LX6V Series

Version 3.1 by Jiahao Lai on 2026/11/25 14:55

Naming rules

1795587947718-795.png

ModelDescription
LX6V-0808EXYT8-channel switch input and 8-channel transistor output. Input supports NPN or PNP. Output supports NPN.
LX6V-16EX16-channel switch input; Input supports NPN or PNP.
LX6V-16EYT16-channel transistor output; Output supports NPN.
LX6V-16EYP16-channel transistor output, outputs support PNP type.
LX6V-16EYP-3A16-channel transistor output, outputs support PNP type, single output supports a maximum current of 3A.
ModelFunction description
LX6V-1616EXYT16-channel switch input, 16-channel transistor output; Support NPN or PNP input, support NPN output.
LX6V-1616EXYP16-channel switch input, 16-channel transistor output; Support NPN or PNP input, support PNP output.
LX6V-32EYT32-channel NPN transistor output;
LX6V-32EYP32-channel transistor output; outputs support PNP type.
LX6V-32EX32-channel switch input; Support NPN or PNP input;

Equipment specifications and wiring description

Appearance and size

CategoryModelSize
16-point I/O expansion moduleLX6V-0808EXYT91.2*28.4*95.1 mm
LX6V-0808EXYP
LX6V-16EX
LX6V-16EYT
LX6V-16EYP
LX6V-16EYP-3A91.2*39.3*95.1 mm
32-point I/O expansion moduleLX6V-1616EXYT91.2*39.3*95.1 mm
LX6V-1616EXYP
LX6V-32EYT
LX6V-32EYP
LX6V-32EX

 The outline and dimensions of the 16-point I/O expansion module are shown in the figure below:

1795587934783-401.png

① I/O LED;② I/O terminal;③ Expansion module interface; ④ Installation hole: 2 (Φ4.5) ;

⑤ DIN rail fastener

The outline and dimensions of the LX6V-16EYP-3A expansion module and the 32-point I/O expansion module are shown in the  figure below:

1795588012661-944.png

① I/O LED;② I/O terminal;③ Expansion module interface; ④ Installation hole: 2 (Φ4.5) ;

⑤ DIN rail fastener

Terminal description

Terminal block arrangement of I/O expansion module as follows:

16-channel module models

LX6V-0808EXYT

LX6V-0808EXYP

LX6V-16EX

LX6V-16EYT

LX6V-16EYP

LX6V-16EYP-3A
Terminal arrangement1795588160386-773.png1795588164192-206.png1795588167492-987.png1795588171429-702.png
32-channel module models

LX6V-32EYT

LX6V-32EYP

LX6V-32EX

LX6V-1616EXYT

LX6V-1616EXYP

Terminal arrangement1795588391390-773.png1795588394240-590.png1795588396368-857.png

Installation

Please install the end cover on the right side of the last expansion module. Align it with the module interface slot and connect it, as shown in the figure below:

1795588425690-423.png

1795588434568-938.png

Cable selection and wiring requirements

The interface of the LX6 series digital I/O expansion module uses plug-in screwless terminal blocks. The cable requirements for different specifications of terminal blocks are as follows:

CategoryModule typeRated connection capacityInsertion terminal length
16-point I/O expansion moduleLX6V-0808EXYT0.2 to 1.0 mm2 (IEC61984 data)10 mm
LX6V-16EX
LX6V-16EYT
LX6V-16EYP
LX6V-16EYP-3A0.12 to 1.5 mm2 (EC61984 data)
32-point I/O expansion moduleLX6V-1616EXYT0.12 to 1.5 mm2 (IEC61984 data)
LX6V-1616EXYP
LX6V-32EYT
LX6V-32EX

Parameter Specification

Input specification

ItemDigital input
Input circuit composition

61.png

NPN connection: S/S connect to 24 V;

PNP connection: S/S connect to 0 V.

✎Note: This is NPN connection in the picture.

Input signal voltageDC ± 24 V ±10%
Input signal current7 mA/DC 24 V (The input current when inputting standard 24 V)
Input ON CurrentAbove 3.5 mA
Input OFF CurrentBelow 1.5 mA
Input response timeApprox. 0.2 ms
Input signal formContact input, support NPN, PNP input
Circuit insulation

16-channel I/O module: Transformer isolation

32-channel I/O module: Transformer isolation / Optical isolation

Action displayWhen inputting ON, LED lights up.

Output specification

General I/O expansion module

ItemTransistor output
Output circuit composition

1795588710271-618.png

External power supplyDC5 to 30V
Circuit insulationTransformer isolation
Action displayLED lights up when driving.

