achieved through the digital state combination of these four terminals.

See attached sheet 1 for detailed combination.

13Multi-speed instruction terminal 2
14Multi-speed instruction terminal 3
15Multi-speed instruction terminal 4
16Terminal 1 for acceleration/deceleration time selectionFour types of acceleration and deceleration time can be selected through the combination of the digital states of these two terminals. See attached sheet 2 for detailed combination.
17Terminal 2 for acceleration/deceleration time selection
18Frequency source switchover(terminal and keypad)

When the frequency source selection (F0.07 ones place) is set to 2, the main frequency source X and auxiliary frequency source Y are switched through this terminal.

When the frequency source selection (F0.07 ones place) is set to 3, this terminal is used to switch between the main frequency source X and the main and auxiliary calculation results.

When the frequency source selection (F0.07 ones place) is set to 4, use this terminal to switch between the auxiliary frequency source Y and the main and auxiliary calculation results

19UP/DOWN setting clear(terminal and keypad)When the frequency source is a digital frequency setting, this terminal can be used to clear the frequency value changed by UP/DOWN and restore the reference frequency to the value set by F0.08.
20Command source switchover terminal

When the command source (F0.01) is set to 1, this terminal can be used to switch between terminal control and keyboard control.

When the command source (F0.01) is set to 2, the communication control and keyboard control can be switched through this terminal.

21Acceleration/deceleration prohibitedEnsure that the inverter is not affected by external signals (except for the stop command) and maintain the current output frequency.
22PID pausePID is temporarily invalid and the inverter maintains the current frequency output.
23PLC status resetThe PLC pauses during execution, and can be restored to the initial state of the simple PLC through this terminal when it is running again.
24Swing pauseThe inverter outputs at the central frequency. The swing frequency is paused.
25Counter inputThe input terminal for counting pulses.
26Counter resetClear the counter status.
27Length count inputThe input terminal for length count.
28Length resetClear the length.
29Torque control prohibitedThe inverter is prohibited from torque control mode.
30ReservedReserved
31Reserved 
32Immediate DC brakingWhen this terminal is valid, the inverter directly switches to the DC braking state
33External faults normally closed inputWhen the external fault signal is sent to the inverter, the inverter reports a fault and stops.
34Frequency setting effect terminalIf the function of this terminal is set, when the frequency is modified, the effective time of the modification is controlled by this terminal
35Reverse PID action directionIf this terminal is valid, the PID action direction is opposite to the direction set by F9.03
36External stop terminal 1During keyboard control, this terminal can be used to stop, which is equivalent to the STOP key on the keypad
37Command source switchover terminal 1Used to switch between terminal control and communication control. When this terminal is valid if F0.02 is set to terminal control, it will switch to communication control; if F0.02 is set to communication control, it will switch to terminal control.
38PID integral pauseIf this terminal is valid, the PID integral function is suspended, but the proportional regulation and differential regulation still function.
39Frequency source X and preset frequency switchover terminalsIf this terminal is valid, the frequency source X is replaced by the preset frequency (F0.08)
40Frequency source Y and preset frequency switchover terminalsIf this terminal is valid, the frequency source Y is replaced by the preset frequency (F0.08)
41Reserved 
42Reserved 
43PID parameter switchover terminalWhen F9.18 (PID parameter switching condition) is DI terminal, when this terminal is valid, PID uses F9.15~F9.17 parameters. When the terminal is invalid, use F9.05~F9.07 parameters
44User-defined fault 1After the external fault signal is sent to the inverter, the inverter reports a fault and handles it according to the fault protection action mode (FA.13~FA.16).
45User-defined fault 2After the external fault signal is sent to the inverter, the inverter reports a fault and handles it according to the fault protection action mode (FA.13~FA.16).
46Speed control/torque control switchoverSwitch the inverter to run in torque control or speed control mode. If this terminal is invalid, it runs in the mode defined by F3.09 (speed/torque control mode), and if it is valid, it switches to the other mode.
47Emergency stopIf this terminal is valid, the inverter will stop at the fastest speed
48External stopping terminal 22Under any control mode, this terminal can be used to stop, and stop according to deceleration time 4
49Deceleration DC brakingIf this terminal is valid, the inverter will first decelerate to the start frequency of stop DC braking and then switch to DC braking state
50Clear the current running timeIf this terminal is valid, the inverter's current running timing time will be cleared, and this function will be used for timing running (F8.42).

Attached sheet: Multi-speed function description

K4K3K2K1Set FrequencyRelated Parameter
OFFOFFOFFOFFMultistage Speed0FD.00
OFFOFFOFFONMultistage Speed1FD.01
OFFOFFONOFFMultistage Speed2FD.02
OFFOFFONONMultistage Speed3FD.03
OFFONOFFOFFMultistage Speed4FD.04
OFFONOFFONMultistage Speed5FD.05
OFFONONOFFMultistage Speed6FD.06
OFFONONONMultistage Speed7FD.07
ONOFFOFFOFFMultistage Speed8FD.08
ONOFFOFFONMultistage Speed9FD.09
ONOFFONOFFMultistage Speed10FD.10
ONOFFONONMultistage Speed11FD.11
ONONOFFOFFMultistage Speed12FD.12
ONONOFFONMultistage Speed13FD.13
ONONONOFFMultistage Speed14FD.14
ONONONONMultistage Speed15FD.15

Attached sheet: description of acceleration and deceleration time selection

Terminal 2Terminal 1Selection of acceleration/deceleration timeRelated Parameter
OFFOFFAcceleration/Deceleration Time1F0.18. F0.19
OFFONAcceleration/Deceleration Time2F8.03. F8.04
ONOFFAcceleration/Deceleration Time3F8.05. F8.06
ONONAcceleration/Deceleration Time4F8.07. F8.08
F5.15DI filter timeDefault0.010s
Setting range0.000s~1.000s 

Set the sensitivity of the DI terminal. If the digital input terminal is susceptible to interference and cause malfunction, you can increase this parameter to increase the anti-interference ability, but cause the sensitivity of the DI terminal to decrease.

F5.16Terminal command modeDefault0
Setting range0Two-line mode 1
1Two-line mode 2
2Three-line mode 1
3Three-line mode 2

This parameter defines four different ways to control the operation of the inverter through external terminals.

0: Two-line mode 1: This mode is the most commonly used two-line mode. The FWD and REV terminal commands determine the forward and reverse of the motor.

1681697850903-377.png

1: Two-wire mode 2: FWD is the enable terminal when using this mode. The direction is determined by the state of the REV.

1681697969422-504.png

2: Three-line mode 1: This mode Din(function code 3) is the enable terminal, and the direction is controlled by FWD and REV respectively.

DIN is pulse effective, user need to disconnect the Din terminal signal when stop.

Din is the multifunctional input terminal of DI1~DI6. At this time, the corresponding terminal function should be defined as the No. 3 function "three-wire operation control".

1681698530367-261.png

3: Three-line mode 2: The enable terminal of this mode is Din, the running command is given by FWD, and the direction is determined by the state of REV. The stop command is completed by disconnecting the Din signal.

Din is the multi-function input terminal of DI1~DI6. At this time, the corresponding terminal function should be defined as the No. 3 function "three-wire operation control".

1681698557086-403.png

F5.17UP/DOWN change rate rangeDefault0.50Hz
Setting range0.01Hz~65.535Hz

Frequency change rate while using terminal UP/DOWN function

F5.18AI1 minimum inputDefault0.00V
Setting range0.00V~F5.15  
F5.19Percentage rate of AI1 minimum inputDefault0.0%
Setting range-100.00%~100.0%
F5.20AI1 maximum inputDefault10.00V
Setting rangeF5.18~10.00V  
F5.21Percentage rate of AI1 maximum inputDefault100.0%
Setting range-100.00%~100.0%
F5.22AI1 filter timeDefault0.10s
Setting range0.00s~10.00s

The above function code defines the relationship between the analog input voltage and the set value represented by the analog input. When the analog input voltage exceeds the set maximum input range, the other part will be calculated as the maximum input. When the analog input voltage exceeds the set minimum input The range, the outside part will be calculated based on the AI minimum input.

When analog input is current input, 1mA current is equivalent to 0.5V voltage. In different applications, the nominal value corresponding to 100% of the analog setting is different. For details, please refer to the description of each application part.

The following figures illustrate several settings:

CHAPTER 7 FUNCTIONAL PARAMETER DETAILS_html_18e4cbe6e1292696.png

Figure 6-6-1 Correspondence between analog reference and setting

F5.23AI2 minimum inputDefault0.00V
Setting range0.00V~F5.25  
F5.24Percentage rate of AI2 minimum inputDefault0.0%
Setting range-100.00%~100.0%
F5.25AI2 maximum inputDefault10.00V
Setting rangeF5.23~10.00V  
F5.26Percentage rate of AI2 maximum inputDefault100.0%
Setting range-100.00%~100.0%
F5.27AI2 filter timeDefault0.10s
Setting range0.00s~10.00s

The function of AI2 is similar to the setting method of AI1.

