Changes for page 09 Function code

Last modified by Iris on 2025/11/17 14:59

From version 9.2
edited by Iris
on 2025/11/14 09:31
Change comment: There is no comment for this version
To version 5.1
edited by Iris
on 2025/11/13 17:32
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -1,4 +1,4 @@
1 -== **F0 group basic function group** ==
1 +**F0 group basic function group**
2 2  
3 3  |(% rowspan="2" style="text-align:center" %)F0.00|(% style="text-align:center" %)Motor control mode|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)1
4 4  |(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
... ... @@ -169,7 +169,7 @@
169 169  
170 170  When the auxiliary frequency source for digital or pulse potentiometer timing, preset frequency (F0.08) does not work, through the keyboard ▲/▼ key (or multi-function input terminal UP, DOWN) can be adjusted on the basis of the main given frequency.
171 171  
172 -When the auxiliary frequency source is given as an analog input (AI1, AI2) or a pulse input, 100% of the input setting corresponds to the auxiliary frequency source range (see F0.05 and F0.06 instructions). If you need to adjust up or down from the main given frequency, set the analog input to a range of n% to +n%.
172 +When the auxiliary frequency source is given as an analog input (AI1, AI2) or a pulse input, 100% of the input setting corresponds to the auxiliary frequency source range (see F0.05 and F0.06 instructions). If you need to adjust up or down from the main given frequency, set the analog input to a range of.n% to +n%.
173 173  
174 174  The frequency source is timed for pulse input, similar to analog quantity setting.
175 175  
... ... @@ -265,11 +265,11 @@
265 265  
266 266  The effect of adjusting the carrier frequency on the following performance:
267 267  
268 -|(% style="text-align:center" %)Carrier frequency|(% style="text-align:center" %)Low [[image:1763022484807-191.png]] High
268 +|(% style="text-align:center" %)Carrier frequency|(% style="text-align:center" %)Low[[image:1763022484807-191.png]]High
269 269  |(% style="text-align:center" %)Motor noise|(% style="text-align:center" %)High [[image:1763022495845-910.png]] Low
270 -|(% style="text-align:center" %)The output current waveform|(% style="text-align:center" %)Worse [[image:1763022525597-175.png]] Better
271 -|(% style="text-align:center" %)Temperature rise in electric motors|(% style="text-align:center" %)High [[image:1763022595008-156.png]] Low
272 -|(% style="text-align:center" %)VFD temperature rise|(% style="text-align:center" %)Low [[image:1763022599082-487.png]] High
270 +|(% style="text-align:center" %)The output current waveform|(% style="text-align:center" %)Worse[[image:1763022525597-175.png]]Better
271 +|(% style="text-align:center" %)Temperature rise in electric motors|(% style="text-align:center" %)High[[image:1763022595008-156.png]]Low
272 +|(% style="text-align:center" %)VFD temperature rise|(% style="text-align:center" %)Low[[image:1763022599082-487.png]]High
273 273  |(% style="text-align:center" %)Leak current|(% style="text-align:center" %)Low[[image:1763022602360-885.png]]High
274 274  |(% style="text-align:center" %)External radiation interference|(% style="text-align:center" %)Low[[image:1763022605234-199.png]]High
275 275  
... ... @@ -318,7 +318,7 @@
318 318  
319 319  When the output frequency is low, reducing the PWM carrier can increase the low frequency starting torque and reduce the electromagnetic interference during starting. When the bit is 1, the program automatically reduces the PWM carrier when the output frequency is low.
320 320  
321 -Hundreds place: Random PWM depth
321 +Hundreds palce: Random PWM depth
322 322  
323 323  In order to make the motor noise spectrum flatter, you can turn on the random PWM function, after the function is turned on, the PWM carrier is no longer a fixed value, but fluctuates around the F0.16 set carrier. When the bit is not 0, the random PWM function works. The larger the value, the wider the fluctuation range and the flatter the noise spectrum. It should be noted that after opening the random carrier, the electromagnetic noise of the motor will not necessarily be reduced, and the actual noise perception varies from person to person.