Maximum load

 

Resistance load

16-channel I/O module: 0.4 A/1 point

32-channel I/O module: 0.25 A / point, 8 A /module

Inductive load

16-channel I/O module: 0.4A/1 point

32-channel I/O module: DC 24 V 6 W /point

Lamp load

16-channel I/O module: DC24 V 0.9 W /point

32-channel I/O module: DC24 V 6 W /point

Open circuit leakage current0.1 mA/DC30V
Minimum load-

Response

Time

OFF → ONApprox. 0.2 ms
ON → OFFApprox. 0.2 ms

LX6V-16EYP-3A expansion module

ItemTransistor output
Quantity/Wiring16 Y outputs, 4 points per common/group, each group with a separate power supply.
Input signal voltage24 V DC
Input signal current3 A 50% simultaneity per group
Protection deviceOverload protection for every 4 Y points
Operation indicationLED lights up when input is ON
Circuit insulationIsolation between groups

✎Note: When connecting the LX6V-16EYP-3A module outputs to high-current loads, wire the ground loop directly to the external power supply terminal. Never connect it to the module's 0V terminal, as this will cause mainboard overheating.

Environment specification

ItemSpecification requirements
Usage environmentNo corrosive, flammable gas, no large amount of conductive dust
Environment temperature (Running)0℃ to 55℃
Environment humidity (Running)35 to 85% RH (No condensation)
Installation

1. Snap mount on IEC/EN 60715 standard TH35 rail (35 mm width, 1 mm backplate thickness)

2. Direct positioning hole mount

Vibration resistanceComplies with JIS C0040 Standard
Mounting methodFrequencyAccelerationAmplitude

X, Y, Z

10 times in each of three directions

(80 minutes in each direction)

DIN rail installation10 to 57 Hz--0.035 mm
57 to 150 Hz4.9 m/s²--
Direct installation10 to 57 Hz--0.075 mm
57 to 150 Hz9.8 m/s²--
Shock resistance

Compliant with JISC0041 standard

(147 m/s2, action time 11 ms, three sinusoidal half to wave pulses in each of X, Y, and Z directions)

EMC immunity levelZone B IEC 61131-2
Altitude requirements≤ 2000 m (80 kPa)
Protection levelIP20
GroundingDo not share the grounding with the power system

Software specification

Input point:

ItemSpecification requirements
Input port filtering time

As host extension: 0 ms to 64 ms (Unit: ms, default settings: 10), each group has 4 DI points, sharing the same filter parameters.

As LX6V-EMB(C)-ECAT extension: 0 to 640 (Unit: 100 us, default setting: 10), each group has 8 DI points, sharing the same filter parameters.

Input port anomaly detection and indicationN/A
Input channel logic level configurationN/A
Independent channel enable configurationN/A
Diagnostic reporting function configurationN/A
I/O MappingSupport three I/O mapping modes: bit access, byte access, word access

Output point:

ItemSpecification requirements
Output port anomaly detection and indicationN/A
Output channel logic level configurationN/A
Independent channel enable configurationN/A
Diagnostic reporting function configurationN/A
I/O mappingSupports three I/O mapping modes: bit access, byte access, word access

Instructions

This module is applicable to the LX6V series PLC and LX6V-EM-ECAT module device. The following is an introduction to these 2 usages.

Use on LX6V/LX6S

Upper computer expansion module configuration process instructions (Take the model LX6V-0808EXYT as an example).

① Double-click on the [Extension module configuration] to open the configuration interface;

② Double-click the corresponding module to add a new one according to the model and position of the modules connected to the current host.

③ Double-click the module in the current machine slot to open the [Module configuration] interface;

1795589074757-723.png

④ Configure modules sequentially: DI point filtering time and I/O mapping. Click [OK] and save the configuration;

22.jpg

33.jpg

Filter time: The default configuration filter time here is 10ms, configurable range: 0 to 64ms.

I/O Mapping: Module DI points and DO points are sequentially mapped to PLC DI10 to DI17, DO10 to DO17.

✎Note: Due to the current host LX6V-0808MT, DI0 to DI7 and DO0 to DO7 have been occupied by the host, so the module channel mapping device starts from DI10 and DO10 to allow configuration!

⑤ Click [Write to PLC], select extension functions on the interface in sequence, then click [Execute] to download the extension module configuration to the PLC.

44.jpg

Use in LX6V-EM□-ECAT module

1. Add EtherCAT device

According to steps ① to ④, right-click EtherCAT. Click [Add]→[Import] to import the ESI device description file.

1795589336494-754.png

Import completed. According to the following figure, select a coupler based on the current host connected module model and position (the figure below takes LX6V-EMB-ECAT as an example).