F5.33DI1 enable delay timeDefault0.0s
Setting range0.0s~3600.0s
F5.34DI1 disable delay timeDefault0.0s
Setting range0.0s~3600.0s
F5.35DI2 enable delay timeDefault0.0s
Setting range0.0s~3600.0s
F5.36DI2 disable delay timeDefault0.0s
Setting range0.0s~3600.0s

Set the delay time from DI terminal status change to inverter response.

Currently only DI1\DI2 has the function of setting the delay time.

F5.37DI valid mode selection 1Default00000
Setting rangeOnes PlaceDI1 terminal valid state setting
0High level
1Low Level
Tens PlaceDI2 terminal valid state setting(0~1,as above)
Hundreds PlaceDI3 terminal valid state setting(0~1,as above)
Thousands PlaceDI4 terminal valid state setting(0~1,as above)
Ten Thousands PlaceDI5 terminal valid state setting(0~1,as above)
F5.38DI valid mode selection 2Default00000
Setting rangeOnes PlaceDI6 terminal valid state setting
0High level
1Low Level
Tens PlaceReserved
Hundreds PlaceReserved
Thousands PlaceReserved
Ten Thousands PlaceReserved

Define the effective state setting of the input terminal.

High level:The connection between DI terminal and COM is valid, while disconnection is invalid.

Low Level:The connection between DI terminal and COM is invalid, while disconnection is valid.

F6 group output terminals

The standard unit of VB series inverter has 2 multi-function relay output terminals, 1 FM terminal and 2 multi-function analog output terminals.

F6.00FM terminal output modeDefault1
Setting range0Pulse Output(FMP)(Reserved)  
1Open-collector output(FMR)  

The FM terminal is a programmable multiplexing terminal. It can be used as an open collector output terminal (FMR). Refer to F6.01 for FMR function.

FMP function needs hardware support

F6.01FMR functionDefault0
F6.02Relay 1 functionDefault2
F6.03Relay 2 functionDefault1
F6.06VDO Output SelectionDefault0

The functions of the multi-function output terminals are as follows:

Set ValueFunctionDescription
0No outputThe output terminal has no function  
1AC Drive runningIt means that the inverter is running and there is an output frequency (it can be zero) and the ON signal is output at this time.
2Fault output(stop)When the inverter fails and it stops, it outputs ON signal.
3Frequency level detection FDT1 outputPlease refer to the detailed description of function codes F8.08 and F8.09.
4Frequency reachedPlease refer to the detailed description of function codes F8.21
5Zero-speed running(no output at stop)The inverter runs and the output frequency is 0, and the ON signal is output.
6Motor overload pre-warningBefore the motor electronic thermal protection acts, it is judged according to the overload forecast value, and the ON signal is output after the forecast value is exceeded. Motor overload parameters are set in FA.00~FA.02.
7AC Drive overload pre-warningAfter checking that the inverter is overloaded, advance 10s before the protection occurs. Output ON signal.
8Set count value reachedWhen the count value reaches the value set by FB.08, the ON signal is output.
9Designated count value reachedWhen the count value reaches the value set by FB.09, the ON signal is output. Refer to the function description of FB group for counting function
10Length reachedWhen the actual length detected exceeds the length set by FB.05, the ON signal is output.
11PLC cycle completeWhen the simple PLC runs a cycle, it outputs a pulse signal with a width of 250ms.
12Accumulative running time reachedWhen the accumulative running time of the inverter exceeds the time set by F8.17, it outputs ON signal.
13Frequency limitedWhen the set frequency exceeds the upper and lower frequency limits and the inverter output frequency reaches the upper and lower frequency limits, the ON signal is output.
14Torque limitedWhen the torque limit function is activated, the stall protection function automatically activates, automatically changes the output frequency, and outputs an ON signal to indicate that the output torque is limited. This output signal can be used to reduce the load or display an overload status signal on the monitoring device.
15Ready for runningThe power supply of the main circuit and control circuit is established, the protection function of the inverter does not operate, and the inverter outputs ON signal when it is in an operational state.
16AI1 larger than AI2When the value of analog input AI1 is greater than the other input AI2, the ON signal is output.
17Frequency upper limit reachedWhen the operating frequency reaches the upper limit frequency, the ON signal is output.
18Frequency lower limit reachedWhen the operating frequency reaches the lower limit frequency, the ON signal is output.
19Undervoltage state outputWhen the inverter is under voltage, it outputs ON signal.
20Communication settingSee the relevant description in the communication protocol.
21Positioning completed (Reserved)Reserved
22Positioning close (Reserved)Reserved
23Zero-speed running 2(having output at stop)When the output frequency of the inverter is 0, the ON signal is output (also output when stopping).
24Accumulative power-on time reachedWhen F7.13 (accumulated power-on time of the inverter) exceeds the time set by F8.16, the ON signal is output.
25Frequency level detection FDT2Please refer to the detailed description of function codes F8.28 and F8.39.
26Frequency 1 reachedPlease refer to the detailed description of function codes F8.30 and F8.31.
27Frequency 2 reachedPlease refer to the detailed description of function codes F8.32 and F8.33.
28Current 1 reachedPlease refer to the detailed description of function codes F8.38 and F8.30.
29Current 2 reachedPlease refer to the detailed description of function codes F8.40 and F8.41.
30Timing reachedWhen F8.42 (timing function selection) is valid, the inverter will output ON signal when the current running time reaches the set timing time.
31AI1 input limit exceededWhen the value of analog input AI1 is greater than F8.46 (AI1 input protection upper limit) or less than F8.45 (AI1 input protection lower limit), FM (FMR) outputs ON signal.
32OffloadOutput ON signal when the inverter is in the off-load state
33Running directionOutput ON signal when inverter is running in reverse
34Zero current detectionPlease refer to the detailed description of function codes F8.34 and F8.35.
35Module temperature reachedWhen F7.07 (IGBT module heatsink temperature) reaches the value of F8.47 (module temperature reached), output ON signal
36Software overcurrent outputPlease refer to the detailed description of function codes F8.36 and F8.37.
37Lower limit frequency reached (non-operational)When the running frequency reaches the lower limit frequency, the ON signal is output (also output when stopping).
38Fault output (continue operation)When the inverter fails, output ON signal
39Reserved 
40This running time arrive 
41User-defined output 1The user can define the conditions for the output terminal to output, see F6.28~F6.32 for details.
42User-defined output 2The user can define the conditions for the output terminal to output, see F6.23~F6.37 for details.
43

Timer output

If the timer arrives, the VFD outputs ON signal

44

Forward running status

If the VFD is running forward, output ON signal

45

Reverse running status

If the VFD is running reverse, output ON signal

F6.11FMP(Pulse output terminal)output selection(Reserved)Default0
F6.12AO1 functionDefault0
F6.13AO2 functionDefault1

The standard output of analog output (zero offset is 0, gain is 1) is 0mA~20mA (or 0V~10V), and the FMP output range is from 0Hz to the setting of function code F5.09.

The range of the corresponding amount expressed is shown in the following Sheet:

Set valueFunctionRange
0Running frequency0~Maximum output power
1Set frequency0~Maximum output frequency
2Output current0~2 times motor rated current
3Output torque0~2 times motor rated torque
4Output power0~2 times motor rated power
5Output voltage0~1.2 times AC drive rated voltage
6PULSE input0.01kHz~100.00kHz
7AI10V~10V
8AI20V~10V/0~20mA
10Length0~Maximum set length
11Count value0~Maximum count value
12Communication setting-10000~10000
13Motor Speed0~Rotation speed corresponding to maximum output frequency
14Output Current0-1000A,as 0-10V
 0-1000V,as 0-10V
15Output Voltage0.0V~1000.0V
F6.14FMP output maximum frequencyDefault50.00kHz   
Setting range0.01kHz~100.00kHz   

When the FM terminal is selected as pulse output, the maximum frequency value of the pulse can be output.

F6.15AO1 offset coefficientDefault0.0%   
Setting range-100.0%~100.0%
F6.16AO1 gainDefault1.00   
Setting range-10.00~10.00
F6.17AO2 offset coefficientDefault0.00%   
Setting range-100.0%~100.0%
F6.18AO2 gainDefault1.00   
Setting range-10.00~10.00

If the zero offset is represented by "b", the gain is represented by k, the actual output is represented by Y, and the standard output is represented by X, the actual output is Y=kX+b; AO1, A02 zero offset coefficient 100% corresponds to 10V (20mA). Standard output refers to the output 0V~10V (20mA) corresponding to the analog output representing 0~max. Generally used to correct the zero drift of analog output and the deviation of output amplitude. It can also be customized to any desired output curve: For example: if the analog output content is the operating frequency, and hope to output 8V (16mA) when the frequency is 0, and 3V (6mA) when the frequency is the maximum frequency, the gain should be set to " .0.50", the zero offset should be set to "80%".

