How to Calibrate AI Analog?

Version 1.1 by Theodore Xu on 2023/08/14 16:30

  1. Check F7.11 and enter the value to FF.00
  2. Set FF.11 = 111 then modify AC.00, AC.01, AC.04, AC.05 for 0, modify AC.02, AC.03, AC.06, AC.07 for 10.000 .
  3. Calibrate AI1: AI1 does not access the voltage, check D0.09 display voltage, put the display value you see into AC.01, then give 10V voltage, put the display value you see into AC.03.
  4. Calibrate AI2: AI2 does not access the voltage, check D0.10 display voltage, put the display value you see into AC.05, then give 10V voltage, put the display value you see into AC.07.