欢迎图片

1 VM Series Manual V1.2

Last modified by Mora Zhou on 2023/12/28 10:44

This is VM series V1.2. S/N on the inverter starts from "X0".

Preface

Thank you for choosing WECON VM Series AC Drive.

This user manual introduces the technical specifications, installation instructions, functions and performance of VM Series AC Drive properly. Please read this user manual carefully before carrying out works such as installation, commissioning, maintenance, etc.

You are specially warned to read and understand safety precaution items of this manual before using this product, and to ensure that relevant electrical installation testers’ professional qualification shall be in line with the provisions of the labor supervision department, and the electrical and environmental conditions for product use shall be in conformity with relevant national standards.

Be sure to verify that the wiring is correct before powering on the product. Before starting the product, it is necessary to debug to ensure correct motor rotating direction.

Safety precautions

■ Warning sign

WECON VM 英文 V01_html_f697a083b5da7fc8.png DANGER: Indicates that failure to comply with the notice will result in severe personal injure or even death.

WECON VM 英文 V01_html_b36792972403c101.png WARNING: Indicates that failure to comply with the notice will result in moderate personal injury, property damage or equipment damage.

WARNING

◎Do not install or operate any AC Drive that is damaged or with missing parts. Failing to follow this rule can result in facility damage or severe injury.

◎When installing or handling the AC Drive, please hold the bottom of the product rather than the case only, to prevent its falling and being damaged.

◎Install the AC Drive on nonflammable material like metal, and keep away from flammable or explosive object, heat source, and similar environment. Otherwise, fire may be caused.

◎When AC Drive is installed inside an electrical cabinet or other kind of enclosure, please install fans or other cooling devices, and keep ventilation well enough to ensure the enclosure temperature below 40℃, or the AC Drive may be damaged due to extreme high temperature.

◎Before wiring, ensure the AC Drive rated input voltage and phases are compatible with the input power source, or fire or personal injury may be caused.

◎Never connect the AC power supply to output terminals U, V and W. Otherwise, the AC Drive will be damaged and the warranty is invalid.

◎Never carry out withstand voltage test to the AC Drive, for example by a megohmmeter. Otherwise, it may cause damage to the AC Drive.

◎The connecting cable of the main circuit terminal should use an insulating sleeve.

◎When the cable length between the AC Drive and the motor exceeds 50 meters, an output reactor is recommended to be used.

◎Do not use a circuit breaker to control the start and stop of the AC Drive. Otherwise, the AC Drive may be damaged.

◎Since the AC Drive makes the motor running speed from low to high in a short time, please confirm that the motor and equipment are in the allowed running range before running.

◎Do not touch due to high temperature of the heat sink and braking resistor.

◎The factory parameters of the AC Drive can meet the requirments of most equipment operation. Under normal circumstances, please do not modify the AC Drive parameters at will. Even if there is some special applications need to change the AC Drive parameters, only necessary parameters could be changed. Otherwise, AC Drive damage may be caused.

◎The PCB board has a CMOS integrated circuit. Do not touch it with your hands, otherwise, static electricity will damage the PCB board.

DANGER

◎Wiring must be completed by qualified professional electricians, otherwise, there may be electric shock or damage to the AC Drive.

◎The power must be disconnected during wiring; otherwise, it may cause electric shock or fire.

◎The grounding terminal should be effectively grounded; otherwise, the outer casing of the AC Drive may be energized.

◎Do not touch the main circuit terminals, otherwise, it may cause electric shock.

◎Terminals for brake resistor are and PB. Do not wire to other terminals, otherwise, fire may be caused.

◎It is only allowed to power on the AC Drive after the wiring is finished and its cover is reinstalled. It is strictly prohibited to remove the cover of AC Drive while power is on. Otherwise, it may cause electric shock.

◎Before programming the AC Drive with fault auto reset or restart option after power off, the mechanical device need to be implemented with safety protection measures first. Otherwise, personal injury will be caused.

◎“ STOP/RESET” key may become invalid as a result of some function setting. It is recommended to install an independent emergency circuit breaker for the AC Drive control system, otherwise, or personal injury may be caused.