F6.19FMR connecting delay timeDefault0.0s
Setting range0.0s~3600.0s
F6.20RELAY1 connecting delay timeDefault0.0s
Setting range0.0s~3600.0s
F6.21RELAY2 connecting delay timeDefault0.0s
Setting range0.0s~3600.0s
F6.22VDO connecting delay timeDefault0.0s
Setting range0.0s~3600.0s
F6.23FMR disconnecting delay timeDefault0.0s
Setting range0.0s~3600.0s
F6.24RELAY1 disconnecting delay timeDefault0.0s
Setting range0.0s~3600.0s
F6.25RELAY2 disconnecting delay timeDefault0.0s
Setting range0.0s~3600.0s
F6.26VDO disconnecting delay timeDefault0.0s
Setting range0.0s~3600.0s

Set the delay time from the state change of the output terminal FMR, relay 1, relay 2, VDO to the output change.

F6.27Output terminal valid state selectionDefault00000
Setting rangeOnes PlaceFMR valid state selection
0Positive Logic
1Negative Logic
Tens PlaceRELAY1 valid state selection(0~1,as above)
Hundreds PlaceRELAY2 valid state selection(0~1,as above)
Thousands PlaceReserved
Ten Thousands PlaceReserved

Define the positive and negative logic of output terminal FMR, relay 1, and relay 2.

Positive logic: the digital output terminal is valid when connected to the corresponding common terminal, but invalid when disconnected;

Inverse logic: the connection between the digital output terminal and the corresponding common terminal is invalid, and the disconnection is valid;

F6.28

User defined output

variability selection (EX)1

Default00
Setting range0~49

This parameter is used to select the reference variable for custom output. Use the selected variable EX as the comparison object

F6.29User defined comparison method 1Default00
Setting range0~14

The ones place selection comparison test mode, the variable selected by F6.28 is used as the comparison test object, and the comparison and test values are set by F6.31~F6.32.

Tens place selects the output mode. False value output means output if the condition is not met, and no output if the condition is met; true value output means output if the condition is met, and no output if the condition is not met.

F6.30User defined output dead zone 1Default0
Setting range0~65535

When the comparison test mode of F6.29 is set to be greater than or equal to or less than or equal to, F6.30 is used to define the processing dead zone value centered on the comparison value X1, and the processing dead zone is only for 1 and 2 of the F6.29 comparison test mode It has an effect, but no effect on 0, 3, and 4. For example, when F6.29 is set to 11, when EX increases from 0 upwards, the output is valid after increasing to greater than or equal to X1+F6.30; when EX decreases downward, after decreasing to less than or equal to X1.F6.30, The output is invalid.

F6.31

User-defined 1 output

comparison value X1

Default0
Setting range0~65535
F6.32

User-defined 1 output

comparison value X2

Default0
Setting range0~65535

These two parameters are used to set the comparison value of the custom output.

The following is an example of using custom output:

When the set frequency is greater than or equal to 20.00HZ, the relay is closed;

The setting parameters are as follows: F6.02 = 41, F6.28 = 1, F6.29 = 11, F6.30 = 0, F6.31 = 2000;

2. The relay is required to close when the bus voltage is less than or equal to 500.0V; in order to avoid frequent relay actions when the detection voltage is 5.0V up and down from 500.0V, it is required to be treated as a dead zone in the range of (500.0-5.0) ~ (500.0+5.0) .

The setting parameters are as follows: F6.02 = 41, F6.28 = 2, F6.29 = 01, F6.30 = 50, F6.31 = 5000;

When the inverter is required to reverse, the relay is closed:

The setting parameters are as follows: F6.02 = 41, F6.28 = 5, F6.29 = 14, F6.31 = 8, F6.32 = 8;

When AI1 input is required to be greater than 3.00V and less than or equal to 6.00V, the relay is closed:

The setting parameters are as follows: F6.02 = 41, F6.28 = 13, F6.29 = 13, F6.31 = 300, F6.32 = 600;

F6.33

User defined output

variability selection (EX)2

Default00
Setting range0~49
F6.34User defined comparison method 2Default00
Setting range0~14
F6.35User defined output dead zone 1Default0
Setting range0~65535
F6.36

User-defined 2 output

comparison value X1

Default0
Setting range0~65535
F6.37

User-defined 2output

comparison value X2

Default0
Setting range0~65535

For the second output, the parameter setting method is the same as F6.28~F6.32.

F6.38The setting time of timerDefault0
Setting range0.00s~100.0s

Set the timer setting time

F7 group keypad display

F7.00LCD keypad parameter copyDefault0
Setting range0No operation
1Upload local functional parameters to LCD keypad
2Download functional parameters from LCD keypad to AC drive

Note: This function only supports LCD keyboard

F7.01MF.K key function selectionDefault0
Setting range0MF.K disabled
1Switchover between keypad control and remote command control(terminal or communication)
2Switchover between forward rotation and reverse rotation
3Forward JOG
4Reverse JOG
5Menu mode switching

The MF.K key is the multi-function key. The function of the keyboard MF.K key can be defined through parameter settings. This key can be used to switch during stop and running.

0: When set to 0, this key has no function.

1: Switchover between keypad control and remote command control(terminal or communication). Refers to the switch of the command source, from the current command source to keyboard control (local operation). If the current command source is keyboard control, this command has no effect.

2: Switchover between forward rotation and reverse rotation

Switch the direction of the frequency command through the keyboard MF.K key. It is valid only in the operation panel command channel.

3: Forward jog

Realize forward jog (FJOG) by keyboard MF.K key.

4: Reverse jog

Reverse jog (RJOG) can be realized by keyboard MF.K key.

5: Menu mode switching

The menu mode switch is realized through the keyboard MF.K key.

F7.02STOP/RESET key functionDefault1
Setting range0STOP/RESET key enabled only in keypad control
1STOP/RESET key enabled in any operation mode
F7.03LED display parameters 1 while runningDefault17
Setting range

0000

~FFFF

Bit00: Running frequency (Hz)

Bit01: Set frequency (Hz)

Bit02: DC bus voltage (V)

Bit03: Output voltage (V)

Bit04: Output current (A)

Bit05: Output power (kW)

Bit06: Output torque (%)

Bit07: DI input status

Bit08: DO output status

Bit09: AI1 power (V)

Bit10: AI2 power (V)

Bit11: Reserved

Bit12: Count value

Bit13: Length value

Bit14: Load speed display

Bit15: PID set value

If you need to display the above parameters while running, set the corresponding digit to 1, convert this binary number to hexadecimal and set it to F7.03.

F7.04LED display parameters 2 while runningDefault0
Setting range

0000

~FFFF

Bit00: PID feedback

Bit01: PLC stage

Bit02: Feedback speed (0.1Hz)

Bit03: Reserved

Bit04: Remaining running time

Bit05: AI1 voltage before correction

Bit06: AI2 voltage before correction

Bit07: Reserved

Bit08: Linear speed

Bit09: Current power-on time

Bit10: Current running time

Bit11: Reserved

Bit12: Communication setting

Bit13: Reserved

Bit14: Main frequency X display

Bit15: Auxiliary frequency Y display

If you need to display the above parameters while running, set the corresponding digit to 1, convert this binary number to hexadecimal and set it to F7.04

The running display parameters are used to set the status parameters that can be viewed when the inverter is running. Up to 32 state parameters can be viewed. Select the state parameters to be displayed according to the digits of the parameter values of F7.03 and F7.04, and the display sequence starts from the lowest bit of F7.03.

F7.05LED display parameters while stoppingDefault33
Setting range

0000

~FFFF

Bit00: Set frequency (Hz)
Bit01: DC bus voltage(V)
Bit02: DI input status
Bit03: DO output status
Bit04: AI1 voltage (V)
Bit05: AI2 voltage (V)
Bit06: Reserved
Bit07: Count value
Bit08: Length value
Bit09: PLC stage
Bit10: Load speed display
Bit11: PID set value
Bit12: Reserved

Bit13: PID feedback value

If you need to display the above parameters while stopping, set the corresponding digit to 1, convert this binary number to hexadecimal and set it to F7.05

F7.06Load speed display coefficienDefault1.0000
Setting range0.0001~6.5000

Correspond the output frequency of the inverter to the load speed through this parameter. Set when you need to display the load speed.

The specific calculation method is described in F7.12.

F7.07Heatsink temperature of IGBTDefault0
Setting range0.0℃~100.0℃

Displays the temperature of the IGBT module. The over-temperature protection value of IGBT module of different models may be different.

F7.08Heatsink temperature of rectifier bridgeDefault0
Setting range0.0℃~100.0℃

Displays the temperature of the rectifier bridge. The over-temperature protection value of rectifier bridge of different models may be different.

F7.09Accumulative running timeDefault0h
Setting range0h~65535h

Display the cumulative running time of the inverter so far. When this time reaches the set running time (F8.17), the multi-function digital output (12) of the inverter will act.

