... ... @@ -1,1 +1,1 @@ 1 - 8Function parameter details1 +2.7 Function parameter details - Author
-
... ... @@ -1,1 +1,1 @@ 1 -XWiki. Jim1 +XWiki.admin - Content
-
... ... @@ -1,4 +1,4 @@ 1 -= 1 F0 group basic parameters = 1 += 6.1 F0 group basic parameters = 2 2 3 3 (% class="table-bordered" %) 4 4 |(% rowspan="3" %)**F0.00**|(% colspan="2" %)Motor control mode|Default|0 ... ... @@ -59,13 +59,13 @@ 59 59 60 60 Select the main source of the AC drive’s input frequency. There are 10 main frequency sources: 61 61 62 - **0:**Digital setting (non-retentive at power failure)62 +0: Digital setting (non-retentive at power failure) 63 63 64 64 The initial value is 0. The frequency can be increased or decreased by the pulse knob, and the set frequency value of the inverter can be changed by the ▲/▼ keys of the keyboard (or UP and DOWN of the multi-function input terminals). 65 65 66 66 Non-retentive means that after the AC drive is powered off, the set frequency value will be restored to 0; it will be cleared after switching as the frequency source, so this parameter should not be the object of frequency source switching. 67 67 68 - **1:**Digital setting (retentive at power failure)68 +1: Digital setting (retentive at power failure) 69 69 70 70 The initial value is the value of F0.08 "Keypad setting frequency". 71 71 ... ... @@ -73,33 +73,27 @@ 73 73 74 74 Retentive means that when the AC drive is powered on again after power failure, the set frequency is the value before the last power failure (note that it is used in conjunction with F0.23). 75 75 76 - **2:**AI176 +2: AI1 77 77 78 - **3:**AI278 +3: AI2 79 79 80 80 Means that the frequency is determined by the analog input terminal. The standard unit provides 2 analog input terminals (AI1, AI2), among which AI1 is 0V~~10V voltage input, AI2 can be 0V~~10V voltage input, or 4mA~~20mA current input, Selected by jumper J8 on the control board. 81 81 82 - **4/5:**PULSE setting(Reserved)82 +4/5: Reserved 83 83 84 - Theset frequencyisivenby the terminal pulse.84 +6: Multi-stage speed 85 85 86 -Pulse given signal specifications: voltage range 9V~~30V, frequency range 0kHz~~100kHz. 87 - 88 -Note: Pulse reference can only be input from the multi-function input terminal, __**requires custom control board development.**__ 89 - 90 -**6: **Multi-stage speed 91 - 92 92 Select multi-stage speed operation mode. Need to set the F5 group "input terminals" and FD group "multi-stage speed and PLC" parameters to determine the corresponding relationship between the given signal and the given frequency. 93 93 94 - **7:**Simple PLC88 +7: Simple PLC 95 95 96 96 Select simple PLC mode. When the frequency source is simple PLC, you need to set the FD group "multi-speed and PLC" parameters to determine the set frequency. 97 97 98 - **8:**PID92 +8: PID 99 99 100 100 Select process PID control. At this time, you need to set the F9 group "PID function of process control ". The running frequency of the inverter is the frequency value after PID action. For the meaning of PID given source, given amount, feedback source, etc., please refer to the introduction of "PID Function of process control" in F9 group. 101 101 102 - **9:**Communication setting96 +9: Communication setting 103 103 104 104 Means that the main frequency source is given by the upper machine through communication. 105 105 ... ... @@ -387,7 +387,7 @@ 387 387 388 388 The decimal place of the control frequency related instruction, the default is 2 decimal places. After the parameter is set, the decimal place of the parameter associated with the frequency is automatically adjusted. This parameter is not affected by F0.20. 389 389 390 -= 2 F1 group start & stop control = 384 += 6.2 F1 group start & stop control = 391 391 392 392 (% class="table-bordered" %) 393 393 |(% rowspan="4" %)**F1.00**|(% colspan="2" %)Starting mode|Default|0 ... ... @@ -547,7 +547,7 @@ 547 547 548 548 Setting whether the AC drive has output when running frequency is 0 549 549 550 -= 3 F2 group motor parameters = 544 += 6.3 F2 group motor parameters = 551 551 552 552 (% class="table-bordered" %) 553 553 |(% rowspan="5" %)**F2.00**|(% colspan="2" %)Motor type selection|Default|0 ... ... @@ -660,7 +660,7 @@ 660 660 661 661 The main and auxiliary winding currents can be changed by adjusting the single-phase motor turns ratio. Generally, reducing the single-phase motor turns ratio can increase the main winding current, reduce the auxiliary winding current, and reduce the motor heating (only effective when F2.00 = 3) . 