◎When the power is on, there may be electricity in the AC Drive’s terminals even if it is in stop mode. Do not touch U, V, W terminals and motor connection terminals, or electrical shock may be caused.

◎Never touch the AC Drive connection terminals when power is on. Otherwise, it may cause an electrical shock.

◎Only qualified electricians can be authorized to do the jobs of maintenance, checking, or parts replacement.

◎After the power supply is OFF, make sure the charge LED is OFF and the residual voltage does not exist, or wait for at least 10 minutes before carrying out maintenance or inspection. Otherwise, damage or injury may be caused.

◎Modification to the AC Drive without permission is strictly prohibited, otherwise, severe injury may be caused. Arbitrarily modification of AC Drive will result in service warranty invalid.

Product information

Technical specifications

ItemSpecifications
Control featuresControl modeV/F control
Startup torque0.5Hz/100%
Speed range1: 50
Speed stability accuracy±1%
Carrier frequency1kHz~6kHz;
Overload capacity60s for 150% of the rated current, 1s for 180% of the rated current.
Torque boost0.0%~30.0%
Input and OutputInput voltage range220V/380V; fluctuation range: ±15%
Input frequency range50/60Hz;fluctuation range: ±5%
Output voltage range0-input voltage; the error is less than 5%
Output frequency range0~400Hz
Basic functionRunning command sourceThree command source:keypad; control terminals; serial communication port.
Frequency sourcesuch as digital setting, analog voltage setting, analog current setting, serial communication port setting.
DC braking

Braking time: 0.0s~50.0s;

Braking action current value: 0.0%~100.0%

Simple PLC/Multiple speedsIt implements up to 8 speeds via the simple PLC function or combination of DI terminal states.
Protection modeMotor short-circuit detection at power-on, input/output phase loss protection, overcurrent protection, overvoltage protection, undervoltage protection, overheat protection, overload protection and so on.
Display and Key operationLED displayIt displays the parameters.
Parameters locking functionIt can lock the parameters to prevent malfunction.
EnvironmentInstallation locationIndoor, free from direct sunlight, dust, corrosive gas, combustible gas, oil smoke, vapour, drip or salt.
AltitudeLower than 1000m. When it is higher than 1000m, for every 100m, it needs to reduce power by 1%, and the maximum altitude is 3000m.
Ambient temperature-10℃~50℃. When it is higher than 40℃, for every 1℃, it needs to reduce power by 1%, and the maximum ambient temperature is 50℃
Humidity≤95%RH, without condensing
VibrationLess than 5.9m/s2 (0.6g)
Storage temperature-25℃~+60℃

Table 1-1-1 Technical specification shee

Product nameplate

WECON VM 英文 V01_html_5a52ff18546c8417.png

Figure 1-2-1 Product nameplate

Model description

VM2 S 1R5GB

①        ② ③    ④

FieldNo.IdentificationDescription
Product seriesProduct seriesVM series
Voltage gradeVoltage grade2: 220VAC; 4: 380VAC
The input powerPower phase identificationS: single; T: three-phase
Rated powerPower range1R5-1.5kW,R is the decimal point

Table 1-3-1 VM series model field comment

Product model

AC Drive ModelRated powerPower capacityInput currentOutput currentMotor G/P
kWkVAAAkWHP
VM-2SR750.751.58.240.751
VM-2S1R51.5314.271.52
VM-2S2R22.24239.62.23
VM-4T2R22.245.85.12.23
VM-4T00445.910.594/5.5
VM-4T5R55.58.914.6135.57.5
VM-4T7R57.51120.5177.510
VM-4T011*111726251115
VM-4T015*152135321520

Table 1-4-1 Product model table

*:In development

Installation

Overall structural drawing

unit: mm

1624240220324-243.png

Figure 2-1-1 Outline dimension diagram

AC Drive ModelOverall DimensionsMounting HoleMounting Hole Diameter
HWDH1W1d
VM-2SR7513469104123555
VM-2S1R5
VM-2S2R214272116130595
VM-4T2R2
VM-4T00419695132179795.5
VM-4T5R5225115154208995.5
VM-4T7R5
VM-4T011------
VM-4T015------

Table 2-1-1 outline dimension

Terminal connection

1624240272484-903.png

Figure 2-2-1 Terminal connection

Main circuit connection

Terminal     markNameDescription
R、S、TPower supply input terminalsConnect to the AC power supply
U、V、WAC drive output terminalsConnect the three-phase motor.
WECON VM 英文 V01_html_2b5dc89a424d22e6.pngGrounding terminalMust be grounded.

