Last modified by Theodore Xu on 2025/04/12 09:37

From version 8.1
edited by Theodore Xu
on 2023/11/13 11:58
Change comment: There is no comment for this version
To version 10.1
edited by Mora Zhou
on 2023/12/21 15:22
Change comment: There is no comment for this version

Summary

Details

Page properties
Author
... ... @@ -1,1 +1,1 @@
1 -XWiki.AiXia
1 +XWiki.Mora
Content
... ... @@ -1,6 +1,9 @@
1 -= 1 Braking resistor selection =
1 += Braking resistor selection =
2 2  
3 +(% class="box infomessage" %)
4 +(((
3 3  **✎Note:** Woodworking engraving machine, lifting, centrifugal drying and other industries belong to the high-frequency braking occasions recommended to use higher power braking resistors.
6 +)))
4 4  
5 5  (% class="table-bordered" %)
6 6  |(% rowspan="2" %)**AC Drive Model**|(% style="width:227px" %)**Inverter Power**|(% style="width:250px" %)(((
... ... @@ -42,7 +42,7 @@
42 42  |VB-4T355G/400P|(% style="width:227px" %)355/400|(% style="width:250px" %)35.5/89.0|(% style="width:329px" %)1.5
43 43  |VB-4T400G|(% style="width:227px" %)400.0|(% style="width:250px" %)40.0/100.0|(% style="width:329px" %)1.5
44 44  
45 -= 2 Recommended power terminal wire =
48 += Recommended power terminal wire =
46 46  
47 47  (% class="table-bordered" %)
48 48  |(% rowspan="2" style="width:190px" %)**AC Drive Model**|(% style="width:74px" %)**Power**|(% style="width:157px" %)**Rated input current**|(% style="width:188px" %)**Rated output current**|(% style="width:227px" %)**Recommended input cable**|(% style="width:305px" %)**Recommended output cable**|(% style="width:348px" %)**Main terminal adapter lug**
... ... @@ -80,7 +80,7 @@
80 80  |(% style="width:190px" %)VB-4T355G/400P|(% style="width:74px" %)355/400|(% style="width:157px" %)665/785|(% style="width:188px" %)650/725|(% style="width:227px" %)2x185|(% style="width:305px" %)2x185|(% style="width:348px" %)GTNR 185-16
81 81  |(% style="width:190px" %)VB-4T400G|(% style="width:74px" %)400|(% style="width:157px" %)785|(% style="width:188px" %)725|(% style="width:227px" %)2x240|(% style="width:305px" %)2x240|(% style="width:348px" %)GTNR 240-16
82 82  
83 -= 3 Ground wire selectio =
86 += Ground wire selectio =
84 84  
85 85  ~1. The terminal must be grounded reliably, and the resistance of the grounding wire must be less than 0.1Ω. Otherwise, the equipment will work abnormally or even be damaged.
86 86