324 324  
... ... @@ -352,9 +352,9 @@
352 352  
353 353  |(% rowspan="2" style="text-align:center" %)F0.20|(% style="text-align:center" %)Parameter initialization|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
354 354  |(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
355 -0: No operation
355 +0: No opreration
356 356  
357 -1: Restore factory default (Do not restore motor parameters)
357 +1: Restore factorydefault (Do not restore motor parameters)
358 358  
359 359  2: Clear the record information
360 360  
... ... @@ -384,8 +384,8 @@
384 384  
385 385  Note the following function codes: F0.18, F0.19, F8.01, F8.02, F8.03, F8.04, F8.05, F8.06, F8.07, F8.08.
386 386  
387 -|(% rowspan="2" style="text-align:center" %)F0.24|(% style="text-align:center; width:382px" %)Acceleration and deceleration time reference frequency|(% style="text-align:center; width:147px" %)Factory default|(% style="text-align:center; width:33px" %)0
388 -|(% style="text-align:center; width:382px" %)Setting range|(% colspan="2" style="width:180px" %)(((
387 +|(% rowspan="2" %)F0.24|Acceleration and deceleration time reference frequency|Factory default|0
388 +|Setting range|(% colspan="2" %)(((
389 389  0: Maximum frequency (F0.10)
390 390  
391 391  1: Set the frequency
... ... @@ -397,7 +397,7 @@
397 397  
398 398  |(% rowspan="2" style="text-align:center" %)F0.25|(% style="text-align:center" %)Fan control|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)01
399 399  |(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
400 -One place: Start/stop control
400 +One place: start/stop control
401 401  
402 402  0: The fan runs after the inverter is powered on
403 403  
... ... @@ -737,7 +737,7 @@
737 737  
738 738  |(% rowspan="2" style="text-align:center" %)F2.12|(% style="text-align:center" %)G/P Machine type|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)Model determination
739 739  |(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
740 -0: G-type machine;
740 +0: G type machine;
741 741  
742 742  1: P-type machine
743 743  )))
... ... @@ -763,14 +763,14 @@
763 763  
764 764  Change F2.04 or F2.05, the program will automatically calculate the number of motor poles, in general, do not need to set this parameter.
765 765  
766 -|(% rowspan="2" style="text-align:center; width:92px" %)F2.22|(% style="text-align:center; width:242px" %)Stator resistance of synchro|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)Model determination
767 -|(% style="text-align:center; width:242px" %)Setting range|(% colspan="2" style="text-align:center" %)0.001 to 65.000(0.001Ohm)
768 -|(% rowspan="2" style="text-align:center; width:92px" %)F2.23|(% style="text-align:center; width:242px" %)Synchro d-axis inductance|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)Model determination
769 -|(% style="text-align:center; width:242px" %)Setting range|(% colspan="2" style="text-align:center" %)0.01mH to 655.35mH
770 -|(% rowspan="2" style="text-align:center; width:92px" %)F2.24|(% style="text-align:center; width:242px" %)Synchro Q-axis inductance|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)Model determination
771 -|(% style="text-align:center; width:242px" %)Setting range|(% colspan="2" style="text-align:center" %)0.01mH to 655.35mH
772 -|(% rowspan="2" style="text-align:center; width:92px" %)F2.25|(% style="text-align:center; width:242px" %)Synchro back electromotive force|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)Model determination
773 -|(% style="text-align:center; width:242px" %)Setting range|(% colspan="2" style="text-align:center" %)0.1V to 1000.0V
766 +|(% rowspan="2" style="text-align:center" %)F2.22|(% style="text-align:center" %)Stator resistance of synchro|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)Model determination
767 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.001 to 65.000(0.001Ohm)
768 +|(% rowspan="2" style="text-align:center" %)F2.23|(% style="text-align:center" %)Synchro d-axis inductance|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)Model determination
769 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.01mH to 655.35mH
770 +|(% rowspan="2" style="text-align:center" %)F2.24|(% style="text-align:center" %)Synchro Q-axis inductance|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)Model determination
771 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.01mH to 655.35mH
772 +|(% rowspan="2" style="text-align:center" %)F2.25|(% style="text-align:center" %)Synchro back electromotive force|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)Model determination
773 +|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.1V to 1000.0V
774 774  
775 775  After the automatic tuning of the synchronous motor is completed, the set values of the synchronous motor parameters (F2.22 to F2.25) are automatically updated.