Table 2-2-1 Main circuit terminals and function

Control circuit connection

CategoryTerminal symbolTerminal nameFunction description
Power supply+10V-GND+10V power supply

Provide +10V power supply to external unit.

Maximum output current: 20 mA.

+24V-COM+24V power supplyProvide +24V power supply to external unit.
Analog inputAI-GNDAnalog input terminal 1Input voltage range: 0-10V
Digital inputDI1Digital input 1 
DI2Digital input 2
DI3Digital input 3
DI4Digital input 4
Relay outputRA-RCNO terminalNO terminal
Communication port and socketS+RS485 signal positive terminal
S-RS485 signal negative terminal

Table 2-2-2 Control terminal instruction

Display and operation

Keypad

You can modify the parameters, monitor the working status and start or stop the AC Drive by operating the keypad, as shown in the following figure.

WECON VM 英文 V01_html_53c6de9f2105008c.png

Figure 3-1-1 Keypad diagram

Description of indicators and keys

ItemNameFunction
IndicatorStatus
  • RUN: ON/Running; OFF/Stop.
  • REMOTE: ON/Terminal control; Blinking/Communication; OFF/keypad control.
  • FWD/REV: ON/Forward rotation; OFF/Reverse rotation; Blinking/Forward and reverse switching.
  • ALARM: Blinking /Fault state.
Keys

PRG (Programming)

Enter or exit the first menu.
ENT (Confirm)Enter the menu interfaces and confirm the parameter setting.
△(Increment)Increase date or function code.
▽(Decrement)Decrease data or function code.
<<(Shift)Select the displayed parameters in the stop or running state and select the digit to be modified when modifying parameters.
RUN/STOP

Control drive start and stop in keypad control mode.

Perform the reset operation when it is in the fault state.

PotentiometerResistance potentiometerFrequency adjustment in keyboard operation mode

Table 3-2-1 Description of Indicators and key

Parameter function

  • “○”: the parameter can be modified in both standby and operating state;
  • “●”: the parameter can’t be modified in operating state;
  • “◎”:the parameter is the actual detected and recorded value which can’t be modified;

Note: the communication address is hexadecimal.