F7.10Product NumberDefault-
Setting rangeProduct Number of AC Drive
F7.11Software VersionDefault 
Setting rangeSoftware Version of Control Board
F7.12Number of decimal places for load speed displayDefault0
Setting range00 decimal places
11 decimal places
22 decimal places
33 decimal places

The load speed calculation method is: if the load speed display coefficient is 2.000, the load speed decimal point position is 2: 2 decimal points.

When the inverter is running: if the running frequency is 40.00 Hz, 4000*2.000 = 8000, and 2 decimal points display, the load speed is 80.00.

When the inverter is stopped: If the set frequency is 50.00 Hz, 5000*2.000 = 10000, and the load speed is 100.00 when displayed with 2 decimal points.

F7.13Accumulative power-on timeDefault0h
Setting range0h~65535h

Display the cumulative power-on time of the inverter so far. When this time reaches the set power-on time (F8.17), the inverter's multi-function digital output (24) will act.

F7.14Accumulative power consumptionDefault0
Setting range0~65535

Displays the cumulative power consumption of the inverter so far.

F7.15Performance software versionDefault-
Setting range-

F8 group auxiliary functions

F8.00JOG running frequencyDefault2.00Hz
Setting range0.00Hz~F0.10
F8.01JOG acceleration timeDefault20.0s
Setting range0.0s~6500.0s
F8.02JOG deceleration timeDefault20.0s  
Setting range0.0s~6500.0s

Define the given frequency and acceleration/deceleration time of the inverter during jog. The jog process starts and stops according to start mode 0 (F1.00, direct start) and stop mode 0 (F1.10, decelerate to stop).

Jog acceleration time refers to the time required for the inverter to accelerate from 0Hz to the maximum output frequency (F0.10).

Jog deceleration time refers to the time required for the inverter to decelerate from the maximum output frequency (F0.10) to 0Hz.

F8.03Acceleration time2DefaultModel dependent
Setting range0. 0s~6500.0s
F8.04Deceleration time2DefaultModel dependent
Setting range0. 0s~6500.0s
F8.05Acceleration time3DefaultModel dependent
Setting range0. 0s~6500.0s
F8.06Deceleration time3DefaultModel dependent
Setting range0. 0s~6500.0s
F8.07Acceleration time4DefaultModel dependent
Setting range0. 0s~6500.0s
F8.08Deceleration time4DefaultModel dependent
Setting range0. 0s~6500.0s

The acceleration and deceleration time can be selected from F0.18 and F0.19 and the above three types of acceleration and deceleration time. The meanings are the same, please refer to the relevant description of F0.18 and F0.19. The acceleration and deceleration time 1~4 during the operation of the inverter can be selected through different combinations of the multifunctional digital input terminal DI. Please refer to the function codes F5.01~F5.05.

F8.09Jump frequency 1Default0.00Hz
Setting range0.00Hz~F0.10
F8.10Jump frequency 2Default0.00Hz
Setting range0.00 Hz~F0.10
F8.11Frequency jump amplitudeDefault0.01Hz
Setting range0.00~F0.10

When the set frequency is within the jump frequency range, the actual running frequency will run at the jump frequency boundary close to the set frequency. By setting the jump frequency, the inverter can avoid the mechanical resonance point of the load. This inverter can set two jumping frequency points. If both skip frequencies are set to 0, this function will not work.

CHAPTER 7 FUNCTIONAL PARAMETER DETAILS_html_9a49731ff18de325.png

Figure 6-9-1 Schematic diagram of hopping frequency

F8.12Forward/Reverse rotation dead-zone timeDefault0.0s
Setting range0.00s~3000.0s

Set the transition time at the output zero frequency during the forward and reverse transition of the inverter, as shown in the figure below:

CHAPTER 7 FUNCTIONAL PARAMETER DETAILS_html_d8f000d30762f35.png

Figure 6-9-2 Schematic diagram of forward and reverse dead zone time

F8.13Reverse controlDefault0
Setting range0Enabled
1Disabled

When this parameter is 0: it can be reverse controlled by keyboard, terminal or communication.

When this parameter is 1: the reverse control function is valid regardless of the command source selection, that is, the reverse control function is invalid under keyboard, terminal, and communication control.

F8.14The carrier frequency is adjusted with temperatureDefault1
Setting range0No
1Yes

Provide fixed and random PWM carrier frequency adjustment methods. Random PWM motor noise has a wide frequency domain, and fixed PWM motor noise frequency is fixed.

The carrier frequency temperature adjustment is effective, which means that the inverter can automatically adjust the carrier frequency according to its own temperature. Selecting this function can reduce the chance of inverter overheating alarm.

F8.15Droop controlDefault0.00Hz
Setting range0.00Hz~10.00Hz

When multiple inverters drive the same load, the load distribution is unbalanced due to different speeds, which makes the inverter with higher speed bear heavier load. The droop control characteristic is that the speed droops as the load increases, which can make the load balanced.

This parameter adjusts the frequency change of the inverter with drooping speed.

F8.16Setting of accumulated power-on arrive timeDefault0h
Setting range0h~65000h

Preset the power-on time of the inverter. When the accumulated power-on time (F7.13) reaches this set power-on time, the inverter's multi-function digital DO outputs a running time arrival signal.

F8.17Setting of accumulated running arrive timeDefault0h
Setting range0h~65000h

Pre-set the running time of the inverter. When the accumulated running time (F7.09) reaches this set running time, the inverter's multi-function digital DO outputs a running time arrival signal.

F8.18Startup protectionDefault0
Setting range0Invalid
1Valid

This function code is used to improve the safety protection coefficient. If it is set to 1, it has two effects: one is that if the running command exists when the inverter is powered on, the running command must be removed to eliminate the running protection status. The second is that if the running command still exists when the inverter fault is reset, the running command must be removed first to eliminate the running protection state. This can prevent the motor from running automatically without knowing it, causing danger.

F8.19Frequency detection value (FDT1)Default50.00Hz
Setting range0.00Hz~F0.10
F8.20Frequency detection hysteresis (FDT1)Default5.0%
Setting range0.0%~100.0%(FDT1)

Set the detection value of the output frequency and the hysteresis value of the output operation release.

CHAPTER 7 FUNCTIONAL PARAMETER DETAILS_html_a185f8b9d5aa6fa7.png

Figure 6-9-3 FDT1 level diagram

F8.21Detection amplitude of frequency reachedDefault0.0%
Setting range0.00~100%*F0.10

When the output frequency of the inverter reaches the set frequency value, this function can adjust its detection amplitude. As shown below:

CHAPTER 7 FUNCTIONAL PARAMETER DETAILS_html_5226db5d1f9834fd.png

Figure 6-9-4 Schematic diagram of frequency arrival detection amplitude

F8.22Jump frequency during acceleration/decelerationDefault0
Setting range

0:Disabled

1:Enabled

This function code is set to be valid. When the running frequency is within the jump frequency range, the actual running frequency will directly skip the set jump frequency boundary.

CHAPTER 7 FUNCTIONAL PARAMETER DETAILS_html_43540e37b92098da.png

Figure 6-9-5 Schematic diagram of effective jumping frequency during acceleration and deceleration

F8.23Accumulated running time arrive selectionDefault0
Setting range0:Keep running
 1:Fault warning
F8.24Accumulated power-on time arrive action selectionDefault0
Setting range0:Keep running
 1:Fault warning

Set to 1: When the fault prompts, if the running time or power-on time arrives, according to the FA group fault protection action selection, the inverter will stop freely, decelerate to stop or continue to run (please refer to the function code FA.13~FA.16 for detailed description).

F8.25Acceleration time 1/2 switching frequency pointDefault0.00Hz
Setting range0.00Hz~F0.10
F8.26Deceleration time 1/2 switching frequency pointDefault0.00Hz
Setting range0.00Hz~F0.10

CHAPTER 7 FUNCTIONAL PARAMETER DETAILS_html_2b2ceaa98c745458.png

Figure 6-9-6 Schematic diagram of acceleration and deceleration time switching

1. Switchover selection during acceleration time

During acceleration, if the running frequency is less than F8.25 (acceleration time 1/2 switching frequency point), acceleration time 2 is selected, otherwise, acceleration time 1 is selected.

2. Switchover selection during deceleration time

During deceleration, if the running frequency is less than F8.26 (deceleration time 1/2 switching frequency point), deceleration time 2 is selected, otherwise, deceleration time 1 is selected.

F8.27Terminal JOG preferredDefault1
Setting range

0:Disabled

1:Enabled

This parameter is used to set the priority of terminal jog. When this parameter is set to be valid, once DI terminal receives the jog control command, the inverter will switch from other running states to terminal jog running state.

F8.28Frequency detection value (FDT2)Default50.00Hz
Setting range0.00Hz~F0.10
F8.29Frequency detection hysteresis (FDT2)Default5.0%
Setting range0.0%~100.0%(FDT2)

The function of FDT2 is similar to the setting method of FDT1 (F8.19, F8.20).

