LX6V Series
Naming rules

| Model | Description |
| LX6V-0808EXYT | 8-channel switch input and 8-channel transistor output. Input supports NPN or PNP. Output supports NPN. |
| LX6V-16EX | 16-channel switch input; Input supports NPN or PNP. |
| LX6V-16EYT | 16-channel transistor output; Output supports NPN. |
| LX6V-16EYP | 16-channel transistor output, outputs support PNP type. |
| LX6V-16EYP-3A | 16-channel transistor output, outputs support PNP type, single output supports a maximum current of 3A. |
| Model | Function description |
| LX6V-1616EXYT | 16-channel switch input, 16-channel transistor output; Support NPN or PNP input, support NPN output. |
| LX6V-1616EXYP | 16-channel switch input, 16-channel transistor output; Support NPN or PNP input, support PNP output. |
| LX6V-32EYT | 32-channel NPN transistor output; |
| LX6V-32EYP | 32-channel transistor output; outputs support PNP type. |
| LX6V-32EX | 32-channel switch input; Support NPN or PNP input; |
Equipment specifications and wiring description
Appearance and size
| Category | Model | Size |
| 16-point I/O expansion module | LX6V-0808EXYT | 91.2*28.4*95.1 mm |
| LX6V-0808EXYP | ||
| LX6V-16EX | ||
| LX6V-16EYT | ||
| LX6V-16EYP | ||
| LX6V-16EYP-3A | 91.2*39.3*95.1 mm | |
| 32-point I/O expansion module | LX6V-1616EXYT | 91.2*39.3*95.1 mm |
| LX6V-1616EXYP | ||
| LX6V-32EYT | ||
| LX6V-32EYP | ||
| LX6V-32EX |
The outline and dimensions of the 16-point I/O expansion module are shown in the figure below:

① I/O LED;② I/O terminal;③ Expansion module interface; ④ Installation hole: 2 (Φ4.5) ;
⑤ DIN rail fastener
The outline and dimensions of the LX6V-16EYP-3A expansion module and the 32-point I/O expansion module are shown in the figure below:

① I/O LED;② I/O terminal;③ Expansion module interface; ④ Installation hole: 2 (Φ4.5) ;
⑤ DIN rail fastener
Terminal description
Terminal block arrangement of I/O expansion module as follows:
| 16-channel module models | LX6V-0808EXYT LX6V-0808EXYP | LX6V-16EX | LX6V-16EYT LX6V-16EYP | LX6V-16EYP-3A |
| Terminal arrangement | ![]() | ![]() | ![]() | ![]() |
| 32-channel module models | LX6V-32EYT LX6V-32EYP | LX6V-32EX | LX6V-1616EXYT LX6V-1616EXYP |
| Terminal arrangement | ![]() | ![]() | ![]() |
Installation
Please install the end cover on the right side of the last expansion module. Align it with the module interface slot and connect it, as shown in the figure below:


Cable selection and wiring requirements
The interface of the LX6 series digital I/O expansion module uses plug-in screwless terminal blocks. The cable requirements for different specifications of terminal blocks are as follows:
| Category | Module type | Rated connection capacity | Insertion terminal length |
| 16-point I/O expansion module | LX6V-0808EXYT | 0.2 to 1.0 mm2 (IEC61984 data) | 10 mm |
| LX6V-16EX | |||
| LX6V-16EYT | |||
| LX6V-16EYP | |||
| LX6V-16EYP-3A | 0.12 to 1.5 mm2 (EC61984 data) | ||
| 32-point I/O expansion module | LX6V-1616EXYT | 0.12 to 1.5 mm2 (IEC61984 data) | |
| LX6V-1616EXYP | |||
| LX6V-32EYT | |||
| LX6V-32EX |
Parameter Specification
Input specification
| Item | Digital input |
|---|---|
| Input circuit composition |
NPN connection: S/S connect to 24 V; PNP connection: S/S connect to 0 V. ✎Note: This is NPN connection in the picture. |
| Input signal voltage | DC ± 24 V ±10% |
| Input signal current | 7 mA/DC 24 V (The input current when inputting standard 24 V) |
| Input ON Current | Above 3.5 mA |
| Input OFF Current | Below 1.5 mA |
| Input response time | Approx. 0.2 ms |
| Input signal form | Contact input, support NPN, PNP input |
| Circuit insulation | 16-channel I/O module: Transformer isolation 32-channel I/O module: Transformer isolation / Optical isolation |
| Action display | When inputting ON, LED lights up. |
Output specification
General I/O expansion module
| Item | Transistor output | ||
|---|---|---|---|
| Output circuit composition |
| ||
| External power supply | DC5 to 30V | ||
| Circuit insulation | Transformer isolation | ||
| Action display | LED lights up when driving. | ||
Maximum load
| Resistance load | 16-channel I/O module: 0.4 A/1 point 32-channel I/O module: 0.25 A / point, 8 A /module | |
| Inductive load | 16-channel I/O module: 0.4A/1 point 32-channel I/O module: DC 24 V 6 W /point | ||
| Lamp load | 16-channel I/O module: DC24 V 0.9 W /point 32-channel I/O module: DC24 V 6 W /point | ||
| Open circuit leakage current | 0.1 mA/DC30V | ||
| Minimum load | - | ||
Response Time | OFF → ON | Approx. 0.2 ms | |
| ON → OFF | Approx. 0.2 ms | ||
LX6V-16EYP-3A expansion module
| Item | Transistor output |
| Quantity/Wiring | 16 Y outputs, 4 points per common/group, each group with a separate power supply. |
| Input signal voltage | 24 V DC |
| Input signal current | 3 A 50% simultaneity per group |
| Protection device | Overload protection for every 4 Y points |
| Operation indication | LED lights up when input is ON |
| Circuit insulation | Isolation between groups |
✎Note: When connecting the LX6V-16EYP-3A module outputs to high-current loads, wire the ground loop directly to the external power supply terminal. Never connect it to the module's 0V terminal, as this will cause mainboard overheating.
Environment specification
| Item | Specification requirements | ||||
| Usage environment | No corrosive, flammable gas, no large amount of conductive dust | ||||
| Environment temperature (Running) | 0℃ to 55℃ | ||||
| Environment humidity (Running) | 35 to 85% RH (No condensation) | ||||
| Installation | 1. Snap mount on IEC/EN 60715 standard TH35 rail (35 mm width, 1 mm backplate thickness) 2. Direct positioning hole mount | ||||
| Vibration resistance | Complies with JIS C0040 Standard | ||||
| Mounting method | Frequency | Acceleration | Amplitude | X, Y, Z 10 times in each of three directions (80 minutes in each direction) | |
| DIN rail installation | 10 to 57 Hz | -- | 0.035 mm | ||
| 57 to 150 Hz | 4.9 m/s² | -- | |||
| Direct installation | 10 to 57 Hz | -- | 0.075 mm | ||
| 57 to 150 Hz | 9.8 m/s² | -- | |||
| Shock resistance | Compliant with JISC0041 standard (147 m/s2, action time 11 ms, three sinusoidal half to wave pulses in each of X, Y, and Z directions) | ||||
| EMC immunity level | Zone B IEC 61131-2 | ||||
| Altitude requirements | ≤ 2000 m (80 kPa) | ||||
| Protection level | IP20 | ||||
| Grounding | Do not share the grounding with the power system | ||||
Software specification
Input point:
| Item | Specification requirements |
| Input port filtering time | As host extension: 0 ms to 64 ms (Unit: ms, default settings: 10), each group has 4 DI points, sharing the same filter parameters. As LX6V-EMB(C)-ECAT extension: 0 to 640 (Unit: 100 us, default setting: 10), each group has 8 DI points, sharing the same filter parameters. |
| Input port anomaly detection and indication | N/A |
| Input channel logic level configuration | N/A |
| Independent channel enable configuration | N/A |
| Diagnostic reporting function configuration | N/A |
| I/O Mapping | Support three I/O mapping modes: bit access, byte access, word access |
Output point:
| Item | Specification requirements |
| Output port anomaly detection and indication | N/A |
| Output channel logic level configuration | N/A |
| Independent channel enable configuration | N/A |
| Diagnostic reporting function configuration | N/A |
| I/O mapping | Supports three I/O mapping modes: bit access, byte access, word access |
Instructions
This module is applicable to the LX6V series PLC and LX6V-EM-ECAT module device. The following is an introduction to these 2 usages.
Use on LX6V/LX6S
Upper computer expansion module configuration process instructions (Take the model LX6V-0808EXYT as an example).
① Double-click on the [Extension module configuration] to open the configuration interface;
② Double-click the corresponding module to add a new one according to the model and position of the modules connected to the current host.
③ Double-click the module in the current machine slot to open the [Module configuration] interface;

④ Configure modules sequentially: DI point filtering time and I/O mapping. Click [OK] and save the configuration;


Filter time: The default configuration filter time here is 10ms, configurable range: 0 to 64ms.
I/O Mapping: Module DI points and DO points are sequentially mapped to PLC DI10 to DI17, DO10 to DO17.
✎Note: Due to the current host LX6V-0808MT, DI0 to DI7 and DO0 to DO7 have been occupied by the host, so the module channel mapping device starts from DI10 and DO10 to allow configuration!
⑤ Click [Write to PLC], select extension functions on the interface in sequence, then click [Execute] to download the extension module configuration to the PLC.

Use in LX6V-EM□-ECAT module
Example

Example description
① After configuring the module and I/O mapping by using the expansion module configuration interface, the X point of the module can be monitored or the Y point state of the module can be set directly through the ladder diagram;
② When M0 is set to ON, Y10~Y17 will be set as the lower 8 bits status of D50;