Functional parameter

ParameterNameSetting RangeDefaultPropertyAddress
F0.00ReservedReserved00000
F0.01Command source selection
  • 0:Operation panel control(LED off)
  • 1:Terminal control(LED on)
  • 2:Communication LED (LED blinking)
00001
F0.02Setting main frequency source X
  • 0:Digital setting (non-retentive at power failure)
  • 1:Digital setting (retentive at power failure)
  • 2:Keypad Knob
  • 3:AI
  • 4:Multi-stage speed
  • 5:Simple PLC
  • 6:Communication
20002
F0.03Keypad setting frequency0.00Hz~F0.0550.0Hz0003
F0.04Running direction selection
  • 0:Forward
  • 1:Reverse
00004
F0.05Maximum Output Frequency50.00Hz~400.00Hz50.0Hz0005
F0.06Upper Limit of FrequencyF0.07~F0.0550.0Hz0006
F0.07Lower Limit of Frequency0.00Hz~F0.060.0Hz0007
F0.08The option of frequency lower limit
  • 0:Running at frequency lower limit
  • 1:Stop
  • 2:Standby
00008
F0.09Carrier Frequency1kHz~6.0kHz6.0kHz0009
F0.10Acceleration Time 10.0s~100.0s10.0s000A
F0.11Deceleration Time 10.0s~100.0s10.0s000B
F0.12Stop Mode
  • 0:Decelerate to stop
  • 1:Free stop
0000C
F0.13Retentive of digital setting frequency
  • 0:No retentive
  • 1:retentive
1000D
F0.14Fan operating mode
  • 0:Run when motor is running
  • 1:Keep run when power on
0000E
F0.15AI1 Input Option
  • 0: 0-10V
  • 1: 4-20mA
  • 2: 0-20mA
  • 3: 0-5V
  • 4: 0.5-4.5V
0000F
F1.00Default Setting Restoring
  • 0: No Operation
  • 1: Restore to factory default setting (not including F2 parameters)
  • 2: Clear error records
00100
F1.01Parameters Lockup
  • 0: Invalid
  • 1: Valid
00101
F1.02User Password0~6500000102
F2.00Motor Rated Power0.1kW~2.2kWDetermined by Drive Model0200
F2.01Motor Rated Voltage0~380VDetermined by Drive Model0201
F2.02Motor Rated Frequency0~ F0.05Determined by Drive Model0202
F2.03Motor Rated Current1.00~10.00Determined by Drive Model0203
F2.05Type of Motor
  • 0: Three Phase
  • 1: Single Phase
00205
F2.06Single-phase motor main and auxiliary winding turns ratio10~200800206
F2.07Single-phase motor current correction factor50~2001300207
F4.00Torque Boost0.0%~30.0%4.0%0400
F4.01Cut-off frequency of torque boost0.00Hz~F0.0550.00Hz0401
F4.02Trigging frequency of DC braking at stop0.00Hz~F0.050.00Hz0402
F4.03Delay time of DC braking at stop0.0s~50.0s0.0s0403
F4.04The current of DC braking at stop0~100%00404
F4.05The time of DC braking at stop0.0s~50.0s0.0s0405
F4.06Automatic adjustment of carrier Frequency
  • 0: Invalid;
  • 1: Valid
00406
F4.070 frequency output option
  • 0: Valid;
  • 1: Invalid
10407
F5.00DI1 terminal function selection
  • 0: No function
  • 1: Forward running (FWD)
  • 2: Reverse running (REV)
  • 3: Three-wire operation control
  • 4: Forward point movement (FJOG)
  • 5: Reverse point movement (RJOG)
  • 6: Error Reset
  • 7: Terminal UP
  • 8: Terminal Down
  • 9: UP/DOWN Setting Clear
  • 10: External error input(Normally Open)
  • 11: PLC Status reset
  • 12: Multi stage speed terminal 1
  • 13: Multi stage speed terminal 2
  • 14: Reserved
10500
F5.01DI2 terminal function selection20501
F5.02DI3 terminal function selection60502
F5.03DI4 terminal function selection00503
F5.04DI filter time0.000s~1.000s0.010s0504
F5.05Terminal Command Option
  • 0: Two-line mode 1
  • 1: Two-line mode 2
  • 2: Three-line mode 1
  • 3: Three-line mode 2
00505
F5.06UP/DOWN change rate range0.01Hz~50.00Hz0.50Hz0506
F5.07AI minimum input0.00V~F5.090.00V0507
F5.08Percentage rate of AI minimum input-100.0%~+100.0%0.0%0508
F5.09AI maximum inputF5.07~+10.00V10.00V0509
F5.10Percentage rate of AI maximum input-100.0%~+100.0%100.0%050A
F5.11AI filter time0.00s~10.00s0.10s050B
F5.12DI1 Enable Delay Time0.0s~100.0s0.0s050C
F5.13DI2 Enable Delay Time0.0s~100.0s0.0s050D
F5.14DI1 Disable Delay Time0.0s~100.0s0.0s050E
F5.15DI2 Disable Delay Time0.0s~100.0s0.0s050F
F5.16AI Input Digital Functional Option
  • 0: No function
  • 1: Forward running (FWD)
  • 2: Reverse running (REV)
  • 3: Three-wire operation control
  • 4: Forward point movement (FJOG)
  • 5: Reverse point movement (RJOG)
  • 6: Error Reset
  • 7: Terminal UP
  • 8: Terminal Down
  • 9: UP/DOWN Setting Clear
  • 10: External error input(Normally Open)
  • 11: PLC Status reset
  • 12: Multi stage speed terminal 1
  • 13: Multi stage speed terminal 2
  • 14: Reserved
00510
F5.17AI Input Valid Level Option
  • 0: Low Level Valid
  • 1: High Level Valid
10511
F6.00Relay Output Option
  • 0: No Output
  • 1: VFD Running
  • 2: Error Output(Output is valid only after VFD stops)
  • 3: Ready for Running
  • 4: Communication Setting
  • 5: User Defined Output
00600
F6.01Relay1 Closed Delay Time0.0s~100.0s0.0s0601
F6.02Relay1 Open Delay Time0.0s~100.0s0.0s0602
F6.03