776 776  
... ... @@ -808,325 +808,3 @@
808 808  |(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.1V
809 809  
810 810  The per unit value of the motor parameters is used for the actual program calculation. After learning or parameter recovery, the actual change is F2.31 to F2.40. F2.06 to F2.10 and F2.22 to F2.25 are calculated from the per unit value, so only F2.31 to F2.40 values can be modified, F2.06 to F2.10 and F2.22 to F2.25 are only used to display and cannot be changed.
811 -
812 -== **F3 vector control parameters** ==
813 -
814 -The F3 group function code is only valid in vector control mode, that is, it is valid when F0.00 = 0 and invalid when F0.00 = 1.
815 -
816 -|(% rowspan="2" style="text-align:center" %)F3.00|(% style="text-align:center" %)ASR (Speed loop) proportional gain 1|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.20
817 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00 to 1.00
818 -|(% rowspan="2" style="text-align:center" %)F3.01|(% style="text-align:center" %)ASR(Velocity ring) integration time 1|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.20
819 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.01 to 10.00s
820 -|(% rowspan="2" style="text-align:center" %)F3.03|(% style="text-align:center" %)ASR filtering time 1|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.000s
821 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.000 to 0.100s
822 -|(% rowspan="2" style="text-align:center" %)F3.04|(% style="text-align:center" %)ASR switching frequency 1|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)5.00Hz
823 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00 to 50.00Hz
824 -|(% rowspan="2" style="text-align:center" %)F3.05|(% style="text-align:center" %)ASR(Speed loop) proportional gain 2|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.20
825 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00 to 1.00
826 -|(% rowspan="2" style="text-align:center" %)F3.06|(% rowspan="2" style="text-align:center" %)ASR(Velocity loop) integration time 2|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.20
827 -|(% colspan="2" style="text-align:center" %)0.01 to 10.00s
828 -|(% rowspan="2" style="text-align:center" %)F3.08|(% style="text-align:center" %)ASR filtering time 2|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.000s
829 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.000 to 0.100s
830 -|(% rowspan="2" style="text-align:center" %)F3.09|(% style="text-align:center" %)ASR switching frequency 2|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)10.00Hz
831 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00 to 50.00Hz
832 -
833 -F3.00 and F3.01 are PI adjustment parameters when the operating frequency is less than switching frequency 1 (F3.04).
834 -
835 -F3.05 and F3.06 are PI adjustment parameters whose operating frequency is greater than switching frequency 2 (F3.09).
836 -
837 -The PI parameters of the frequency segment between switching frequency 1 and switching frequency 2 are linear switching of the two groups of PI parameters, as shown in the figure below:
838 -
839 -(% style="text-align:center" %)
840 -(((
841 -(% style="display:inline-block" %)
842 -[[Figure 9-3-1 PI parameter diagram>>image:1763026906844-539.png]]
843 -)))
844 -
845 -The speed dynamic response characteristic of vector control can be adjusted by setting the proportional coefficient and integration time of the speed regulator. Proportional increase
846 -
847 -If the integration time is reduced, the dynamic response of the speed loop can be accelerated. The system may oscillate if the proportional gain is too large or the integration time is too small.
848 -
849 -Recommended adjustment method:
850 -
851 -If the Factory parameters cannot meet the requirements, fine-tune the Factory default parameters: first increase the proportional gain to ensure that the system does not oscillate; Then the integration time is reduced so that the system has both faster response characteristics and smaller overshoot.
852 -
853 -Note: Setting the PI parameter incorrectly may result in excessive speed overshoot. Even overvoltage failure occurs when overshoot falls back.
