Wiki source code of 09 Appendix A Selection Guide

Last modified by Theodore Xu on 2025/03/04 16:11

Show last authors
1 = Braking resistor selection =
2
3 (% class="box infomessage" %)
4 (((
5 **✎Note**
6
7 0.75kW-22kW:VB default support barking unit so just install braking resistor. Please set F4.16=0,FA.03=0,FA.04=120.
8
9 37kW and above:VB does not support the default barking unit, so need to install external brake unit and brake resistor. Please set F4.16=0, FA.03=0, FA.04=150.
10
11 Woodworking engraving machine, lifting, centrifugal drying and other industries belong to the high-frequency braking occasions recommended to use higher power braking resistors.
12 )))
13
14 (% class="table-bordered" %)
15 |(% rowspan="2" %)**AC Drive Model**|(% style="width:227px" %)**Inverter Power**|(% style="width:250px" %)(((
16 **Braking resistor power**
17
18 **(General occasions/High frequency braking occasions)**
19 )))|(% style="width:329px" %)**Braking resistor resistance value**
20 |(% style="width:227px" %)kW|(% style="width:250px" %)kW|(% style="width:329px" %)Ω
21 |(% colspan="4" %)**Single phase 220V input**
22 |VB-2SR75GB|(% style="width:227px" %)0.8|(% style="width:250px" %)0.1/0.15|(% style="width:329px" %)200.0
23 |VB-2S1R5GB|(% style="width:227px" %)1.5|(% style="width:250px" %)0.2/0.3|(% style="width:329px" %)100.0
24 |VB-2S2R2GB|(% style="width:227px" %)2.2|(% style="width:250px" %)0.2/0.5|(% style="width:329px" %)70.0
25 |(% colspan="4" %)**Three-phase 380V input**
26 |VB-4TR75GB|(% style="width:227px" %)0.8|(% style="width:250px" %)0.1/0.15|(% style="width:329px" %)750.0
27 |VB-4T1R5GB|(% style="width:227px" %)1.5|(% style="width:250px" %)0.2/0.3|(% style="width:329px" %)400.0
28 |VB-4T2R2GB|(% style="width:227px" %)2.2|(% style="width:250px" %)0.2/0.5|(% style="width:329px" %)250.0
29 |VB-4T004GB/5R5PB|(% style="width:227px" %)4/5.5|(% style="width:250px" %)0.4/0.8|(% style="width:329px" %)150.0
30 |VB-4T5R5GB/7R5PB|(% style="width:227px" %)5.5/7.5|(% style="width:250px" %)0.6/1.2|(% style="width:329px" %)100.0
31 |VB-4T7R5GB|(% style="width:227px" %)7.5|(% style="width:250px" %)0.8/1.5|(% style="width:329px" %)75.0
32 |VB-4T011GB/015PB|(% style="width:227px" %)11/15|(% style="width:250px" %)1.1/2.5|(% style="width:329px" %)50.0
33 |VB-4T015GB/18R5PB|(% style="width:227px" %)15/18.5|(% style="width:250px" %)1.5/3.0|(% style="width:329px" %)40.0
34 |VB-4T18R5GB/022PB|(% style="width:227px" %)18.5/22|(% style="width:250px" %)1.9/4.0|(% style="width:329px" %)30.0
35 |VB-4T022GB/030PB|(% style="width:227px" %)22/30|(% style="width:250px" %)2.2/4.5|(% style="width:329px" %)25.0
36 |VB-4T030G/037P|(% style="width:227px" %)30/37|(% style="width:250px" %)3.0/6.0|(% style="width:329px" %)20.0
37 |VB-4T037G/045P|(% style="width:227px" %)37/45|(% style="width:250px" %)3.7/7.5|(% style="width:329px" %)15.0
38 |VB-4T045G/055P|(% style="width:227px" %)45/55|(% style="width:250px" %)4.5/9.0|(% style="width:329px" %)13.0
39 |VB-4T055G/075P|(% style="width:227px" %)55/75|(% style="width:250px" %)5.5/15|(% style="width:329px" %)11.0
40 |VB-4T075G/093P|(% style="width:227px" %)75/93|(% style="width:250px" %)7.5/18|(% style="width:329px" %)8.0
41 |VB-4T093G/110P|(% style="width:227px" %)93/110|(% style="width:250px" %)9.3/20|(% style="width:329px" %)6.0