User defined output

Variability option(EX)

  • 0: Running Frequency
  • 1: Set Frequency
  • 2: Bus Voltage
  • 3: Output Voltage
  • 4: Output Current
00603
F6.04User defined comparison methodUnits digit:comparison test method
  • 0: Equal (EX==X1)
  • 1: Equal or greater than
  • 2: Equal or less than
  • 3: Interval comparison (X1≤EX≤X2)
  • 4: Units digit test (EX&X1=X2)

Tens digit: output method

  • 0: False value output
  • 1: Real value output
00604
F6.05User defined output dead zone0~6553500605
F6.06

User-defined output

comparison value 1

0~6553500606
F6.07

User-defined output

comparison value 2

0~6553500607
F6.08AO1 Output Option
  • 0: Running Frequency(0~F0.05)
  • 1: Set Frequency(0~F0.05)
  • 2: Output Current(0~Double Rated Current of VFD)
  • 3: Output Voltage(0~1.2times of VFD Rated Output Voltage)
  • 4: AI(0~10V)
  • 5: Bus Voltage(0~500.0/1000.0V)
00608
F6.09AO2 Output Option00609
F6.10AO1 offset coefficient-100.0%~+100.0%0.0%060A
F6.11AO1 gain-10.00~+10.001.00060B
F6.12AO2 offset coefficient-100.0%~+100.0%0.0%060C
F6.13AO2 offset coefficient-10.00~+10.001.00060D
F7.00ReservedReserved00700
F7.01STOP Button Function
  • 0: Valid only at keypad control mode
  • 1: Valid at all control modes
10701
F7.02LED display parameters at running status
  • Bit0: Running Frequency(Hz)
  • Bit1: Set Frequency(Hz)
  • Bit2: Bus Voltage(V)
  • Bit3: Output Voltage(V)
  • Bit4: Output Current(A)
  • Bit5: DI Input Status
  • Bit6: DO Output Status
  • Bit7: Keypad Knob Voltage(V)
  • Bit8: AIVoltage(V)
  • Bit9: Load Speed
  • Bit10: PID Set Value
  • Bit11: PID Feedback Value
  • Bit12: PLC Stage
  • Bit13: Feedback Frequency(Unit:0.1Hz)
  • Bit14: Communication Set Value
  • Bit15: Main Frequency Source X
0x1F0702
F7.03LED display parameters at stop status0x060703
F7.04Load speed display coefficient0.0001~6.50003.0000704
F7.05Software Version--0705
F8.00Jog Running Frequency0.00Hz~F0.052.00Hz0800
F8.01Jog Acceleration Time0.0s~100.0s10.0s0801
F8.02Jog Deceleration Time0.0s~100.0s10.0s0802
F8.03FWD/REV dead zone time0.0s~100.0s0.0s0803
F8.04Reverse control
  • 0: valid
  • 1: invalid
00804
F8.05Reserved000805
F8.06Startup Protection Option
  • 0:Invalid
  • 1:Valid
00806
F8.07Terminal jogging priority
  • 0: Invalid
  • 1: Valid
10807
FC.00Local Addresse1~30,0 for broadcast addresse10C00
FC.01Baud Rate
  • 0: 4800bPS
  • 1: 9600bPS
  • 2: 19200bPS
10C01
FC.02Data format
  • 0: No check, data format (8.N.1)
  • 1: Odd Parity check, data format (8.O.1)
  • 2: Even parity check, data format (8.E.1)
00C02
FC.03Respond Delay0ms~20ms20C03
FC.04Reserved000C04
FD.00Multistage speed 0-100.0%~100.0%(100.0% as F0.05)0.00%0D00
FD.01Multistage speed 1-100.0%~100.0%0.00%0D01
FD.02Multistage speed 2-100.0%~100.0%0.00%0D02
FD.03Multistage speed 3-100.0%~100.0%0.00%0D03
FD.04Simple PLC running mode
  • 0: Stop after the AC Drive runs one cycle
  • 1: Keep final values after the AC Drive runs one cycle
  • 2: Repeat after the AC Drive runs one cycle
00D04
FD.05Simple PLC retentive optionUnits Digit: Reserved
Tens Digit:
  •  0: Invalid
  •  1: Valid
00D05
FD.06Running time of simple PLC reference 00.0s(h)~100.0s(h)0.0s(h)0D06
FD.07Acceleration/deceleration time of simple PLC reference 00~300D07
FD.08Running time of simple PLC reference 10.0~100.00.0s(h)0D08
FD.09Acceleration/deceleration time of simple PLC reference 10~300D09
FD.10Running time of simple PLC reference 20.0 ~100.00.0s(h)0D0A
FD.11Acceleration/deceleration time of simple PLC reference 20~300D0B
FD.12Running time of simple PLC reference 30.0~100.00.0s(h)0D0C
FD.13Acceleration/deceleration time of simple PLC reference 30~300D0D
FD.14Time unit of simple PLC running
  • 0: s(second)
  • 1: h(hour)
  • 2: min(minute)
00D0E
FD.15The source of multistage speed 0
  • 0: Set by FD.00
  • 1: AI
00D0F