854 -
855 -|(% rowspan="2" style="text-align:center" %)F3.02|(% style="text-align:center" %)Loss of velocity protection value|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0ms
856 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 5000ms
857 -
858 -In order to prevent motor speed, when the motor speed is detected to have a large deviation from the target speed and maintain F3.02 time or more, the inverter alarms.
859 -
860 -|(% rowspan="2" style="text-align:center; width:115px" %)F3.03|(% style="text-align:center; width:445px" %)ASR Filtering time 1|(% style="text-align:center; width:232px" %)Factory default|(% style="text-align:center; width:89px" %)0.000s
861 -|(% style="text-align:center; width:445px" %)Setting range|(% colspan="2" style="text-align:center; width:321px" %)0.000 to 0.100s
862 -|(% rowspan="2" style="text-align:center; width:115px" %)F3.08|(% style="text-align:center; width:445px" %)ASR Filtering time 2|(% style="text-align:center; width:232px" %)Factory default|(% style="text-align:center; width:89px" %)0.000s
863 -|(% style="text-align:center; width:445px" %)Setting range|(% colspan="2" style="text-align:center; width:321px" %)0.000 to 0.100s
864 -
865 -It is used to set the filtering time of the speed loop feedback. When the output frequency is below F3.04, the filtering time is F3.03. When the value is higher than F3.04, the filtering time is F3.08.
866 -
867 -|(% rowspan="2" style="text-align:center; width:115px" %)F3.10|(% style="text-align:center; width:446px" %)Slip compensation coefficient|(% style="text-align:center; width:233px" %)Factory default|(% style="text-align:center; width:87px" %)100%
868 -|(% style="text-align:center; width:446px" %)Setting range|(% colspan="2" style="text-align:center; width:320px" %)0 to 250%
869 -
870 -This parameter is used to adjust the slip frequency compensation for high performance vector control. When fast response and high speed accuracy are required, proper adjustment of this parameter can improve the dynamic response speed of the system and eliminate the steady-state speed error.
871 -
872 -|(% rowspan="2" style="text-align:center" %)F3.11|(% style="text-align:center; width:449px" %)Maximum electric torque|(% style="text-align:center; width:235px" %)Factory default|(% style="text-align:center; width:83px" %)160.0%
873 -|(% style="text-align:center; width:449px" %)Setting range|(% colspan="2" style="text-align:center; width:318px" %)0.0 to 250.0%
874 -|(% rowspan="2" style="text-align:center" %)F3.12|(% style="text-align:center; width:449px" %)Maximum generating torque|(% style="text-align:center; width:235px" %)Factory default|(% style="text-align:center; width:83px" %)160.0%
875 -|(% style="text-align:center; width:449px" %)Setting range|(% colspan="2" style="text-align:center; width:318px" %)0.0 to 250.0%
876 -
877 -When speed control is set, the maximum electric torque in the electric state and the maximum electric torque in the generation state are respectively.
878 -
879 -|(% rowspan="2" style="text-align:center; width:115px" %)F3.16|(% style="text-align:center; width:452px" %)Current loop D axis proportional gain|(% style="text-align:center; width:237px" %)Factory default|(% style="text-align:center; width:77px" %)1.0
880 -|(% style="text-align:center; width:452px" %)Setting range|(% colspan="2" style="text-align:center; width:314px" %)0.1 to 10.0
881 -|(% rowspan="2" style="text-align:center; width:115px" %)F3.17|(% style="text-align:center; width:452px" %)Current loop D axis integral gain|(% style="text-align:center; width:237px" %)Factory default|(% style="text-align:center; width:77px" %)1.0
882 -|(% style="text-align:center; width:452px" %)Setting range|(% colspan="2" style="text-align:center; width:314px" %)0.1 to 10.0
883 -|(% rowspan="2" style="text-align:center; width:115px" %)F3.18|(% style="text-align:center; width:452px" %)Current loop Q axis proportional gain|(% style="text-align:center; width:237px" %)Factory default|(% style="text-align:center; width:77px" %)1.0
884 -|(% style="text-align:center; width:452px" %)Setting range|(% colspan="2" style="text-align:center; width:314px" %)0.1 to 10.0
885 -|(% rowspan="2" style="text-align:center; width:115px" %)F3.19|(% style="text-align:center; width:452px" %)Current loop Q axis integral gain|(% style="text-align:center; width:237px" %)Factory default|(% style="text-align:center; width:77px" %)1.0
886 -|(% style="text-align:center; width:452px" %)Setting range|(% colspan="2" style="text-align:center; width:314px" %)0.1 to 10.0
887 -
888 -Set PI parameter of current loop in vector control of asynchronous machine and synchronous machine. When the vector control, if the speed, current oscillation, instability phenomenon, can be appropriately reduced each gain to achieve stability; At the same time, increasing each gain helps to improve the dynamic response of the motor.