662 662 663 -= 4 F3 group vector control parameters = 657 += 6.4 F3 group vector control parameters = 664 664 665 665 F3 group function codes are only valid in vector control mode, that is, it is valid when F0.00=0, and it is invalid when F0.00=1. 666 666 ... ... @@ -797,7 +797,7 @@ 797 797 798 798 During startup, torque command 1 = F3.11 * F3.24 / 100; after maintaining time F3.25 seconds, it will be restored to torque command 2 = F3.11; torque command 1/2 switching requires torque acceleration and deceleration time F3.14/F3.15. 799 799 800 -= 5 F4 group v/f control parameters = 794 += 6.5 F4 group v/f control parameters = 801 801 802 802 This group of function codes is only valid for V/F control (F0.00=1), and invalid for vector control. 803 803 ... ... @@ -966,7 +966,7 @@ 966 966 967 967 According to the actual use, select the situation where the AVR function is enabled. 968 968 969 -= 6 F5 group input terminals = 963 += 6.6 F5 group input terminals = 970 970 971 971 The standard unit of the VB series inverter has 6 multi-function digital input terminals and 2 analog input terminals. 972 972 ... ... @@ -1101,7 +1101,7 @@ 1101 1101 1102 1102 0: Two-line mode 1: This mode is the most commonly used two-line mode. The FWD and REV terminal commands determine the forward and reverse of the motor. 1103 1103 1104 -1: Two-wire mode 2: FWDis the enable terminal when using this mode. The direction is determined by the state of theREV.1098 +1: Two-wire mode 2: REV is the enable terminal when using this mode. The direction is determined by the state of the FWD. 1105 1105 1106 1106 2: Three-line mode 1: This mode Din is the enable terminal, and the direction is controlled by FWD and REV respectively. 1107 1107 ... ... @@ -1157,6 +1157,20 @@ 1157 1157 The function of AI2 is similar to the setting method of AI1. 1158 1158 1159 1159 (% class="table-bordered" %) 1154 +|(% rowspan="2" %)**F5.28**|PULSE INPUT minimum input|Default|0.00kHz 1155 +|Setting range|(% colspan="2" %)0.00kHz~~F5.30 1156 +|(% rowspan="2" %)**F5.29**|Percentage rate of PULSE INPUT minimum input|Default|0.0% 1157 +|Setting range|(% colspan="2" %)-100.00%~~100.0% 1158 +|(% rowspan="2" %)**F5.30**|PULSE INPUT maximum input|Default|50.00kHz 1159 +|Setting range|(% colspan="2" %)F5.28~~50.00kHz 1160 +|(% rowspan="2" %)**F5.31**|Percentage rate of PULSE INPUT maximum input|Default|100.0% 1161 +|Setting range|(% colspan="2" %)-100.00%~~100.0% 1162 +|(% rowspan="2" %)**F5.32**|PULSE INPUT filter time|Default|0.10s 1163 +|Setting range|(% colspan="2" %)0.00s~~10.00s 1164 + 1165 +This group of function codes defines the corresponding relationship when pulse is used as the frequency setting method. Pulse frequency input can only be input through DI6 channel. The application of this group of functions is similar to that of AI1. 1166 + 1167 +(% class="table-bordered" %) 1160 1160 |(% rowspan="2" %)**F5.33**|DI1 enable delay time|Default|0.0s 1161 1161 |Setting range|(% colspan="2" %)0.0s~~3600.0s 1162 1162 |(% rowspan="2" %)**F5.34**|DI1 disable delay time|Default|0.0s ... ... @@ -1194,7 +1194,7 @@ 1194 1194 1195 1195 Low Level:The connection between DI terminal and COM is invalid, while disconnection is valid. 1196 1196 1197 -= 7 F6 group output terminals = 1205 += 6.7 F6 group output terminals = 1198 1198 1199 1199 The standard unit of VB series inverter has 2 multi-function relay output terminals, 1 FM terminal and 2 multi-function analog output terminals. 1200 1200 ... ... @@ -1448,14 +1448,8 @@ 1448 1448 1449 1449 For the second output, the parameter setting method is the same as F6.28~~F6.32. 