Monitoring Parameters

ParameterNameMinimum UnitPriorityAddress
D0.00Running Frequency(Hz)0.01HzD000
D0.01Set Frequency(Hz)0.01HzD001
D0.02Bus Voltage(V)0.1VD002
D0.03Output Voltage(V)1VD003
D0.04Output Current(A)0.01AD004
D0.05IGBT Module Temperature(℃)0.1℃D005
D0.06DI Input Status1D006
D0.07DO Output Status1D007
D0.08Keypad Knob Voltage0.01VD008
D0.09AI Voltage(V)0.01VD009
D0.10Reserved1D010
D0.13PLC Stage1D013
D0.14Feedback Speed(Unit0.1Hz)0.1HzD014

Error Records

ParameterNameRange and DescriptionPriorityAddress
E0.00Latest error type
  • No Error: 0
  • Acceleration Over Current: Err02
  • Deceleration Over Current: Err03
  • Over Current at constant speed: Err04
  • Acceleration Over Voltage: Err05
  • Deceleration Over Voltage: Err06
  • Over Voltage at constant speed: Err07
  • Low Voltage error: Err09
  • VFD overload: Err10
  • Motor overload: Err11
  • IGBT overheat: Err14
  • External Error: Err15
  • Current Detection Error: Err18
  • Parameter writing/reading error: Err21
  • EEPROM writing/reading error: Err22
 E000
E0.01Running Frequency at latest error0.0Hz~F0.05 E001
E0.02Output Current at latest error0.00~655.35 E002
E0.03Bus Voltage at latest error0.0~810 E003
E0.04Input terminals status at latest error0~63 E004
E0.05IGBT temperature at latest error0~65535 E005
E1.00Former error typeAs E0.00 E100
E1.01Running Frequency at former error0.0Hz~F0.05 E101
E1.02Output Current at former error0.00~655.35 E102
E1.03Bus Voltage at former error0.0~810 E103
E1.04Input terminals status at former error0~63 E104
E1.05IGBT temperature at former error0~65535 E105

Communication Protocol

VM Series AC Drive provides RS485 communication interface and supports Modbus communication protocol. Users can achieve centralized control by computer or PLC, set AC Drive operation commands, modify or read function code parameters, read the working state and fault info of the AC Drive.