889 -
890 -|(% rowspan="2" style="text-align:center; width:116px" %)F3.20|(% style="text-align:center; width:454px" %)D-axis feed forward gain|(% style="text-align:center; width:236px" %)Factory default|(% style="text-align:center; width:75px" %)50.0%
891 -|(% style="text-align:center; width:454px" %)Setting range|(% colspan="2" style="text-align:center; width:311px" %)0.0 to 200.0%
892 -|(% rowspan="2" style="text-align:center; width:116px" %)F3.21|(% style="text-align:center; width:454px" %)Q-axis feed forward gain|(% style="text-align:center; width:236px" %)Factory default|(% style="text-align:center; width:75px" %)50.0%
893 -|(% style="text-align:center; width:454px" %)Setting range|(% colspan="2" style="text-align:center; width:311px" %)0.0 to 200.0%
894 -
895 -The current loop has been decoupled, and the feed forward can accelerate the response speed of the current loop. Increasing feed forward can make the response faster, but it is generally not recommended to exceed 100.0%.
896 -
897 -|(% rowspan="2" style="text-align:center; width:113px" %)F3.22|(% style="text-align:center; width:458px" %)Optimize the current loop bandwidth|(% style="text-align:center; width:240px" %)Factory default|(% style="text-align:center; width:70px" %)2.00ms
898 -|(% style="text-align:center; width:458px" %)Setting range|(% colspan="2" style="text-align:center; width:310px" %)0.0 to 99.99ms
899 -|(% rowspan="2" style="text-align:center; width:113px" %)F3.23|(% style="text-align:center; width:458px" %)Current loop control word|(% style="text-align:center; width:240px" %)Factory default|(% style="text-align:center; width:70px" %)0
900 -|(% style="text-align:center; width:458px" %)Setting range|(% colspan="2" style="text-align:center; width:310px" %)0 to 65535
901 -
902 -This parameter is used to set the current ring.
903 -
904 -|(% rowspan="2" style="text-align:center" %)F3.24|(% style="text-align:center" %)Weak magnetic control current upper limit|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)50%
905 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 200%
906 -|(% rowspan="2" style="text-align:center" %)F3.25|(% style="text-align:center" %)Weak magnetic control feed forward gain|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0%
907 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 500%
908 -|(% rowspan="2" style="text-align:center" %)F3.26|(% style="text-align:center" %)Weak magnetic control proportional gain|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)500
909 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 9999
910 -|(% rowspan="2" style="text-align:center" %)F3.27|(% style="text-align:center" %)Weak magnetic control integral gain|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)1000
911 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 9999
912 -
913 -When the asynchronous motor and permanent magnet synchronous motor work in vector mode, the weak magnetic acceleration can be carried out. F3.24 sets the upper limit of demagnetization current, and the weak magnetic function is turned off when the time phase is set to 0. F3.25 to F3.27 Set the parameters of magnetic weakening control. When instability occurs during magnetic weakening, adjust the parameters for debugging.
914 -
915 -|(% rowspan="2" style="text-align:center" %)F3.28|(% style="text-align:center" %)MTPA gain|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0%
916 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 500.0%
917 -|(% rowspan="2" style="text-align:center" %)F3.29|(% style="text-align:center" %)MTPA filtering time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)100ms
918 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 999.9ms
919 -
920 -MTPA function is to optimize the excitation strategy of permanent magnet synchronous motor to maximize motor output/motor current; When the difference between D and Q axis inductance of permanent magnet motor is large, adjusting [F3.28] can obviously change the motor current under the same load. Adjustment [F3.29] can improve the stability of motor operation.
