... ... @@ -51,7 +51,7 @@
51 51  |2|(% colspan="2" %)AI1
52 52  |3|(% colspan="2" %)AI2
53 53  |4|(% colspan="2" %)Reserved
54 -|5|(% colspan="2" %)PULSE setting(Reserved
54 +|5|(% colspan="2" %)Reserved
55 55  |6|(% colspan="2" %)Multi-stage speed setting
56 56  |7|(% colspan="2" %)Simple PLC
57 57  |8|(% colspan="2" %)PID
... ... @@ -79,7 +79,7 @@
79 79  
80 80  Means that the frequency is determined by the analog input terminal. The standard unit provides 2 analog input terminals (AI1, AI2), among which AI1 is 0V~~10V voltage input, AI2 can be 0V~~10V voltage input, or 4mA~~20mA current input, Selected by jumper J8 on the control board.
81 81  
82 -**5: **PULSE setting(Reserved)
82 +**4/5: **PULSE setting(Reserved)
83 83  
84 84  The set frequency is given by the terminal pulse.
85 85  
... ... @@ -1101,27 +1101,18 @@
1101 1101  
1102 1102  0: Two-line mode 1: This mode is the most commonly used two-line mode. The FWD and REV terminal commands determine the forward and reverse of the motor.
1103 1103  
1104 -[[image:1681697850903-377.png||height="282" width="633"]]
1105 -
1106 1106  1: Two-wire mode 2: FWD is the enable terminal when using this mode. The direction is determined by the state of the REV.
1107 1107  
1108 -[[image:1681697969422-504.png]]
1106 +2: Three-line mode 1: This mode Din is the enable terminal, and the direction is controlled by FWD and REV respectively.
1109 1109  
1110 -2: Three-line mode 1: This mode Din(function code 3) is the enable terminal, and the direction is controlled by FWD and REV respectively.
1108 +But the pulse is valid, it must be completed by disconnecting the Din terminal signal when stopping.
1111 1111  
1112 -DIN is pulse effective, user need to disconnect the Din terminal signal when stop.
1113 -
1114 1114  Din is the multifunctional input terminal of DI1~~DI6. At this time, the corresponding terminal function should be defined as the No. 3 function "three-wire operation control".
1115 1115  
1116 -[[image:1681698530367-261.png||height="298" width="628"]]
1117 -
1118 1118  3: Three-line mode 2: The enable terminal of this mode is Din, the running command is given by FWD, and the direction is determined by the state of REV. The stop command is completed by disconnecting the Din signal.
1119 1119  
1120 1120  Din is the multi-function input terminal of DI1~~DI6. At this time, the corresponding terminal function should be defined as the No. 3 function "three-wire operation control".
1121 1121  
1122 -[[image:1681698557086-403.png||height="267" width="625"]]
1123 -
1124 -
1125 1125  (% class="table-bordered" %)
1126 1126  |(% rowspan="2" %)**F5.17**|UP/DOWN change rate range|Default|0.50Hz
1127 1127  |Setting range|(% colspan="2" %)0.01Hz~~65.535Hz
... ... @@ -1166,6 +1166,20 @@
1166 1166  The function of AI2 is similar to the setting method of AI1.
1167 1167  
1168 1168  (% class="table-bordered" %)
1160 +|(% rowspan="2" %)**F5.28**|PULSE INPUT minimum input|Default|0.00kHz
1161 +|Setting range|(% colspan="2" %)0.00kHz~~F5.30 
1162 +|(% rowspan="2" %)**F5.29**|Percentage rate of PULSE INPUT minimum input|Default|0.0%
1163 +|Setting range|(% colspan="2" %)-100.00%~~100.0%
1164 +|(% rowspan="2" %)**F5.30**|PULSE INPUT maximum input|Default|50.00kHz
1165 +|Setting range|(% colspan="2" %)F5.28~~50.00kHz  
1166 +|(% rowspan="2" %)**F5.31**|Percentage rate of PULSE INPUT maximum input|Default|100.0%
1167 +|Setting range|(% colspan="2" %)-100.00%~~100.0%
1168 +|(% rowspan="2" %)**F5.32**|PULSE INPUT filter time|Default|0.10s
1169 +|Setting range|(% colspan="2" %)0.00s~~10.00s
1170 +
1171 +This group of function codes defines the corresponding relationship when pulse is used as the frequency setting method. Pulse frequency input can only be input through DI6 channel. The application of this group of functions is similar to that of AI1.
1172 +
1173 +(% class="table-bordered" %)
1169 1169  |(% rowspan="2" %)**F5.33**|DI1 enable delay time|Default|0.0s
1170 1170  |Setting range|(% colspan="2" %)0.0s~~3600.0s
1171 1171  |(% rowspan="2" %)**F5.34**|DI1 disable delay time|Default|0.0s
... ... @@ -1457,12 +1457,6 @@
1457 1457  
1458 1458  For the second output, the parameter setting method is the same as F6.28~~F6.32.
1459 1459  
1460 -(% class="table-bordered" %)
1461 -|(% rowspan="2" %)**F6.38**|The setting time of timer|Default|0
1462 -|Setting range|(% colspan="3" %)0.00s~~100.0s
1463 -
1464 -Set the timer setting time
1465 -
1466 1466  = 8 F7 group keypad display =
1467 1467  
1468 1468  (% class="table-bordered" %)
1681697850903-377.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Jim
Size
... ... @@ -1,1 +1,0 @@
1 -18.5 KB
Content
1681697969422-504.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Jim
Size
... ... @@ -1,1 +1,0 @@
1 -10.9 KB
Content
1681698530367-261.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Jim
Size
... ... @@ -1,1 +1,0 @@
1 -10.0 KB
Content
1681698557086-403.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Jim
Size
... ... @@ -1,1 +1,0 @@
1 -11.8 KB
Content