Communication Control Address

FunctionAddressDescriptionRemarksCharacteristic
Communication Set Value1000H-10000~10000 (with ± sign)F0.05* (±100.00%)R/W
Control Command2000H0001: Forward running-W
0002: Reverse running-W
0003: JOG forward-W
0004: JOG reverse-W
0005: Free stop-W
0006: Deceleration stop-W
0007: Fault reset-W
Running Status3000H0001: FWD running-R
0002: REV running-R
0003: Stopped-R
Monitoring Data1001HRunning Frequency(Hz)2 decimal placesR
1002HSet Frequency(Hz)2 decimal placesR
1003HBus Voltage(V)1 decimal placeR
1004HOutput Voltage(V)1 decimal placeR
1005HOutput Current(A)2 decimal placesR
1006HIGBT Temperature1 decimal placeR
1007HDigital input statusDI1-DI4 Added by binary bit weightR
1009HKeypad Knob Voltage(V)1 decimal placeR
101AHAI Volatage (V)1 decimal placeR
100BHLoad Speed Display1 decimal placeR
100EHPLC StageSimple PLC running stageR
Failure status8000H0000: No error-R
0002: Acceleration Over Current-R
0003: Acceleration Over Current-R
0004: Over Current at Constant Speed-R
0005: Acceleration Over Voltage-R
0006: Deceleration Over Voltage-R
0007: Over Voltage at Constant Speed-R
0009: Low Voltage Error-R
000A: VFD Overload-R
000B: Motor Overload-R
000E: IGBT Overheat-R
000F: External Error-R
0012: Current Detection Error-R
0015: Parameters Writing/Reading Error-R
Communication Error Feedback8001H0000: No Error-R
0001: Password Error-R
0002: Command Code Error-R
0003: CRCError-R
0004: Invalid Address-R
0005: Invalid Parameter-R
0006: Parameters Adjustment Failed-R
0007: System Locked-R
0008: Parameters Being Saved-R

Sheet 5-1-1 Control Command Addresses

EEPROM Addresses Introduction

The addresses listed in the sheet above is the way of writing RAM. The RAM stores the data after power-off and does not save it. In the communication mode, for the write command "06H", if the parameter needs to be stored after power-off, the method of writing EEPROM should be used. The original "0" of the most significant bit of the RAM address is changed to "F", which is converted into the corresponding EEPROM address, for example: "0XXX" is changed to "FXXX"

Example of address conversion: Upper limit frequency F006, write RAM communication address: 0006, corresponding EEPROM address: F006.

Acceleration time F010, the communication address for writing RAM is: 000A, and the corresponding address for EEPROM is: F00A.

Other parameters, are like that...

It should be noted that the erasing life of EEPROM is about 1 million times. After exceeding the erasing times, it will affect the reliability of data storage. If it is not necessary, it is recommended to control the communication by writing to RAM.