921 -
922 -|(% rowspan="2" style="text-align:center" %)F3.30|(% style="text-align:center" %)Magnetic flux compensation coefficient|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)100%
923 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 500%
924 -|(% rowspan="2" style="text-align:center" %)F3.31|(% style="text-align:center" %)Open-loop vector observer gain|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)1024
925 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 9999
926 -|(% rowspan="2" style="text-align:center" %)F3.32|(% style="text-align:center" %)Open loop vector observation filtering time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)20ms
927 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)1 to 100ms
928 -|(% rowspan="2" style="text-align:center" %)F3.33|(% style="text-align:center" %)The open-loop vector compensates the starting frequency|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)1.0%
929 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 100.0%
930 -|(% rowspan="2" style="text-align:center" %)F3.34|(% style="text-align:center" %)Open loop vector control word|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)4
931 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 9999
932 -
933 -This parameter is used to set the parameter of flux observation when asynchronous motor or synchronous motor is controlled by open loop vector.
934 -
935 -|(% rowspan="2" style="text-align:center" %)F3.35|(% style="text-align:center" %)Synchronous open loop start mode|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)1
936 -|(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
937 -0: Direct startup
938 -
939 -1: Start at an Angle
940 -)))
941 -
942 -It is used to set the starting mode when the synchronous motor is open loop vector, 0 starts DC first, pulls the permanent magnet to the set position and then starts; 1 Find the permanent magnet position before starting.
943 -
944 -|(% rowspan="2" style="text-align:center" %)F3.36|(% style="text-align:center" %)DC pull in time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)500ms
945 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)1ms to 9999ms
946 -
947 -Synchronous motor start DC pull in time, time is too short may appear permanent magnet has not completely pulled to the set position on the end of the possibility, may appear not smooth start or even start failure.
948 -
949 -|(% rowspan="2" style="text-align:center" %)F3.37|(% style="text-align:center" %)Synchronous open loop vector low frequency boost|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)20.0%
950 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 100.0%
951 -|(% rowspan="2" style="text-align:center" %)F3.38|(% style="text-align:center" %)Synchronous open loop vector high frequency boost|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.0%
952 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0 to 100.0%
953 -|(% rowspan="2" style="text-align:center" %)F3.39|(% style="text-align:center" %)Low frequency boost to maintain frequency|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)10.0%
954 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0 to 100.0%
955 -|(% rowspan="2" style="text-align:center" %)F3.40|(% style="text-align:center" %)Low frequency increases cutoff frequency|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)20.0%
956 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.0 to 100.0%
957 -
958 -At low frequency, the D-axis current can be appropriately increased to improve the accuracy of flux observation and starting torque. When the relative frequency (relative to the rated frequency) is lower than F3.39, the D-axis current feed is set to F3.37; When the relative frequency is higher than F3.38, the given current of D-axis is F3.38. When the relative frequency is before F3.38 and F3.39, the D-axis current is given between F3.39 and F3.40. When the synchronous motor is running at high frequency under no-load or light load (relative frequency is higher than F3.40), the D-axis current F3.38 can be set appropriately to reduce the current jitters.
959 -
960 -|(% rowspan="2" style="text-align:center" %)F3.46|(% style="text-align:center" %)Speed/torque control mode|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
961 -|(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
962 -0: Speed control
963 -
964 -1: Torque control
965 -)))
966 -
967 -1: Torque control is only effective when the open loop vector is controlled, and VF control is invalid.
968 -
969 -
970 -|(% rowspan="2" style="text-align:center" %)F3.47|(% style="text-align:center" %)Torque given channel selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
971 -|(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
972 -0: F3.48 is set.
