How to Calibrate AI Analog?
Version 3.1 by Theodore Xu on 2023/08/26 16:49
Operating steps
- Check F7.11 and enter the value to FF.00
- Set FF.11 = 111 then modify AC.00, AC.01, AC.04, AC.05 for 0, modify AC.02, AC.03, AC.06, AC.07 for 10.000 .
- Calibrate AI1: AI1 does not access the voltage, check D0.09 display voltage, put the display value you see into AC.01, then give 10V voltage, put the display value you see into AC.03.
- Calibrate AI2: AI2 does not access the voltage, check D0.10 display voltage, put the display value you see into AC.05, then give 10V voltage, put the display value you see into AC.07.