Troubleshooting & countermeasures

Faults and solutions

Fault codeFault typeReasonSolution
Err02Overcurrent during acceleration

1. The output circuit of AC Drive is grounded or short circuited.

2. The acceleration time is too short.

3. The startup operation is performed on the rotating motor.

4. The AC Drive model is of too small power.

1. Eliminate external faults.

2. Increase the acceleration time.

3. Select rotational speed tracking restart or start the motor after it stops.

4. Select the AC Drive of higher power.

Err03Overcurrent during deceleration

1. The output circuit of AC Drive is grounded or short circuited.

2. The deceleration time is too short.

1. Eliminate external faults.

2. Increase the deceleration time.

Err04Overcurrent at constant speed

1. The output circuit of AC Drive is grounded or short circuited.

2. The AC Drive model is of too small power.

1. Eliminate external faults.

2. Select the AC Drive of higher power.

Err05Overvoltage during acceleration

1. Input voltage abnormal.

2. An external force drives the motor during acceleration.

3. The acceleration time is too short.

4. The braking unit and braking resistor are not installed.

1. Turn the input power to the normal range.

2. Cancel the external force.

3. Increase the acceleration time.

4. Installed the braking unit and braking resistor.

Err06Overvoltage during deceleration

1. Input voltage abnormal.

2. An external force drives the motor during deceleration.

3. The deceleration time is too short.

4. The braking unit and braking resistor are not installed.

1. Turn the input power to the normal range.

2. Cancel the external force.

3. Increase the deceleration time.

4. Installed the braking unit and braking resistor.

Err07Overvoltage at constant speed

1. Input voltage abnormal.

2. An external force drives the motor during deceleration.

1. Turn the input power to the normal range.

2. Cancel the external force.

Err09Undervoltage

1. Instantaneous power failure occurs on the input supply.

2. The input voltage is not within the normal range.

3. The AC Drive has an abnormality.

1. Reset the fault.

2. Adjust the input voltage to normal range.

3. Looking for technical service.

Err10AC Drive overload

1. The load is too heavy or lockedrotor occurs on motor.

2. The AC Drive model is of too small power.

1. Reduce the load and check the motor.

2. Select the AC Drive of higher power.

Err11Motor overload

The parameter setting of F2.03 does not match the motor

2. The AC Drive model is of too small power.

1. Set this parameter correctly.

2. Reduce the load and check the motor.

Err14Module overheating

1. The ambient temperature is too high.

2. The air filter is blocked.

3. The fan is damaged.

4. The IGBT is damaged.

1. Lower the ambient temperature.

2. Clean the air filter.

3. Replace the fan.

4. Ask for technical service.

Err15External equipment faultExternal fault signal (DI) triggers1. Check the input DI terminal
Err16Communication fault

1. The PC is in abnormal state.

2. The communication cable is faulty.

3. The communication parameters of FC group are set improperly.

1. Check the cabling of the PC.

2. Check the communication cabling.

3. Set the communication parameters properly.

Err18Current detection fault

1. Current detection circuit is abnormal.

2. Control circuit is abnormal.

1. Ask for technical service.
Err21Data overflow1. The control board is abnormal.1. Ask for technical service.
Err22On-power EEPROM check fault1. The EEPROM chip is damaged.1. Ask for technical service.

Table 6-1-1 Faults and solutions

Common faults and solutions

SNFaultPossible causesSolutions
1No display at power-on state

1. The input power of AC Drive is abnormal.

2. The control board has a bad contact with cable that is connected to the keypad.

3. The AC Drive is abnormal.

1. Check the input power.

2. Re-connect the cable.

3. Ask for technical service.

2The motor does not rotate after the AC Drive runs.

1. The motor is damaged.

2. The motor cables is abnormal.

3. The cable between the drive board and control board is in poor contact.

4. The AC Drive is abnormal.

1. Replay the motor.

2. Ensure the cable between the AC Drive and the motor is normal.

3. Check the cable between the drive board and control board.

4. Ask for technical service.

3DI termianls are disabled.

1. The parameters are set incorrectly.

2. The external signal is incorrect.

3. The control board is abnormal.

1. Check and reset the parameters in group F5.

2. Re-connect the external signal cables.

3. Ask for technical service.

4AC Drive interference

1. Carrier frequency setting is not suitable.

2. The grounding method of the AC Drive and the motor is incorrect.

3. The wire between the AC Drive and the motor is too long.

1. Reduce the carrier frequency

2. The AC Drive and the motor are effectively grounded and separated from the ground of the peripheral device.

3. Install out reactor or reduce wire distance.

5Motor noise is too loud.

1. Motor damage or mechanical failure.

2. Carrier frequency setting is too small.

1. Replace the motor or clear the mechanical fault.

2. Increase the carrier frequency appropriately.

6Switch trip

1. Installed a leakage switch or an air switch overload.

2. The input power of AC Drive is abnormal.

3. The AC Drive is damaged.

1. Replay the leakage switch or replay the larfer capacity air switch.

2. Eliminate whether the input power is shorted.

3. Ask for technical service.

Table 6-2-1 Common faults and solutions