42 |VB-4T110G/132P|(% style="width:227px" %)110/132|(% style="width:250px" %)11.0/25|(% style="width:329px" %)6.0
43 |VB-4T132G/160P|(% style="width:227px" %)132/160|(% style="width:250px" %)13.2/33.0|(% style="width:329px" %)5.0
44 |VB-4T160G/185P|(% style="width:227px" %)160/185|(% style="width:250px" %)16.0/40.0|(% style="width:329px" %)4.0
45 |VB-4T185G/200P|(% style="width:227px" %)185/200|(% style="width:250px" %)18.5/46.0|(% style="width:329px" %)3.0
46 |VB-4T200G/220P|(% style="width:227px" %)200/220|(% style="width:250px" %)20.0/50.0|(% style="width:329px" %)3.0
47 |VB-4T220G/250P|(% style="width:227px" %)220/250|(% style="width:250px" %)22.0/55.0|(% style="width:329px" %)3.0
48 |VB-4T250G/280P|(% style="width:227px" %)250/280|(% style="width:250px" %)25.0/62.5|(% style="width:329px" %)2.0
49 |VB-4T280G/315P|(% style="width:227px" %)280/315|(% style="width:250px" %)28.0/70.0|(% style="width:329px" %)2.0
50 |VB-4T315G/355P|(% style="width:227px" %)315/355|(% style="width:250px" %)31.5/79.0|(% style="width:329px" %)2.0
51 |VB-4T355G/400P|(% style="width:227px" %)355/400|(% style="width:250px" %)35.5/89.0|(% style="width:329px" %)1.5
52 |VB-4T400G|(% style="width:227px" %)400.0|(% style="width:250px" %)40.0/100.0|(% style="width:329px" %)1.5
53
54 = Recommended power terminal wire =
55
56 (% class="table-bordered" %)
57 |(% rowspan="2" style="width:190px" %)**AC Drive Model**|(% style="width:74px" %)**Power**|(% style="width:157px" %)**Rated input current**|(% style="width:188px" %)**Rated output current**|(% style="width:227px" %)**Recommended input cable**|(% style="width:305px" %)**Recommended output cable**|(% style="width:348px" %)**Main terminal adapter lug**
58 |(% style="width:74px" %)kW|(% style="width:157px" %)A|(% style="width:188px" %)A|(% style="width:227px" %)mm²|(% style="width:305px" %)mm²|(% style="width:348px" %)Model
59 |(% colspan="7" %)**Single phase 220V input**
60 |(% style="width:190px" %)VB-2SR75GB|(% style="width:74px" %)0.75|(% style="width:157px" %)8.2|(% style="width:188px" %)4.5|(% style="width:227px" %)0.75|(% style="width:305px" %)0.75|(% style="width:348px" %)E1510
61 |(% style="width:190px" %)VB-2S1R5GB|(% style="width:74px" %)1.5|(% style="width:157px" %)14|(% style="width:188px" %)7|(% style="width:227px" %)1.5|(% style="width:305px" %)1.5|(% style="width:348px" %)E1510
62 |(% style="width:190px" %)VB-2S2R2GB|(% style="width:74px" %)2.2|(% style="width:157px" %)23|(% style="width:188px" %)9.6|(% style="width:227px" %)2.5|(% style="width:305px" %)2.5|(% style="width:348px" %)E1510
63 |(% colspan="7" %)**Three-phase 380V input**
64 |(% style="width:190px" %)VB-4TR75GB|(% style="width:74px" %)0.75|(% style="width:157px" %)3.4|(% style="width:188px" %)2.1|(% style="width:227px" %)0.75|(% style="width:305px" %)0.75|(% style="width:348px" %)E1510
65 |(% style="width:190px" %)VB-4T1R5GB|(% style="width:74px" %)1.5|(% style="width:157px" %)5|(% style="width:188px" %)3.8|(% style="width:227px" %)0.75|(% style="width:305px" %)0.75|(% style="width:348px" %)E1510
66 |(% style="width:190px" %)VB-4T2R2GB|(% style="width:74px" %)2.2|(% style="width:157px" %)5.8|(% style="width:188px" %)5.1|(% style="width:227px" %)0.75|(% style="width:305px" %)0.75|(% style="width:348px" %)E1510