CHAPTER 7 FUNCTIONAL PARAMETER DETAILS_html_9a49acf9634cd985.png

Figure 6-9-7 FDT2 level diagram

F8.30Arbitrary frequency reaching detection value 1Default50.00Hz
Setting range0.00Hz~F0.10
F8.31Arbitrary frequency reaching detection amplitude 1Default0.0%
Setting range0.0%~100.0%(F0.10)
F8.32Arbitrary frequency reaching detection value 2Default50.00Hz
Setting range0.00Hz~F0.10
F8.33Arbitrary frequency reaching detection amplitude 2Default0.0%
Setting range0.0%~100.0%(F0.10)

When the output frequency of the inverter is within the positive or negative detection range of the arbitrary arrival frequency detection value 1, 2, output pulse signal. As shown below:

CHAPTER 7 FUNCTIONAL PARAMETER DETAILS_html_3aef8d5790f3423f.png

Figure 6-9-8 Schematic diagram of arbitrary reaching frequency detection

F8.34Zero current detection levelDefault5.0%
Setting range0.0%~300.0%(Motor rated current)
F8.35Zero current detection delay timeDefault0.10s
Setting range0.00s~600.00s

When the output current of the inverter is less than or equal to the zero current detection level and the duration exceeds the zero current detection delay time, a pulse signal is output. As shown below:

CHAPTER 7 FUNCTIONAL PARAMETER DETAILS_html_c93b84a4c5da944b.png

Figure 6-9-9 Schematic diagram of zero current detection

F8.36Software overcurrent pointDefault200.0%
Setting range0.0%(Invalid) ; 0.1%~300.0%(Motor rated current)
F8.37Software overcurrent detection delay timeDefault0.00s
Setting range0.00s~600.00s

When the output current of the inverter is greater than or equal to the software overcurrent point and the duration exceeds the software overcurrent point detection delay time, a pulse signal is output. As shown below:

CHAPTER 7 FUNCTIONAL PARAMETER DETAILS_html_879549a41172d673.png

Figure 6-9-10 Schematic diagram of software overcurrent point detection

F8.38Arbitrary reaching current 1Default100.0%
Setting range0.0%~300.0%(Motor rated current)
F8.39Arbitrary reaching current amplitude 1Default0.0%
Setting range0.0%~300.0%(Motor rated current)
F8.40Arbitrary reaching current 2Default100.0%
Setting range0.0%~300.0%(Motor rated current)
F8.41Arbitrary reaching current amplitude 2Default0.0%
Setting range0.0%~300.0%(Motor rated current)

When the output current of the inverter is within the detection amplitude of the positive and negative currents 1 and 2, it outputs a pulse signal. As shown below:

CHAPTER 7 FUNCTIONAL PARAMETER DETAILS_html_9c74ba626be55d06.png

Figure 6-9-11 Schematic diagram of arbitrary reaching frequency detection

F8.42Timing functionDefault0
Setting range0Disabled
1Enabled
F8.43Timing duration sourceDefault0
Setting range0F8.44 setting
1AI1
2AI2
3Reserved
F8.44Timing durationDefault0.0Min
Setting range0.0Min~6500.0Min

This function is used to complete the timing operation of the inverter. When the F8.42 timing function selection is valid, the inverter is running timing. When the set timing running time is reached, the inverter stops and outputs pulse signals. The timer will be cleared next time it runs. The timing remaining running time can be viewed through D0.20.

The set timing running time is determined by F8.43 and F8.44.

F8.45AI1 input voltage lower limitDefault3.10V
Setting range0.00V~F8.46
F8.46AI1 input voltage upper limitDefault6.80V
Setting rangeF8.45~10.00V

When the value of analog input AI1 is greater than F8.46 (AI1 input protection upper limit) or less than F8.47 (AI1 input protection lower limit), FM (FMR) outputs a pulse signal.

F8.47IGBT temperature thresholdDefault75℃
Setting range0.00V~F8.46

When F7.07 (IGBT module radiator temperature) reaches this value, output pulse signal

F8.48Fast current limitingDefault1
Setting range0Disabled
1Enabled

Enabling the fast current limiting function can minimize the inverter's overcurrent fault and protect the inverter from uninterrupted operation. After entering the fast current-limiting state for a period of time, a fast current-limiting fault (Err40) will be reported, indicating that the inverter is overloaded. Please refer to the handling of Err10.

F9 group pid function of process control

PID control is a common method used in process control. It adjusts the output frequency of the inverter by performing proportional, integral, and differential calculations on the difference between the feedback signal of the controlled quantity and the target quantity signal to form a negative feedback system. The controlled amount is stable at the target amount. It is suitable for process control such as flow control, pressure control and temperature control. The basic control block diagram is as follows:

CHAPTER 7 FUNCTIONAL PARAMETER DETAILS_html_972dcbcc01a1c9f6.png

生产流程图.png

Figure 6-10-1 Block diagram of process PID principle

F9.00PID setting sourceDefault0
PID setting source0F9.01
1AI1
2AI2
3Reserved
4

Reserved

5Communication setting
6Multi-speed instructions

When the frequency source selects PID, that is, if F0.03 or F0.04 is selected as 8, this group of functions will work. (Please refer to function code F0.03-F0.04). This parameter determines the target quantity given channel of the process PID. The set target value of the process PID is a relative value, and the set 100% corresponds to 100% of the feedback signal of the controlled system; the PID range (F9.04) is not necessary, because no matter how much the range is set, the system will It is calculated by relative value (0~100%). However, if the PID range is set, the actual value of the signal corresponding to the PID setting and feedback can be visually observed through the keyboard display parameters.

F9.01PID digital settingDefault50.0%
Setting range0.0%~100.0%

When F9.00=0 is selected, the target source is keyboard setting. This parameter needs to be set. The reference value of this parameter is the feedback amount of the system.

F9.02PID feedback sourceDefault0
Setting range0AI1
1AI2
2Reserved
3AI1-AI2
4PULSE setting(DI6)
5Communication setting
6AI1+AI2
7MAX(|AI1|,|AI2|)
8MIN (|AI1|,|AI2|)

Use this parameter to select the PID feedback channel.

F9.03PID controlling directionDefault0
Setting range0Positive
1Negative

Positive effect: When the feedback signal is less than the PID setting, the inverter output frequency is required to increase in order to make the PID balance. Such as the tension PID control of winding.

Reverse effect: When the feedback signal is greater than the PID setting, the output frequency of the inverter is required to decrease in order to balance the PID. Such as unwinding tension PID control.

The effect of this function is affected by terminal function 35: PID direction.

F9.04PID setting feedback rangeDefault1000
Setting range0~65535PID given feedback range is a dimensionless unit. Used as the display of PID given and feedback.
F9.05Proportional gain P1Default20.0
Setting range0.0~100.0
F9.06Integral time I1Default2.00s
Setting range0.01s~10.00s
F9.07Differential time D1Default0.000s
Setting range0.00~10.000

Proportional gain P: determines the adjustment intensity of the entire PID regulator, the greater the P, the greater the adjustment intensity. The parameter of 100 means that when the deviation between the PID feedback amount and the given amount is 100%, the adjustment range of the PID regulator to the output frequency command is the maximum frequency (ignoring the integral effect and the derivative effect).

Integral time I: Decide how fast the PID regulator performs integral adjustment on the deviation between the PID feedback amount and the given amount. Integral time means that when the deviation between PID feedback quantity and given quantity is 100%, the integral regulator (ignoring proportional action and differential action) is continuously adjusted after this time, and the adjustment quantity reaches the maximum frequency (F0.09). The shorter the integration time, the greater the adjustment intensity.

Differential time D: determines the intensity of the PID regulator to adjust the rate of change of the deviation between the PID feedback quantity and the given quantity. Differential time means that if the feedback amount changes 100% within this time, the adjustment amount of the differential regulator is the maximum frequency (F0.09) (ignoring proportional action and integral action). The longer the derivative time, the greater the adjustment intensity.

F9.08PID reverse cut-off frequencyDefault0.00Hz
Setting range0.00~F0.10
F9.09PID deviation limitDefault0.01%
Setting range0. 0%~100.0%

Deviation limit: When the PID feedback deviation is within this range, PID stops adjusting;

F9.10PID differential limit rangeDefault0.10%
Setting range0.00%~100.00%
F9.11PID setting change timeDefault0.00s
Setting range0.00s~650.00s

PID given change time refers to the time required for the actual value of PID to change from 0.0% to 100.0%.

When the PID setting changes, the actual value of the PID setting will not respond immediately. Moreover, it changes linearly according to the given change time to prevent the given mutation from occurring.

F9.12PID feedback filtering timeDefault0.00s
Setting range0.00s~60.00s
F9.13PID output filtering timeDefault0.00s
Setting range0.00s~60.00s

Filter the PID feedback and output value to eliminate sudden changes.

F9.14Proportional gain P2Default20.0
Setting range0.0~100.0
F9.15Integral time I2Default2.00s
Setting range0.01s~10.00s
F9.16Differential time D2Default0.000s
Setting range0.00~10.000

The setting method is similar to F9.05, F9.06, F9.07. It is used in situations where PID parameter changes are required, see F9.18 introduction.