1795589361584-592.png

2. Configure module

Right-click the currently added coupler and add the extension module of the coupler loading in.

1795589398878-468.png

✎Note: When the configured module is not the actual loaded module, error report will not OP succeed!

3. Configuration module parameters

1795589432900-576.png

Module configuration

① 0808 EXY Digital input filter 8 bit: used to set the filtering time of 0808EXYT input point.

1. Default 1ms, unit: 0.1 ms

2. Configurable range: 0 to 64 ms

② 0808EXYT DO module CH0-8bit stop mode after EtherCAT lost link: Used to set 0808EXY output point to stop when EtherCAT drops;

DO STOP MODE:

1. 0: EtherCAT keeps output after disconnection

2. Non-0: Output with stop value after EtherCAT is disconnected.

③ 0808EXYT DO module 8bit stop value after EtherCAT lost link: Used to set the DO output value when EtherCAT is dropped at the 0808EXYT output point.

I/O mapping

IO module input and output points can be mapped into variables/device.

For example, the figure below shows mapping DO channel values to devices Y100 to Y107, and DI channels to devices Y100 to Y107.

1795589505219-756.png

Click "Save" and download to the PLC.

4. Object dictionary

ModelIndexSub-indexDescriptionData typeRangeAccessUnitDefaultName

LX6V-0808EXYT/

LX6V-0808EXYP

16#800016#010808EXYT/P digital input module: Filter time for bit0 to bit7UINT160 to 640W/R0.1ms100808EXYT/P Digital input filter time 8-bit
16#800116#01

0808EXYT/P digital output mode selection:

0: Keep output after EtherCAT disconnection;

Non-0: Use stop value after EtherCAT disconnection

UINT80 to 255W/R--2550808EXYT/P DO module CH0 8bit stop mode after EtherCAT lost link
16#800216#01Output value of 0808EXYT/P digital output after disconnectionUINT80 to 255W/R--00808EXYT/P DO module CH0 8bit stop value after EtherCAT lost link
16#A00016#00Module status informationUINT16--R----module status
16#01Version numberUINT16--R----version
16#02Error statusUINT16--R----run status
16#03Channel statusUINT16--R----channel status
16#600016#01Bit0 to bit7 indicates digital input CH0UINT80 to 255W/R----Digital input CH0 8-bit
16#700016#01Bit0 to bit7 indicates digital output CH0UINT80 to 255W/R----Digital output CH0 8-bit
LX6V-16EX16#800016#0116EX input module CH0 bit0 to bit7 filter timeUINT160 to 640W0.1ms1016EX Digital input filter time CH0
16#0216EX input module CH1 bit0-bit7 filter timeUINT160 to 640W0.1ms1016EX Digital input filter time CH1
16#600016#01Bit0 to bit7 indicates digital input CH0UINT80 to 255R----Digital input CH0 8bit
16#02Bit0 to bit7 indicates digital input CH0UINT80 to 255R----Digital input CH0 8bit

LX6V-16EYT/

LX6V-16EYP

16#800016#01

16EYT/ 16EYP digital output mode selection:

0: Maintain output after EtherCAT disconnection;

Non-0: Use stop value output after EtherCAT disconnection

UINT80 to 255W--25516EYT/P DO module CH0 stop mode after EtherCAT lost link
16#02UINT80 to 255W--25516EYT/P DO module CH1 stop mode after EtherCAT lost link
16#800116#0116EYT/ 16EYP digital output value after disconnectionUINT80 to 255W--016EYT/P DO module CH0 stop value after EtherCAT lost link
16#01UINT80 to 255W--016EYT/P DO module CH1 stop value after EtherCAT lost link
16#A00016#00Module status informationUINT16--R----module status
16#01Version numberUINT16--R----version
16#02Error statusUINT16--R----run status
16#03Channel statusUINT16--R----channel status
16#700016#01Bit0 to bit7: Digital output CH0UINT80 to 640W/R0.1ms10Digital output CH0 8-bit
16#02Bit0 to bit7: Digital output CH1UINT80 to 640W/R0.1ms10Digital output CH1 8-bit
LX6V-1616EXYT/LX6V-1616EXYP16#800016#011616EXYT/1616EXYP input module CH0 bit0 to bit7 filter timeUINT160 to 640W/R0.1ms101616EXYT/P Digital input filter time CH0 8-bit
16#02UINT160 to 640W/R0.1ms101616EXYT/P Digital input filter time CH1 8 bit
16#800116#01

1616EXYT/1616EXYP digital output mode selection:

0: Maintain output after EtherCAT disconnection;

