Changes for page 08 Function parameter details
Last modified by Theodore Xu on 2025/02/21 14:13
From version 13.1
edited by Theodore Xu
on 2023/08/23 15:15
on 2023/08/23 15:15
Change comment:
There is no comment for this version
To version 10.1
edited by Theodore Xu
on 2023/07/11 16:30
on 2023/07/11 16:30
Change comment:
There is no comment for this version
Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -2326,21 +2326,22 @@ 2326 2326 When “continue running” is selected: the inverter continues to run and prompts A~*~*. For the running frequency, refer to the description of FA.20 and FA.21. 2327 2327 2328 2328 (% class="table-bordered" %) 2329 -|(% rowspan="3" %)((( 2330 -**FA.17** 2331 -)))|(% colspan="2" rowspan="1" %)Instant stop /no-stop mode |((( 2329 +|(% rowspan="2" %)((( 2330 +FA.17 2331 +)))|((( 2332 +Undervoltage setting 2333 +)))|((( 2332 2332 Default 2333 2333 )))|((( 2334 -0 2336 +100.0% 2335 2335 ))) 2336 -|( % colspan="1" rowspan="2" %)(((2338 +|((( 2337 2337 Setting range 2338 -)))|(% rowspan="1" %)0|(%colspan="2" rowspan="1" %)(((2339 - General machine instant stop/no-stop2340 +)))|(% colspan="2" rowspan="1" %)((( 2341 +60.0%~~140.0% 2340 2340 ))) 2341 -|1|(% colspan="2" %)Spinning machine instant stop/no-stop 2342 2342 2343 - Sethemodeofinstantstop andno-stop.2344 +Instantaneous power failure mode selection 2344 2344 2345 2345 (% class="table-bordered" %) 2346 2346 |(% rowspan="2" %)**FA.18**|Undervoltage setting|Default|100.0%