67 |(% style="width:190px" %)VB-4T004GB/5R5PB|(% style="width:74px" %)4/5.5|(% style="width:157px" %)10.5/14.6|(% style="width:188px" %)44452|(% style="width:227px" %)1.5|(% style="width:305px" %)1.5|(% style="width:348px" %)E1510
68 |(% style="width:190px" %)VB-4T5R5GB/7R5PB|(% style="width:74px" %)5.5/7.5|(% style="width:157px" %)14.6/20.5|(% style="width:188px" %)13/17|(% style="width:227px" %)2.5|(% style="width:305px" %)2.5|(% style="width:348px" %)E2512
69 |(% style="width:190px" %)VB-4T7R5GB|(% style="width:74px" %)7.5|(% style="width:157px" %)20.5|(% style="width:188px" %)17|(% style="width:227px" %)4|(% style="width:305px" %)4|(% style="width:348px" %)E2512
70 |(% style="width:190px" %)VB-4T011GB/015PB|(% style="width:74px" %)44515|(% style="width:157px" %)26/35|(% style="width:188px" %)25/32|(% style="width:227px" %)4|(% style="width:305px" %)4|(% style="width:348px" %)GTNR 6-5
71 |(% style="width:190px" %)VB-4T015GB/18R5PB|(% style="width:74px" %)15/18.5|(% style="width:157px" %)35/38.5|(% style="width:188px" %)32/37|(% style="width:227px" %)6|(% style="width:305px" %)6|(% style="width:348px" %)GTNR 6-5
72 |(% style="width:190px" %)VB-4T18R5GB/022PB|(% style="width:74px" %)18.5/22|(% style="width:157px" %)38.5/46|(% style="width:188px" %)37/45|(% style="width:227px" %)10|(% style="width:305px" %)10|(% style="width:348px" %)GTNR 10-6
73 |(% style="width:190px" %)VB-4T022GB/030PB|(% style="width:74px" %)22/30|(% style="width:157px" %)46.5/62|(% style="width:188px" %)45/60|(% style="width:227px" %)10|(% style="width:305px" %)10|(% style="width:348px" %)GTNR 10-6
74 |(% style="width:190px" %)VB-4T030G/037P|(% style="width:74px" %)30/37|(% style="width:157px" %)62/76|(% style="width:188px" %)60/75|(% style="width:227px" %)16|(% style="width:305px" %)16|(% style="width:348px" %)GTNR 25-6
75 |(% style="width:190px" %)VB-4T037G/045P|(% style="width:74px" %)37/45|(% style="width:157px" %)76/92|(% style="width:188px" %)75/91|(% style="width:227px" %)25|(% style="width:305px" %)25|(% style="width:348px" %)GTNR 25-6
76 |(% style="width:190px" %)VB-4T045G/055P|(% style="width:74px" %)45/55|(% style="width:157px" %)92/113|(% style="width:188px" %)91/110|(% style="width:227px" %)35|(% style="width:305px" %)35|(% style="width:348px" %)GTNR 35-10
77 |(% style="width:190px" %)VB-4T055G/075P|(% style="width:74px" %)55/75|(% style="width:157px" %)113/157|(% style="width:188px" %)112/150|(% style="width:227px" %)50|(% style="width:305px" %)50|(% style="width:348px" %)GTNR 50-10
78 |(% style="width:190px" %)VB-4T075G/093P|(% style="width:74px" %)75/93|(% style="width:157px" %)157/180|(% style="width:188px" %)150/170|(% style="width:227px" %)70|(% style="width:305px" %)70|(% style="width:348px" %)GTNR 95-10
79 |(% style="width:190px" %)VB-4T093G/110P|(% style="width:74px" %)93/110|(% style="width:157px" %)180/214|(% style="width:188px" %)170/210|(% style="width:227px" %)95|(% style="width:305px" %)95|(% style="width:348px" %)GTNR 95-10
80 |(% style="width:190px" %)VB-4T110G/132P|(% style="width:74px" %)110/132|(% style="width:157px" %)214/256|(% style="width:188px" %)210/253|(% style="width:227px" %)95|(% style="width:305px" %)95|(% style="width:348px" %)GTNR 95-10