F9.17PID parameter switchover conditionDefault0
Setting range0No switchover
1DI terminal
2Automatic switchover based on deviation
F9.18PID parameter switchover deviation 1Default20.0%
Setting range0.0%~F9.20
F9.19PID parameter switchover deviation 2Default80.0%
Setting rangeF9.19~100.0%

In some applications, a set of PID parameters may not satisfy the entire running process. At this time, multiple groups of PID parameters may need to be switched.

When not switching, the PID parameter is constant as parameter group 1.

When the DI terminal is switched, the multi-function terminal function selection is 43: When the PID parameter switching terminal and the terminal is valid, the parameter group 2 is selected, otherwise, the parameter group 1 is selected.

To switch automatically according to the deviation, when the deviation between the reference and the feedback is less than the PID parameter switching deviation 1 (F9.19), use F9.05, F9.06, F9.07 as the PID adjustment parameters, and the deviation between the reference and the feedback When it is greater than PID switching deviation 2 (F9.20), use F9.15, F9.16, and F9.17 as PID adjustment parameters. The PID parameters of the deviation segment between the switching deviation 1 and the switching deviation 2 are two sets of PID parameters linear switching.

F9.20PID initial valueDefault0.0%
Setting range0.0%~100.0%
F9.21PID initial value holding timeDefault0.00s
Setting range0.00s~650.00s

When PID is running, the inverter will first run with PID initial value (F9.21) given output and the duration is F9.22 (PID initial value holding time), and then start normal PID adjustment.

F9.22Two output deviation forward maximum valueDefault1.00%.
Setting range0.00%~100.00%
F9.23Two output deviation reverse maximum valueDefault1.00%
Setting range0.00%~100.00%

This function code is used to limit the difference between the two beats (2ms/beat) of the PID output, so as to prevent the PID output from changing too fast. F9.23 and F9.24 respectively correspond to the maximum output deviation during forward and reverse rotation.

F9.24PID integral propertyDefault00
Setting rangeOnes PlaceIntegration separation
0Disabled
1Enabled
Tens PlaceOutput to limit value
0Continue the integral
1Stop the integral

Integration separation

When it is valid, if terminal function 22: integral pause is valid, the PID integral operation will stop. Only proportional and derivative are calculated.

Output to limit value

If it is to stop integration, when the PID output value reaches the maximum or minimum value, the PID integration stops calculating.

If it is continuous integration, the PID integration will be calculated at any time

F9.25Detection value of PID feedback lossDefault0.0%
Setting range

0.0%:No judging feedback loss

0.1%~100.0%

F9.26Detection time of PID feedback lossDefault0.0s
Setting range0.0s~20.0s

This function code is used to judge whether PID feedback is lost. When the PID feedback is less than the feedback loss detection value (F9.26) and the duration reaches F9.27 (feedback loss detection time), the inverter reports a fault and runs according to the fault handling method.

F9.27PID operation at stopDefault0
Setting range0No PID operation at stop
1PID operation at stop
F9.28PID function selectionDefault0
Setting range0Normal PID
1Sleep PID

0: The inverter runs under normal PID control and the sleep function is invalid.

1: The inverter runs under sleep PID control, and the sleep function is enabled.

F9.29PID sleep thresholdDefault60.0%
Setting range0.0%~100.0%
F9.30PID sleep delayDefault3.0s
Setting range0.0~3600s
F9.31PID wake-up thresholdDefault20.0%
Setting range0.0%~100.0%
F9.32PID wake-up time delayDefault3.0s
PID wake-up time delay0.0~3600s

When the sleep PID is selected, if the feedback is higher than the setting of F9.29 sleep threshold, the inverter will start the sleep timer. After the sleep delay time set by F9.30, if the feedback amount is still higher than the setting of F9.29 If the feedback is lower than the setting of the wake-up threshold of F9.31, the inverter will start the wake-up timer. After the time set by F9.32 wake-up delay, if the feedback If it is still lower than the set value of F9.31 wake-up threshold, the wake-up is successful and PID control is performed. Refer to Figure 6-22 below to understand the relationship between the above parameters.

CHAPTER 7 FUNCTIONAL PARAMETER DETAILS_html_229dff56f8f13b95.png

Figure 6-10-2 PID sleep and wake-up timing diagram

FA group faults & protection

FA.00Motor overload protection selectionDefault1
Setting range0Disabled
1Enabled

Choose 0: The inverter has no overload protection for the load motor, at this time the thermal relay shall be added in front of the motor;

Choose 1: At this time, the inverter has overload protection function for the motor. See FA.01 for protection value.

FA.01Motor overload protection gainDefault1.00
Setting range0.20~10.00

Motor overload protection is an inverse time curve; 220%×(FA.01)×motor rated current for 1 minute, 150%×(FA.01)×motor rated current for 60 minutes.

FA.02Motor overload warning coefficientDefault80%
Setting range50%~100%

The reference value of this value is the motor overload current. When the inverter detects that the output current reaches (FA.02) × motor overload current and continues for the specified time on the inverse time curve, it outputs a pre-alarm signal from DO or relay.

FA.03Overvoltage stall gainDefault10
Setting range0 (Invalid)~100

Adjust the inverter's ability to suppress overvoltage stall. The larger the value, the stronger the ability to suppress overvoltage.

For loads with small inertia, this value should be small, otherwise the dynamic response of the system will slow down.

For loads with large inertia, this value should be large, otherwise the suppression effect is not good, and overvoltage faults may occur.

FA.04Overvoltage stall protective voltageDefault130%
Setting range120%~150%(3 phase)

Select the protection point of the overvoltage stall function. When this value is exceeded, the inverter starts to perform the over-voltage stall protection function.

FA.05Overcurrent stall gainDefaultModel dependent
Setting range0~100 

Adjust the inverter's ability to suppress excessive stall speed. The larger the value, the stronger the ability to suppress overcurrent.

For loads with small inertia, this value should be small, otherwise the dynamic response of the system will slow down.

For loads with large inertia, this value should be large, otherwise the suppression effect is not good, and overcurrent faults may occur.

FA.06Overvoltage stall protective currentDefault150%
Setting range100%~200%

Select the current protection point for the over-current stall function. When this value is exceeded, the inverter starts to perform the overcurrent stall protection function.

FA.07Short-circuit to ground upon power-onDefault1
Setting range0Disabled
1Enabled

The inverter can be selected to detect whether the motor has a ground protection short-circuit fault when the inverter is powered on. If this function is valid, the inverter will output for a short time at the moment of power-on.

FA.08Fault auto reset timesDefault0
Setting range0~5

When the inverter selects automatic fault reset, it is used to set the number of times that can be reset automatically. If the value exceeds this value, the inverter will be on standby and waiting for repair.

FA.09Relay action during fault auto resetDefault0
Setting range0:Disabled; 1:Enabled

After selecting the inverter fault automatic reset function, during the execution of the fault reset, through this parameter setting, you can decide whether the fault relay is required to act, so as to shield the fault alarm caused by this and make the equipment continue to run.

FA.10Time interval of fault auto resetDefault1.0s
Setting range0.1s~100.0s

The waiting time for the inverter from the fault alarm to the automatic reset of the fault.

FA.11Input phase loss protectionDefaultModel dependent
Setting range

0:Disabled

1:Enabled

Choose whether to protect the input phase loss.

FA.12Output phase loss protectionDefault1
Setting range

0:Disabled

1:Enabled

Choose whether to protect the output phase loss.

FA.13Fault protection action selection 1Default00000
Setting rangeOnes PlaceMotor Overload(Err11)
0Free stopping
1Stop according to the stop mode
2Continue to run
Tens PlaceInput Phase Loss(Err12) (0~2,as ones place)
Hundr-eds PlaceOutput Phase Loss (Err13) (0~2,as ones place)
Thous-ands PlaceExternal Fault(Err15) (0~2,as ones place)
Ten thous-ands PlaceCommunication Fault(Err16) (0~2,as ones place)
FA.14ReservedDefault 
Setting rangeOnes PlaceReserved
0Reserved
1Reserved
2Reserved
Tens PlaceReserved
0Reserved
1Reserved
Hundr-eds PlaceReserved
Thous-ands PlaceReserved
Ten thous-ands PlaceReserved
FA.15Fault protection action selection 3Default00000
Setting rangeOnes PlaceUser-defined fault 1(Err27) (0~2,as ones place of FA.13)
Tens PlaceUser-defined fault 2(Err28) (0~2,as ones place of FA.13)
Hundreds PlacePowering on time reached(Err29) (0~2,as ones place of FA.13)
Thousands PlaceLoad loss(Err30)
0Free stopping
1Stop according to the stop mode
2Decelerate to 7% of the rated frequency of the motor and continue to run, and automatically return to the set frequency if the load is not lost
 Ten thousands Place

PID feedback loss during

Running (Err31) (0~2,as ones place of FA.13)

When “free stop” is selected: the inverter prompts Err** and stops directly.

