... ... @@ -4,8 +4,10 @@
4 4  (((
5 5  **✎Note**
6 6  
7 -When VFD install Braking resistor,it needs set F4.16=0,FA.03=0,FA.04=120.
7 +0.75kW-22kW:VB default support barking unit so just install Braking resistor. Please set F4.16=0,FA.03=0,FA.04=120.
8 8  
9 +37kW and above:VB does not support the default barking unit, so need to install external brake unit and brake resistor. Please set F4.16=0, FA.03=0, FA.04=150.
10 +
9 9  Woodworking engraving machine, lifting, centrifugal drying and other industries belong to the high-frequency braking occasions recommended to use higher power braking resistors.
10 10  )))
11 11  
... ... @@ -87,7 +87,7 @@
87 87  |(% style="width:190px" %)VB-4T355G/400P|(% style="width:74px" %)355/400|(% style="width:157px" %)665/785|(% style="width:188px" %)650/725|(% style="width:227px" %)2x185|(% style="width:305px" %)2x185|(% style="width:348px" %)GTNR 185-16
88 88  |(% style="width:190px" %)VB-4T400G|(% style="width:74px" %)400|(% style="width:157px" %)785|(% style="width:188px" %)725|(% style="width:227px" %)2x240|(% style="width:305px" %)2x240|(% style="width:348px" %)GTNR 240-16
89 89  
90 -= Ground wire selectio =
92 += Ground wire selection =
91 91  
92 92  ~1. The terminal must be grounded reliably, and the resistance of the grounding wire must be less than 0.1Ω. Otherwise, the equipment will work abnormally or even be damaged.