Last modified by Theodore Xu on 2025/02/21 14:13

From version 11.1
edited by Theodore Xu
on 2023/08/23 15:12
Change comment: There is no comment for this version
To version 10.1
edited by Theodore Xu
on 2023/07/11 16:30
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -2326,19 +2326,20 @@
2326 2326  When “continue running” is selected: the inverter continues to run and prompts A~*~*. For the running frequency, refer to the description of FA.20 and FA.21.
2327 2327  
2328 2328  (% class="table-bordered" %)
2329 -|(% rowspan="3" %)(((
2329 +|(% rowspan="2" %)(((
2330 2330  FA.17
2331 -)))|(% colspan="2" rowspan="1" %)Instant stop /no-stop mode |(((
2331 +)))|(((
2332 +Undervoltage setting
2333 +)))|(((
2332 2332  Default
2333 2333  )))|(((
2334 -0
2336 +100.0%
2335 2335  )))
2336 -|(% colspan="1" rowspan="2" %)(((
2338 +|(((
2337 2337  Setting range
2338 -)))|(% rowspan="1" %)0|(% colspan="2" rowspan="1" %)(((
2339 -General machine instant stop/no-stop
2340 +)))|(% colspan="2" rowspan="1" %)(((
2341 +60.0%~~140.0%
2340 2340  )))
2341 -|1|(% colspan="2" %)Spinning machine instant stop/no-stop
2342 2342  
2343 2343  Instantaneous power failure mode selection
2344 2344