973 -
974 -1: AI1╳F3.48
975 -
976 -2: AI2╳F3.48
977 -
978 -3: AI3╳F3.48
979 -
980 -4: PUL╳F3.48
981 -
982 -5: Keyboard potentiometer ╳F3.48
983 -
984 -6: RS485 communication ╳F3.48
985 -)))
986 -
987 -Torque setting adopts relative value, 100.0% corresponds to the rated torque of the motor. The Setting range is 0% to 200.0%, indicating that the maximum torque of the inverter is 2 times the rated torque of the inverter.
988 -
989 -0: Keyboard number given by function code F3.48.
990 -
991 -1: AI1 × F3.48 Set by AI1 terminal voltage analog input.
992 -
993 -2: AI2 × F3.48 Set by AI2 terminal voltage or current analog input.
994 -
995 -3: AI3 × F3.48 is set by the AI3 terminal current input analog.
996 -
997 -4: PUL × F3.48 is set by the high-speed pulse input from the PUL terminal.
998 -
999 -5: Keyboard potentiometer set × F7.01 by the keyboard potentiometer analog setting.
1000 -
1001 -6: RS485 communication set x F3.48 is set by RS485 serial port communication.
1002 -
1003 -Note: If the value of 1 to 6 is 100%, it corresponds to the value set by the function code F3.48.
1004 -
1005 -|(% rowspan="2" style="text-align:center" %)F3.48|(% style="text-align:center" %)Torque keyboard numeric setting|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)100.0%
1006 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to 200.0%
1007 -
1008 -When the function code F3.47 = 0, the torque is set by the function code F3.48.
1009 -
1010 -|(% rowspan="2" style="text-align:center" %)F3.49|(% style="text-align:center" %)Torque direction selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)00
1011 -|(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
1012 -Units: torque direction setting
1013 -
1014 -0: The torque direction is positive
1015 -
1016 -1: The torque direction is negative
1017 -
1018 -Tens place: Torque reversing setting
1019 -
1020 -0: Torque reversal is allowed
1021 -
1022 -1: Torque reversal is prohibited
1023 -)))
1024 -
1025 -LED units place: Torque direction setting
1026 -
1027 -0: The torque direction is positive inverter running.
1028 -
1029 -1: The torque direction is negative inverter reversal operation.
1030 -
1031 -LED tens place: Torque reversing setting
1032 -
1033 -0: Allows the torque converter to keep running in one direction.
1034 -
1035 -1: The torque reversal inverter can be run in both positive and negative directions.
1036 -
1037 -Note: The running direction will not be affected by the F0.16 setting during torque control, and only one direction will be maintained when starting with the keyboard FWD or REV keys.
1038 -
1039 -|(% rowspan="2" style="text-align:center" %)F3.50|(% style="text-align:center" %)Upper limit of output torque|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)150.0%
1040 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)F3.51 to 200.0%
1041 -|(% rowspan="2" style="text-align:center" %)F3.51|(% style="text-align:center" %)Lower limit of output torque|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0%
1042 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0 to F3.50
1043 -
1044 -Output torque upper limit: Used to set the output torque upper limit for torque control.
1045 -
1046 -Lower output torque limit: Used to set the lower output torque limit during torque control.
1047 -
1048 -|(% rowspan="2" style="text-align:center" %)F3.52|(% style="text-align:center; width:311px" %)Torque control forward speed limit selection|(% style="text-align:center; width:168px" %)Factory default|(% style="text-align:center" %)0.10s
1049 -|(% style="text-align:center; width:311px" %)Setting range|(% colspan="2" style="width:260px" %)(((
1050 -0: F3.54 is set
1051 -
1052 -1: AI1╳F3.54
1053 -
1054 -2: AI2╳F3.54
1055 -
1056 -3: AI3╳F3.54
1057 -
1058 -4: PUL╳F3.54
1059 -
1060 -5: Keyboard potentiometer given ╳F3.54
1061 -
1062 -6: RS485 communication given ╳F3.54
1063 -)))
1064 -
1065 -It is used to set the maximum forward operating frequency limit of the inverter under the torque control mode.
