... ... @@ -54,7 +54,7 @@
54 54  |2|(% colspan="2" %)AI1
55 55  |3|(% colspan="2" %)AI2
56 56  |4|(% colspan="2" %)Reserved
57 -|5|(% colspan="2" %)PULSE setting DI6(Reserved)
57 +|5|(% colspan="2" %)PULSE setting DI6
58 58  |6|(% colspan="2" %)Multi-stage speed setting
59 59  |7|(% colspan="2" %)Simple PLC
60 60  |8|(% colspan="2" %)PID
... ... @@ -257,12 +257,12 @@
257 257  
258 258  Select the running state of the AC drive when the set frequency is lower than the lower limit frequency. In order to prevent the motor from running at low speed for a long time, this function can be used to choose to stop.
259 259  
260 +== Carrier frequency ==
261 +
260 260  (% class="table-bordered" %)
261 261  |(% rowspan="2" style="width:139px" %)** F0.16**|(% style="width:680px" %)Carrier Frequency|(% style="width:429px" %)Default|(% style="width:204px" %)Model Dependent
262 262  |(% style="width:680px" %)Setting Range|(% colspan="2" style="width:633px" %)0.5kHz~~16.0kHz
263 263  
264 -= Carrier frequency =
265 -
266 266  This function adjusts the carrier frequency of the AC drive. By adjusting the carrier frequency, the motor noise can be reduced, the resonance point of the mechanical system can be avoided, the leakage current of the line to the ground and the interference caused by the inverter can be reduced.
267 267  
268 268  When the carrier frequency is low, the higher harmonic components of the output current increase, the motor loss increases, and the motor temperature rise increases.