Last modified by xingzhi lin on 2026/01/19 10:43

Show last authors
1 (% class="box infomessage" %)
2 (((
3 ✎Note: The inverter needs to **download the firmware version first**, after the firmware version download is completed, the inverter **can only connect to permanent magnet synchronous motors**, can't connect to asynchronous motors, and **can only use the svc mode (F0.00=0)**, the **maximum frequency** can't be more than **300HZ.**
4 )))
5
6 == [[Download the software>>https://docs.we-con.com.cn/bin/view/VFD/Download/2%20Hardware/]] ==
7
8 (% style="text-align:center" %)
9 [[image:下载目录.png]]
10
11 Enter account number and password
12
13 * Login account: WECON
14 * Password: Wwecan123@
15
16 (% style="text-align:center" %)
17 [[image:软件登录.png]]
18
19 == Firmware version ==
20
21 (% class="box infomessage" %)
22 (((
23 ✎Note: Don't check internet
24 )))
25
26
27 (% style="text-align:center" %)
28 [[image:工具不要勾选Internet.png]]
29
30 Remote files:VB_28034_PMSM_V01.02_20200914.hex 
31
32 (% class="box infomessage" %)
33 (((
34 **[[Check out the video for the exact upgrade process. >>https://youtu.be/vubKSh741s4]]**
35 )))
36
37 (% style="text-align:center" %)
38 [[image:选择对应的固件版本.png]]
39
40 == FF group ==
41
42 After the version download is completed, you need to modify the FF group parameters of the inverter.
43
44 For VC VFD, you need to press ENT to enter FF group, and the password is 1005.
45
46 * Check the value of F7.11 and input the value of F7.11 to FF.00.
47 * Modify FF.01 as the corresponding power code of the inverter (contact technical support for confirmation).
48 * Modify FF.03 as the power of the inverter, for example, 18kW, FF.03=18.
49
50 == Motor self-learning ==
51
52 * F0.00=0
53 * F0.01=0
54 * F2.00=2
55 * F2.01-F2.05(Check the motor nameplate)
56 * F2.11=13 synchronous motor stationary tuning (calculate the reverse potential), **TUNE appears to press RUN**, wait for the self-learning is completed.
57 * Check the parameters F2.16-F2.20.