1066 -
1067 -When the converter torque control, if the load torque is less than the motor output torque, the motor speed will continue to rise, in order to prevent mechanical system accidents such as racing, it is necessary to limit the maximum motor speed during torque control.
1068 -
1069 -0: Keyboard number given by function code F3.54.
1070 -
1071 -1: AI1 × F3.54 Set by AI1 terminal voltage analog input.
1072 -
1073 -2: AI2 × F3.54 Set by AI2 terminal voltage analog input.
1074 -
1075 -3: AI3 × F3.54 is set by the AI3 terminal current input analog.
1076 -
1077 -4: PUL × F3.54 is set by the high-speed pulse input from the PUL terminal.
1078 -
1079 -5: Keyboard potentiometer set × F3.54 by the keyboard potentiometer analog setting.
1080 -
1081 -6: RS485 communication Set × F3.54 is set by RS485 serial port communication.
1082 -
1083 -**✎Note:** If 100% is set in 1 to 6 above, it corresponds to the value set in function code [F3.54].
1084 -
1085 -|(% rowspan="2" style="text-align:center" %)F3.53|(% style="text-align:center" %)Torque control reversal speed limit selection|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0
1086 -|(% style="text-align:center" %)Setting range|(% colspan="2" %)(((
1087 -0: F3.55 is set
1088 -
1089 -1: AI1╳F3.55
1090 -
1091 -2: AI2╳F3.55
1092 -
1093 -3: AI3╳F3.55
1094 -
1095 -4: PUL╳F3.55
1096 -
1097 -5: Keyboard potentiometer given ╳F3.55
1098 -
1099 -6: RS485 communication given ╳F3.55
1100 -
1101 -7: Purchase card
1102 -)))
1103 -
1104 -F3.53 is set the same as F3.52, F3.53 is used to limit the speed when reversing, and the corresponding number is given the function code F3.55.
1105 -
1106 -|(% rowspan="2" style="text-align:center" %)F3.54|(% style="text-align:center" %)Torque control positive maximum speed limit|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)50.00Hz
1107 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00 to Upper limit frequency
1108 -|(% rowspan="2" style="text-align:center" %)F3.55|(% style="text-align:center" %)Torque control reversal maximum speed limit|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)50.00Hz
1109 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00 to Upper limit frequency
1110 -
1111 -When function codes F3.52 and F3.53 are set to 0, the maximum speed limit is set by F3.54 and F3.55.
1112 -
1113 -|(% rowspan="2" style="text-align:center" %)F3.56|(% style="text-align:center" %)Speed/torque switching delay|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.01s
1114 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00 to 10.00s
1115 -
1116 -When the speed/torque mode is switched through terminals DI1 to DI4 or F3.46, the switch can be performed only after the delay time set in F3.56.
1117 -
1118 -|(% rowspan="2" style="text-align:center" %)F3.57|(% style="text-align:center" %)Torque acceleration time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.01s
1119 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00 to 10.00s
1120 -|(% rowspan="2" style="text-align:center" %)F3.58|(% style="text-align:center" %)Torque deceleration time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.01s
1121 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00 to 10.00s
1122 -
1123 -In the torque operation mode, the difference between the output torque of the motor and the load torque determines the speed change rate of the motor and the load. Therefore, electricity
1124 -
1125 -The speed of the machine may change rapidly, causing problems such as noise or mechanical overshoot; By setting the torque to control the acceleration and deceleration time, the motor speed can be gently changed. The torque acceleration and deceleration time is based on 2 times the rated torque of the inverter (200%).
1126 -
1127 -|(% rowspan="2" style="text-align:center" %)F3.59|(% style="text-align:center" %)Forward and reverse torque dead zone time|(% style="text-align:center" %)Factory default|(% style="text-align:center" %)0.00s
1128 -|(% style="text-align:center" %)Setting range|(% colspan="2" style="text-align:center" %)0.00 to 650.00s
1129 -
1130 -Used for the transition time waiting at 0.0Hz when the direction changes in torque operating mode.
1131 -
1132 -
1763026906844-539.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Iris
Size
... ... @@ -1,1 +1,0 @@
1 -26.2 KB
Content