Non-0: Use stop value output after EtherCAT disconnection

UINT80 to 255W/R--2551616EXYT/P DO module CH0 8-bit stop mode after EtherCAT lost link
16#02UINT80 to 255W/R--2551616EXYT/P DO module CH1 8-bit stop mode after EtherCAT lost link
16#800216#01LX6V-1616EXYT/LX6V-1616EXYP digital output value after disconnectionUINT80 to 255W/R--01616EXYT/P DO module CH0 8-bit stop value after EtherCAT lost link
16#800216#02UINT80 to 255W/R--01616EXYT/P DO module CH1 8-bit stop value after EtherCAT lost link
16#A00016#00Module status informationUINT16--R----module status
16#01Version numberUINT16--R----version
16#02Error statusUINT16--R----run status

LX6V-32EYT/

LX6V-32EYP

16#800016#01

32EYT/P digital output mode selection:

0: Maintain output after EtherCAT disconnection;

Non-0: Use stop value output after EtherCAT disconnection

UINT80 to 255W--25532EYT/P DO module CH0 stop mode after EtherCAT lost link
16#02UINT80 to 255W--25532EYT/P DO module CH1 stop mode after EtherCAT lost link
16#03UINT80 to 255W--25532EYT/P DO module CH2 stop mode after EtherCAT lost link
16#04UINT80 to 255W--25532EYT/P DO module CH3 stop mode after EtherCAT lost link
 16#0132EYT/P digital output value after disconnectionUINT80 to 255W--032EYT/P DO module CH0 stop value after EtherCAT lost link
16#02UINT80 to 255W--032EYT/P DO module CH1 stop value after EtherCAT lost link
16#03UINT80 to 255W--032EYT/P DO module CH2 stop value after EtherCAT lost link
16#04UINT80 to 255W--032EYT/P DO module CH3 stop value after EtherCAT lost link
16#A00016#00Module status informationUINT16--R----module status
16#01Version numberUINT16--R----version
16#02Error statusUINT16--R----run status
16#03Channel statusUINT16--R----channel status
16#700016#01Bit0 to bit7 indicates digital output CH0UINT80 to 255W----Digital output CH0 8-bit
16#02Bit0 to bit7 indicates digital output CH1UINT80 to 255W----Digital output CH1 8-bit
16#02Bit0 to bit7 indicates digital output CH2UINT80 to 255W----Digital output CH2 8-bit
16#02Bit0 to bit7 indicates digital output CH3UINT80 to 255W----Digital output CH3 8-bit
LX6V-32EX16#800016#0132EX input module CH2 bit0 to bit7 filter timeUINT160 to 640W0.1ms1032EX Digital input filter time CH0
16#0232EX  input module CH3 bit0 to bit7 filter timeUINT160 to 640W0.1ms1032EX Digital input filter time CH1
16#0232EX  input module CH3 bit0 to bit7 filter timeUINT160 to 640W0.1ms1032EX Digital input filter time CH2
16#0332EX  input module CH3 bit0 to bit7 filter timeUINT160 to 640W0.1ms1032EX Digital input filter time CH3
16#600016#01Bit0 to bit7 indicates digital input CH0UINT80 to 255R----Digital input CH0 8-bit
16#02Bit0 to bit7 indicates digital input CH1UINT80 to 255R----Digital input CH1 8-bit
16#03Bit0 to bit7 indicates digital input CH2UINT80 to 255R----Digital input CH2 8-bit
16#04Bit0 to bit7 indicates digital input CH3UINT80 to 255R----Digital input CH3 8-bit

Example

1. Use on LX6V/LX6S host

1795589626922-113.png

Description:

① After configuring the module and I/O mapping using the extension module configuration interface, the status of module X point or module Y point can be directly monitored through the ladder diagram;

② When M0 is set to ON, Y10 to Y27 will be set to the 16-bit status of D50.

2. Use on the LX6V-EM□-ECAT module

1795589648394-159.png

Description:

① In the configuration interface of the LX6V-0808EXYT [Expansion module] under the LX6V-EMB-ECAT coupler, configure the module and map the I/O output points to D0 and the input points to D1, then, the status of module X points or Y points can be directly monitored via ladder diagrams.

1795589677220-765.png

② When M0 is ON, the 8 output points of the LX6V-0808EXYT expansion module attached to the LX6V-EMB-ECAT coupler will be set to the lower 8 bits of D50.

Error code

Error codeDescriptionActionSolutionTest time
7080Extension module and checksum errorKeep runningDetect the link between the extension module and the host or whether there is external interferenceWhen instruction running
7081Abnormal communication message of extension moduleKeep runningDetect the link between the extension module and the host or whether there is external interferenceWhen instruction running
7083extension module access abnormalKeep runningDetect the link between the extension module and the hostWhen instruction running