When "Stop according to stop mode" is selected: the inverter prompts A** and stops according to the stop mode, and prompts ErrXX after stopping.

When “continue running” is selected: the inverter continues to run and prompts A**. For the running frequency, refer to the description of FA.20 and FA.21.

FA.16

Overcurrent stall Integral coefficient

Default500
Setting range1~2000

Set overcurrent stall Integral coefficient rate.

FA.17

Instant stop /no-stop mode 

Default

0

Setting range

0

General machine instant stop/no-stop 

1Spinning machine instant stop/no-stop

Set the mode of instant stop and no-stop.

FA.18Undervoltage settingDefault100.0%
Setting range60.0%~140.0%

Adjusting this parameter can adjust the voltage point at which the inverter reports undervoltage fault (Err09), and 100.0% corresponds to 350V.

FA.19Overvoltage settingDefault810.0V
Setting range200.0V ~ 2500.0V

Generally, this parameter is not adjusted after the inverter leaves the factory. If there is frequent overvoltage during operation, please consult the manufacturer's customer service department before making adjustments.

FA.20Continue running frequency selection during failureDefault0
Setting range0Run with the current run frequency
1Run with the setting frequency
2Run with the upper limit frequency
3Run with lower limit frequency.
4

Run with standby frequency when abnormal

(FA.21)

FA.21Abnormal standby frequency settingDefault100.0%(Current set frequency)
Setting range60.0%~100.0%

When a fault occurs during the operation of the inverter and the fault handling method is keep running, the inverter prompts A** and runs at the set frequency determined by this function.

FA.22Action selection at instantaneous power failureDefault0
Setting range0Invalid
1Stop as Deceleration time 1
2Stop as Deceleration time 2
FA.23Action pause judging voltage at instantaneous power failureDefault90.0%
Setting range80.0%~100.0%(Standard Bus Voltage)
FA.24Voltage rally judging time at instantaneous power failureDefault0.50s
Setting range0.00s~100.00s
FA.25Action judging voltage at instantaneous power failureDefault80.0%
Setting range60.0%~100.0%( Standard Bus Voltage)

This function means that the inverter will not stop when the power is cut instantaneously. In the case of an instantaneous power failure or a sudden voltage drop, the inverter will reduce its output speed, and compensate for the voltage drop by feeding back energy through the load to keep the inverter running in a short time.

If the instantaneous stop non-stop function selection is valid, when the bus voltage is lower than the voltage indicated by the instantaneous stop non-stop action judgment voltage (FA.25), the inverter will decelerate according to the instantaneous stop action selection. When the stop action judgment voltage (FA.25) represents the voltage, and the duration is maintained for the momentary stop and non-stop voltage rise judgment time (FA.24), the inverter resumes the set frequency operation; otherwise the inverter will continue to reduce the operating frequency to Stop at 0 o'clock. Instantaneous stop non-stop function if shown.

The deceleration time of instantaneous power failure is too long, the load feedback energy is small, and the low voltage can not be effectively compensated; the deceleration time is too short, the load feedback energy is large, which will cause overvoltage protection. Please adjust the deceleration time appropriately according to the load inertia and the weight of the load.

FA.26Loss of loads protection optionsDefault0
Setting range0Disabled
1Enabled
FA.27Loss of loads detection levelDefault10.0%
Setting range0.0%~100.0%(Motor rated current)
FA.28Loss of loads detection timeDefault1.0s
Setting range0.0s~60.0s

If this function is valid, when the inverter loses load, the inverter reports Err30 fault, and the output frequency is 7% of the rated frequency; if the load is restored, it will run at the set frequency. The off-load detection level and detection time can be set.

FA.29The decimal point of the frequency in failure stateDefault222
Setting rangeOnes PlaceThe third fault frequency decimal point
11 decimal point
22 decimal point
Tens PlaceThe second fault frequency decimal point (1~2,as ones place)
Hundreds PlaceThe first fault frequency decimal point (1~2,as ones place)

Since the frequency decimal point can be set, this function code is used to record the position of the decimal point of the frequency at the time of failure (for frequency display during failure).

Note: The function code display data is H.xxx, where H. means hexadecimal data.

FB group frequency swing, length fixing and counting

The swing frequency function is suitable for textile, chemical fiber and other industries and occasions that require traverse and winding functions.

Swing frequency function means that the output frequency of the inverter swings up and down around the set frequency (frequency command is selected by F0.07). The trajectory of the running frequency on the time axis is shown in the figure below, where the swing amplitude is determined by FB.00 and FB. 01 setting, when FB.01 is set to 0, that is, the swing amplitude is 0, and the swing frequency has no effect.

CHAPTER 7 FUNCTIONAL PARAMETER DETAILS_html_1c70827204f62468.png

Figure 6-12-1 Schematic diagram of swing frequency work

FB.00Swing frequency setting modeDefault0
Setting range0Relative to the central frequency
1Relative to the maximum frequency

Use this parameter to determine the reference amount of swing.

0: Relative to the center frequency (F0.07 frequency source selection), a variable swing amplitude system. The swing amplitude changes with the center frequency (set frequency).

1: Relative to the maximum frequency (F0.10 maximum output frequency), it is a fixed swing amplitude system.

FB.01Swing frequency amplitudeDefault0.0%
Setting range0.0%~100.0%
FB.02Jump frequency amplitudeDefault0.0%
Setting range0.0%~50.0%

Use this parameter to determine the swing amplitude and kick frequency. The swing frequency operation frequency is restricted by the upper and lower limit frequencies.

The swing amplitude is relative to the center frequency (variable swing amplitude, select FB.00=0): swing amplitude AW = frequency source F0.07 × swing amplitude FB.01.

The swing amplitude is relative to the maximum frequency (fixed swing amplitude, select FB.00=1): swing amplitude AW = maximum frequency F0.10× swing amplitude FB.01.

Kick frequency = swing amplitude AW × sudden jump frequency amplitude FB.02. That is, when the swing frequency is running, the value of the kick frequency relative to the swing amplitude.

If the swing amplitude is relative to the center frequency (variable swing amplitude, select FB.00=0), the kick frequency is the variable value.

If the swing amplitude is relative to the maximum frequency (fixed swing amplitude, select FB.00=1), the kick frequency is a fixed value.

FB.03Swing frequency cycleDefault10.0s
Setting range0.0s~3000.0s
FB.04Triangular wave rising time coefficientDefault50.0%
Setting range0.0%~100.0%

Swing frequency cycle: the time value of a complete swing frequency cycle. FB.04 triangle wave rise time coefficient is relative to FB.03 swing frequency period.

Triangular wave rise time = swing frequency period FB.03 × triangular wave rise time coefficient FB.04 (unit: s)

Triangular wave falling time = swing frequency period FB.03 × (1-triangular wave rising time coefficient FB.04) (unit: s)

FB.05Setting lengthDefault1000m
Setting range0m~65535m
FB.06Actual lengthDefault0m
Setting range0m~65535m
FB.07Number of pulses per meterDefault100.0
Setting range0.1~6553.5

The three function codes of set length, actual length and number of pulses per m are mainly used for fixed length control. The length is calculated by the pulse signal input from the digital input terminal, and the corresponding input terminal needs to be set as the length counting input terminal. Generally, when the pulse frequency is high, DI5 input is required.

Actual length = length count input pulse number / pulse number per m

When the actual length FB.06 exceeds the set length FB.05, the multi-function digital output terminal "length reach terminal" will output ON signal (please refer to F1.04 function code)

FB.08Set count valueDefault1000
Setting range1~65535
FB.09Designated count valueDefault1000
Setting range1~65535

The count value is counted by inputting the pulse signal from the counter input terminal in the multi-function switch input terminal.

When the count value reaches the set count value, the switch output terminal outputs a signal that the set count value has reached. The counter stops counting.

When the count value reaches the designated count value, the switch output terminal outputs a signal that the designated count value has reached. The counter continues to count and stops at the "set count value".

The designated count value FB.09 should not be greater than the set count value FB.08.

This function is as below:

CHAPTER 7 FUNCTIONAL PARAMETER DETAILS_html_3afe609068e8ab4b.png

Figure 6-12-2 Schematic diagram of set count value given and designated count value given

FC group communication parameters

FC.00Local addressDefault1
Setting range00~247

When the local address is set to 0, it is the broadcast address, which realizes the broadcast function of the host computer. The address of this machine is unique (except the broadcast address), which is the basis for the point-to-point communication between the host computer and the inverter.

FC.01Baud RateDefault5
Setting range0300 bps
1600 bps
21200 bps
32400 bps
44800 bps
59600 bps
619200 bps
738400 bps

This parameter is used to set the data transmission rate between the host computer and the inverter. Note that the baud rate set by the host computer and the inverter must be consistent, otherwise, the communication cannot be carried out. The greater the baud rate, the faster the communication speed.

