1 (% class="box infomessage" %)
2 (((
3 ✎Note: The inverter needs to **download the firmware version first**, after the firmware version download is completed, the inverter **can only connect to permanent magnet synchronous motors**, can't connect to asynchronous motors, and **can only use the svc mode (F0.00=0)**, the **maximum frequency** can't be more than **300HZ.**
4 )))
5
6 == [[Download the software>>https://docs.we-con.com.cn/bin/view/VFD/Download/2%20Hardware/]] ==
7
8 (% style="text-align:center" %)
9 [[image:下载目录.png]]
10
11 Enter account number and password
12
13 * Login account: WECON
14 * Password: WECAN123@
15
16 (% style="text-align:center" %)
17 [[image:软件登录.png]]
18
19 == Firmware version ==
20
21 (% class="box infomessage" %)
22 (((
23 ✎Note: Don't check internet
24 )))
25
26
27 (% style="text-align:center" %)
28 [[image:工具不要勾选Internet.png]]
29
30 Remote files:VB_28034_PMSM_V01.02_20200914.hex 
31
32 (% class="box infomessage" %)
33 (((
34 **[[Check out the video for the exact upgrade process. >>https://youtu.be/vubKSh741s4]]**
35 )))
36
37 (% style="text-align:center" %)
38 [[image:选择对应的固件版本.png]]
39
40 == FF group ==
41
42 After the version download is completed, you need to modify the FF group parameters of the inverter.
43
44 * Check the value of F7.11 and input the value of F7.11 to FF.00.
45 * Modify FF.01 as the corresponding power code of the inverter (contact technical support for confirmation).
46 * Modify FF.03 as the power of the inverter, for example, 18kW, FF.03=18.
47
48 == Motor self-learning ==
49
50 * F0.00=0
51 * F0.01=0
52 * F2.00=2
53 * F2.01-F2.05(Check the motor nameplate)