3 ✎Note: The inverter needs to **download the firmware version first**, after the firmware version download is completed, the inverter **can only connect to permanent magnet synchronous motors**, can't connect to asynchronous motors, and **can only use the svc mode (F0.00=0)**, the **maximum frequency** can't be more than **300HZ.**
4 )))
5
xingzhi lin 4.1 6 == ==
Wecon 1.1 7
8 == Motor self-learning ==
9
10 * F0.00=0
11 * F0.01=0
12 * F2.00=2
13 * F2.01-F2.05(Check the motor nameplate)
14 * F2.11=13 synchronous motor stationary tuning (calculate the reverse potential), **TUNE appears to press RUN**, wait for the self-learning is completed.
15 * Check the parameters F2.16-F2.20.