09 Appendix A Selection Guide
Braking resistor selection
AC Drive Model | Inverter Power | Braking resistor power (General occasions/High frequency braking occasions) | Braking resistor resistance value |
kW | kW | Ω | |
Single phase 220V input | |||
VB-2SR75GB | 0.8 | 0.1/0.15 | 200.0 |
VB-2S1R5GB | 1.5 | 0.2/0.3 | 100.0 |
VB-2S2R2GB | 2.2 | 0.2/0.5 | 70.0 |
Three-phase 380V input | |||
VB-4TR75GB | 0.8 | 0.1/0.15 | 750.0 |
VB-4T1R5GB | 1.5 | 0.2/0.3 | 400.0 |
VB-4T2R2GB | 2.2 | 0.2/0.5 | 250.0 |
VB-4T004GB/5R5PB | 4/5.5 | 0.4/0.8 | 150.0 |
VB-4T5R5GB/7R5PB | 5.5/7.5 | 0.6/1.2 | 100.0 |
VB-4T7R5GB | 7.5 | 0.8/1.5 | 75.0 |
VB-4T011GB/015PB | 11/15 | 1.1/2.5 | 50.0 |
VB-4T015GB/18R5PB | 15/18.5 | 1.5/3.0 | 40.0 |
VB-4T18R5GB/022PB | 18.5/22 | 1.9/4.0 | 30.0 |
VB-4T022GB/030PB | 22/30 | 2.2/4.5 | 25.0 |
VB-4T030G/037P | 30/37 | 3.0/6.0 | 20.0 |
VB-4T037G/045P | 37/45 | 3.7/7.5 | 15.0 |
VB-4T045G/055P | 45/55 | 4.5/9.0 | 13.0 |
VB-4T055G/075P | 55/75 | 5.5/15 | 11.0 |
VB-4T075G/093P | 75/93 | 7.5/18 | 8.0 |
VB-4T093G/110P | 93/110 | 9.3/20 | 6.0 |
VB-4T110G/132P | 110/132 | 11.0/25 | 6.0 |
VB-4T132G/160P | 132/160 | 13.2/33.0 | 5.0 |
VB-4T160G/185P | 160/185 | 16.0/40.0 | 4.0 |
VB-4T185G/200P | 185/200 | 18.5/46.0 | 3.0 |
VB-4T200G/220P | 200/220 | 20.0/50.0 | 3.0 |
VB-4T220G/250P | 220/250 | 22.0/55.0 | 3.0 |
VB-4T250G/280P | 250/280 | 25.0/62.5 | 2.0 |
VB-4T280G/315P | 280/315 | 28.0/70.0 | 2.0 |
VB-4T315G/355P | 315/355 | 31.5/79.0 | 2.0 |
VB-4T355G/400P | 355/400 | 35.5/89.0 | 1.5 |
VB-4T400G | 400.0 | 40.0/100.0 | 1.5 |
Recommended power terminal wire
AC Drive Model | Power | Rated input current | Rated output current | Recommended input cable | Recommended output cable | Main terminal adapter lug |
kW | A | A | mm² | mm² | Model | |
Single phase 220V input | ||||||
VB-2SR75GB | 0.75 | 8.2 | 4.5 | 0.75 | 0.75 | E1510 |
VB-2S1R5GB | 1.5 | 14 | 7 | 1.5 | 1.5 | E1510 |
VB-2S2R2GB | 2.2 | 23 | 9.6 | 2.5 | 2.5 | E1510 |
Three-phase 380V input | ||||||
VB-4TR75GB | 0.75 | 3.4 | 2.1 | 0.75 | 0.75 | E1510 |
VB-4T1R5GB | 1.5 | 5 | 3.8 | 0.75 | 0.75 | E1510 |
VB-4T2R2GB | 2.2 | 5.8 | 5.1 | 0.75 | 0.75 | E1510 |
VB-4T004GB/5R5PB | 4/5.5 | 10.5/14.6 | 44452 | 1.5 | 1.5 | E1510 |
VB-4T5R5GB/7R5PB | 5.5/7.5 | 14.6/20.5 | 13/17 | 2.5 | 2.5 | E2512 |
VB-4T7R5GB | 7.5 | 20.5 | 17 | 4 | 4 | E2512 |
VB-4T011GB/015PB | 44515 | 26/35 | 25/32 | 4 | 4 | GTNR 6-5 |
VB-4T015GB/18R5PB | 15/18.5 | 35/38.5 | 32/37 | 6 | 6 | GTNR 6-5 |
VB-4T18R5GB/022PB | 18.5/22 | 38.5/46 | 37/45 | 10 | 10 | GTNR 10-6 |
VB-4T022GB/030PB | 22/30 | 46.5/62 | 45/60 | 10 | 10 | GTNR 10-6 |
VB-4T030G/037P | 30/37 | 62/76 | 60/75 | 16 | 16 | GTNR 25-6 |
VB-4T037G/045P | 37/45 | 76/92 | 75/91 | 25 | 25 | GTNR 25-6 |
VB-4T045G/055P | 45/55 | 92/113 | 91/110 | 35 | 35 | GTNR 35-10 |
VB-4T055G/075P | 55/75 | 113/157 | 112/150 | 50 | 50 | GTNR 50-10 |
VB-4T075G/093P | 75/93 | 157/180 | 150/170 | 70 | 70 | GTNR 95-10 |
VB-4T093G/110P | 93/110 | 180/214 | 170/210 | 95 | 95 | GTNR 95-10 |
VB-4T110G/132P | 110/132 | 214/256 | 210/253 | 95 | 95 | GTNR 95-10 |
VB-4T132G/160P | 132/160 | 256/307 | 253/304 | 120 | 120 | GTNR 150-12 |
VB-4T160G/185P | 160/185 | 307/345 | 304/340 | 150 | 150 | GTNR 150-12 |
VB-4T185G/200P | 185/200 | 345/385 | 340/377 | 150 | 150 | GTNR 150-12 |
VB-4T200G/220P | 200/220 | 385/430 | 377/426 | 185 | 185 | GTNR 185-16 |
VB-4T220G/250P | 220/250 | 430/468 | 426/465 | 2x120 | 2x120 | GTNR 150-16 |
VB-4T250G/280P | 250/280 | 468/525 | 465/520 | 2x120 | 2x120 | GTNR 150-16 |
VB-4T280G/315P | 280/315 | 525/590 | 520/585 | 2x120 | 2x120 | GTNR 150-16 |
VB-4T315G/355P | 315/355 | 590/665 | 585/650 | 2x150 | 2x150 | GTNR 150-16 |
VB-4T355G/400P | 355/400 | 665/785 | 650/725 | 2x185 | 2x185 | GTNR 185-16 |
VB-4T400G | 400 | 785 | 725 | 2x240 | 2x240 | GTNR 240-16 |
Ground wire selection
1. The terminal must be grounded reliably, and the resistance of the grounding wire must be less than 0.1Ω. Otherwise, the equipment will work abnormally or even be damaged.
2. Do not share the grounding terminal and the N terminal of the neutral line of the power supply.
3. impedance of the protective grounding conductor must meet the requirements of being able to withstand the large short-circuit current that may occur in the event of a fault.
4. The protective grounding conductor must use a yellow-green cable.
5. The size of the protective grounding conductor is selected according to the following table:
The cross-sectional area of a phase wire (S) | Minimum cross-sectional area of protective conductor (Sp) |
S ≤ 16mm2 | S |
16mm2< S ≤ 35mm2 | 16mm2 |
316mm2 < S | S/2 |