81 |(% style="width:190px" %)VB-4T132G/160P|(% style="width:74px" %)132/160|(% style="width:157px" %)256/307|(% style="width:188px" %)253/304|(% style="width:227px" %)120|(% style="width:305px" %)120|(% style="width:348px" %)GTNR 150-12
82 |(% style="width:190px" %)VB-4T160G/185P|(% style="width:74px" %)160/185|(% style="width:157px" %)307/345|(% style="width:188px" %)304/340|(% style="width:227px" %)150|(% style="width:305px" %)150|(% style="width:348px" %)GTNR 150-12
83 |(% style="width:190px" %)VB-4T185G/200P|(% style="width:74px" %)185/200|(% style="width:157px" %)345/385|(% style="width:188px" %)340/377|(% style="width:227px" %)150|(% style="width:305px" %)150|(% style="width:348px" %)GTNR 150-12
84 |(% style="width:190px" %)VB-4T200G/220P|(% style="width:74px" %)200/220|(% style="width:157px" %)385/430|(% style="width:188px" %)377/426|(% style="width:227px" %)185|(% style="width:305px" %)185|(% style="width:348px" %)GTNR 185-16
85 |(% style="width:190px" %)VB-4T220G/250P|(% style="width:74px" %)220/250|(% style="width:157px" %)430/468|(% style="width:188px" %)426/465|(% style="width:227px" %)2x120|(% style="width:305px" %)2x120|(% style="width:348px" %)GTNR 150-16
86 |(% style="width:190px" %)VB-4T250G/280P|(% style="width:74px" %)250/280|(% style="width:157px" %)468/525|(% style="width:188px" %)465/520|(% style="width:227px" %)2x120|(% style="width:305px" %)2x120|(% style="width:348px" %)GTNR 150-16
87 |(% style="width:190px" %)VB-4T280G/315P|(% style="width:74px" %)280/315|(% style="width:157px" %)525/590|(% style="width:188px" %)520/585|(% style="width:227px" %)2x120|(% style="width:305px" %)2x120|(% style="width:348px" %)GTNR 150-16
88 |(% style="width:190px" %)VB-4T315G/355P|(% style="width:74px" %)315/355|(% style="width:157px" %)590/665|(% style="width:188px" %)585/650|(% style="width:227px" %)2x150|(% style="width:305px" %)2x150|(% style="width:348px" %)GTNR 150-16
89 |(% style="width:190px" %)VB-4T355G/400P|(% style="width:74px" %)355/400|(% style="width:157px" %)665/785|(% style="width:188px" %)650/725|(% style="width:227px" %)2x185|(% style="width:305px" %)2x185|(% style="width:348px" %)GTNR 185-16
90 |(% style="width:190px" %)VB-4T400G|(% style="width:74px" %)400|(% style="width:157px" %)785|(% style="width:188px" %)725|(% style="width:227px" %)2x240|(% style="width:305px" %)2x240|(% style="width:348px" %)GTNR 240-16
91
92 = Ground wire selection =
93
94 ~1. The terminal must be grounded reliably, and the resistance of the grounding wire must be less than 0.1Ω. Otherwise, the equipment will work abnormally or even be damaged.
95
96 2. Do not share the grounding terminal and the N terminal of the neutral line of the power supply.
97
98 3. impedance of the protective grounding conductor must meet the requirements of being able to withstand the large short-circuit current that may occur in the event of a fault.
99
100 4. The protective grounding conductor must use a yellow-green cable.
101
102 5. The size of the protective grounding conductor is selected according to the following table:
103
104 (% class="table-bordered" %)
105 |(((
106 **The cross-sectional area of a phase wire (S)**
107 )))|(((
108 **Minimum cross-sectional area of protective conductor (Sp)**
109 )))
110 |(((
111 S ≤ 16mm2
112 )))|(((
113 S
114 )))
115 |(((
116 16mm2< S ≤ 35mm2
117 )))|(((
118 16mm2
119 )))
120 |(((
121 316mm2 < S
122 )))|(((
123 S/2
124 )))