1450 1450 1451 -(% class="table-bordered" %) 1452 -|(% rowspan="2" %)**F6.38**|The setting time of timer|Default|0 1453 -|Setting range|(% colspan="3" %)0.00s~~100.0s 1459 += 6.8 F7 group keypad display = 1454 1454 1455 -Set the timer setting time 1456 - 1457 -= 8 F7 group keypad display = 1458 - 1459 1459 (% class="table-bordered" %) 1460 1460 |(% rowspan="4" %)**F7.00**|(% colspan="2" %)LCD keypad parameter copy|Default|0 1461 1461 |(% rowspan="3" %)Setting range|0|(% colspan="2" %)No operation ... ... @@ -1665,7 +1665,7 @@ 1665 1665 |(% rowspan="2" %)**F7.15**|Performance software version|Default|- 1666 1666 |Setting range|(% colspan="2" %)- 1667 1667 1668 -= 9 F8 group auxiliary functions = 1670 += 6.9 F8 group auxiliary functions = 1669 1669 1670 1670 (% class="table-bordered" %) 1671 1671 |(% rowspan="2" %)**F8.00**|JOG running frequency|Default|2.00Hz ... ... @@ -1965,7 +1965,7 @@ 1965 1965 1966 1966 Enabling the fast current limiting function can minimize the inverter's overcurrent fault and protect the inverter from uninterrupted operation. After entering the fast current-limiting state for a period of time, a fast current-limiting fault (Err40) will be reported, indicating that the inverter is overloaded. Please refer to the handling of Err10. 1967 1967 1968 -= 10 F9 group pid function of process control = 1970 += 6.10 F9 group pid function of process control = 1969 1969 1970 1970 PID control is a common method used in process control. It adjusts the output frequency of the inverter by performing proportional, integral, and differential calculations on the difference between the feedback signal of the controlled quantity and the target quantity signal to form a negative feedback system. The controlled amount is stable at the target amount. It is suitable for process control such as flow control, pressure control and temperature control. The basic control block diagram is as follows: 1971 1971 ... ... @@ -2167,8 +2167,9 @@ 2167 2167 2168 2168 Figure 6-10-2 PID sleep and wake-up timing diagram 2169 2169 2170 -= 11 FA group faults & protection = 2171 2171 2173 += 6.11 FA group faults & protection = 2174 + 2172 2172 (% class="table-bordered" %) 2173 2173 |(% rowspan="3" %)**FA.00**|Motor overload protection selection|Default|1 2174 2174 |(% rowspan="2" %)Setting range|0|Disabled ... ... @@ -2401,7 +2401,7 @@ 2401 2401 2402 2402 Note: The function code display data is H.xxx, where H. means hexadecimal data. 2403 2403 2404 -= 12 FB group frequency swing, length fixing and counting = 2407 += 6.12 FB group frequency swing, length fixing and counting = 2405 2405 2406 2406 The swing frequency function is suitable for textile, chemical fiber and other industries and occasions that require traverse and winding functions. 2407 2407 ... ... @@ -2488,7 +2488,7 @@ 2488 2488 2489 2489 Figure 6-12-2 Schematic diagram of set count value given and designated count value given 2490 2490 2491 -= 13 FC group communication parameters = 2494 += 6.13 FC group communication parameters = 2492 2492 2493 2493 (% class="table-bordered" %) 2494 2494 |(% rowspan="2" %)**FC.00**|Local address|Default|1 ... ... @@ -2539,7 +2539,7 @@ 2539 2539 2540 2540 Used to determine the output unit of the current value when the communication reads the output current. 2541 2541 2542 -= 14 FD group muti-stage speed and simple plc functions = 2545 += 6.14 FD group muti-stage speed and simple plc functions = 2543 2543 2544 2544 The simple PLC function is that the inverter has a programmable controller (PLC) built in to complete automatic control of multi-segment frequency logic. The running time, running direction and running frequency can be set to meet the technological requirements. This series of inverters can realize 16-speed change control, and there are 4 kinds of acceleration and deceleration time for selection. When the set PLC completes a cycle, an ON signal can be output from the multifunctional digital output terminals DO1 and DO2 or multifunctional relay 1 and relay 2. See F1.02~~F1.05 for details. When the frequency source selection F0.07, F0.03, F0.04 is determined as the multi-speed operation mode, it is necessary to set FD.00~~FD.15 to determine its characteristics. 2545 2545 ... ... @@ -2698,7 +2698,7 @@ 2698 2698 2699 2699 This parameter determines the target quantity given channel of multi-speed 0. 2700 2700 2701 -= 15 FE group user password management = 2704 += 6.15 FE group user password management = 2702 2702 2703 2703 (% class="table-bordered" %) 2704 2704 |(% rowspan="2" %)**FE.00**|User password|Default|0