FC.02Data formatDefault3
Setting range0No check, data format <8,N,2>
1Even parity check, data format <8,E,1>
2Odd Parity check, data format <8,0,1>
3No check, data format <8,N,1>

The data format set by the host computer and the inverter must be same, otherwise, the communication cannot be carried out.

FC.03Response delayDefault2ms
Setting range0~20ms

Response delay: refers to the intermediate time between the end of the inverter data receiving and the sending of data to the upper computer. If the response delay is less than the system processing time, the response delay is based on the system processing time. If the response delay is longer than the system processing time, the system will wait after processing the data until the response delay time expires before going to the upper computer. send data.

FC.04Communication timeoutDefault0.0 s
Setting range0.0 s(Invalid),0.1~60.0s

When the function code is set to 0.0 s, the communication timeout time parameter is invalid.

When the function code is set to a valid value, if the interval between one communication and the next communication exceeds the communication timeout time, the system will report a communication failure error (Err16). Under normal circumstances, it is set to invalid. If you set the secondary parameters in a continuous communication system, you can monitor the communication status.

FC.05Communication reading current resolutionDefault0
Setting range00.01A
10.1A

Used to determine the output unit of the current value when the communication reads the output current.

FD group muti-stage speed and simple plc functions

The simple PLC function is that the inverter has a programmable controller (PLC) built in to complete automatic control of multi-segment frequency logic. The running time, running direction and running frequency can be set to meet the technological requirements. This series of inverters can realize 16-speed change control, and there are 4 kinds of acceleration and deceleration time for selection. When the set PLC completes a cycle, an ON signal can be output from the multifunctional digital output terminals DO1 and DO2 or multifunctional relay 1 and relay 2. See F1.02~F1.05 for details. When the frequency source selection F0.07, F0.03, F0.04 is determined as the multi-speed operation mode, it is necessary to set FD.00~FD.15 to determine its characteristics.

FD.00Multistage Speed0Default0.0%
Setting range-100.0%~100.0%; 100.0% for maximum frequency (F0.10)
FD.01Multistage Speed1Default0.0%
Setting range-100.0%~100.0%
FD.02Multistage Speed2Default0.0%
Setting range-100.0%~100.0%
FD.03Multistage Speed3Default0.0%
Setting range-100.0%~100.0%
FD.04Multistage Speed4Default0.0%
Setting range-100.0%~100.0%
FD.05Multistage Speed5Default0.0%
Setting range-100.0%~100.0%
FD.06Multistage Speed6Default0.0%
Setting range-100.0%~100.0%
FD.07Multistage Speed7Default0.0%
Setting range-100.0%~100.0%
FD.08Multistage Speed8Default0.0%
Setting range-100.0%~100.0%
FD.09Multistage Speed9Default0.0%
Setting range-100.0%~100.0%
FD.10Multistage Speed10Default0.0Hz
Setting range-100.0%~100.0%
FD.11Multistage Speed11Default0.0%
Setting range-100.0%~100.0%
FD.12Multistage Speed12Default0.0%
Setting range-100.0%~100.0%
FD.13Multistage Speed13Default0.0%
Setting range-100.0%~100.0%
FD.14Multistage Speed14Default0.0%
Setting range-100.0%~100.0%
FD.15Multistage Speed15Default0.0%
Setting range-100.0%~100.0%

When the frequency source parameters F0.07, F0.03, F0.04 are determined to be the PLC operation mode, you need to set FD.00 ~ FD.15, FD.16, FD.17, FD.18 ~ FD.49 to determine them. characteristic.

Note: The symbols of FD.00~FD.15 determine the running direction of the simple PLC. If it is negative, it means running in the reverse direction.

Simple PLC schematic diagram:

FD.16Simple PLC running modeDefault0
Setting range0Stop after the AC Drive runs one cycle
1Keep final values after the AC Drive runs one cycle(running frequency)
2Repeat after the AC Drive runs one cycle
FD.17Simple PLC retentive selectionDefault00
Setting rangeOnes place(Retentive upon power failure)
0No
1Yes
Tens place(Retentive upon stop)
0No
1Yes

PLC operation mode

0: Stop after the AC Drive runs one cycle

After the inverter completes a single cycle, it stops automatically, and it needs to be given a run command again to start.

1: Keep final values after the AC Drive runs one cycle(running frequency)

After the inverter completes a single cycle, it automatically maintains the operating frequency and direction of the last segment.

2: Repeat after the AC Drive runs one cycle

After the inverter completes one cycle, it will automatically start the next cycle until the system stops when there is a stop command.

3: Retentive upon power failure

PLC power-down memory refers to memorizing the operation stage and frequency of PLC before power-off.

4: Retentive upon stop

PLC stop memory is to record the previous PLC running stage and running frequency when stopping.

FD.18Running time of simple PLC reference 0Default0.0s(h)
Setting range0.0s(h)~6553.5s(h)
FD.19Acceleration/deceleration time of simple PLC reference 0Default0
Setting range0~3
FD.20Running time of simple PLC reference 1Default0.0s(h)
Setting range0.0s(h)~6553.5s(h)
FD.21Acceleration/deceleration time of simple PLC reference 1Default0
Setting range0~3
FD.22Running time of simple PLC reference 2Default0.0s(h)
Setting range0.0s(h)~6553.5s(h)
FD.23Acceleration/deceleration time of simple PLC reference 2Default0
Setting range0~3
FD.24Running time of simple PLC reference 3Default0.0s(h)
Setting range0.0s(h)~6553.5s(h)
FD.25Acceleration/deceleration time of simple PLC reference 3Default0
Setting range0~3
FD.26Running time of simple PLC reference 4Default0.0s(h)
Setting range0.0s(h)~6553.5s(h)
FD.27Acceleration/deceleration time of simple PLC reference 4Default0
Setting range0~3
FD.28Running time of simple PLC reference 5Default0.0s(h)
Setting range0.0s(h)~6553.5s(h)
FD.29Acceleration/deceleration time of simple PLC reference 5Default0
Setting range0~3
FD.30Running time of simple PLC reference 6Default0.0s(h)
Setting range0.0s(h)~6553.5s(h)
FD.31Acceleration/deceleration time of simple PLC reference 6Default0
Setting range0~3
FD.32Running time of simple PLC reference 7Default0.0s(h)
Setting range0.0s(h)~6553.5s(h)
FD.33Acceleration/deceleration time of simple PLC reference 7Default0
Setting range0~3
FD.34Running time of simple PLC reference 8Default0.0s(h)
Setting range0.0s(h)~6553.5s(h)
FD.35Acceleration/deceleration time of simple PLC reference 8Default0
Setting range0~3
FD.36Running time of simple PLC reference 9Default0.0s(h)
Setting range0.0s(h)~6553.5s(h)
FD.37Acceleration/deceleration time of simple PLC reference 9Default0
Setting range0~3
FD.38Running time of simple PLC reference 10Default0.0s(h)
Setting range0.0 s(h)~6553.5s(h)
FD.39Acceleration/deceleration time of simple PLC reference 10Default0
Setting range0~3
FD.40Running time of simple PLC reference 11Default0.0s(h)
Setting range0.0s(h)~6553.5s(h)
FD.41Acceleration/deceleration time of simple PLC reference 11Default0
Setting range0~3
FD.42Running time of simple PLC reference 12Default0.0s(h)
Setting range0.0s(h)~6553.5s(h)
FD.43Acceleration/deceleration time of simple PLC reference 12Default0
Setting range0~3
FD.44Running time of simple PLC reference 13Default0.0s(h)
Setting range0.0s(h)~6553.5s(h)
FD.45Acceleration/deceleration time of simple PLC reference 13Default0
Setting range0~3
FD.46Running time of simple PLC reference 14Default0.0s(h)
Setting range0.0s(h)~6553.5s(h)
FD.47Acceleration/deceleration time of simple PLC reference 14Default0
Setting range0~3
FD.48Running time of simple PLC reference 15Default0.0s(h)
Setting range0.0s(h)~6553.5s(h)
FD.49Acceleration/deceleration time of simple PLC reference 15Default0
Setting range0~3
FD.50Time unit of simple PLC runningDefault0
Setting range0s:second
1h:hour
2min:minute
FD.51The source of multistage speed 0Default0
Setting range0Set by FD.00
1AI1
2AI2
3Reserved
4Reserved
5PID
6Set by preset frequency (F0.08)

This parameter determines the target quantity given channel of multi-speed 0.

FE group user password management

FE.00User passwordDefault0
Setting range0~65535

Set to any non-zero number, the password protection function will take effect.

00000: Clear the previously set user password value and disable the password protection function.

When the user password is set and effective, when entering the parameter setting state again, if the user password is incorrect, you can only view the parameters, but

cannot modify the parameters. Please keep in mind the user password. If you accidentally set it by mistake or forget it, please contact the manufacturer.

FE.01Fault record display timesDefault5
Setting range0~15

This function code is used to set the number of displaying fault records.